● For power supply systems that are critical to signicant economic interests or
public order, such as the national computing center, military command
system, emergency command center, railway signal system and control center,
civil aviation and air trac control center, airport command center, nancial
clearing center, and transaction center, the Tier 4 or 3 power architecture
specied in TIA-942 must be used. That is, two power supplies must be used
to supply power to loads.
● If the root mean square (RMS) of the mains voltage exceeds 320 V AC, the
UPS may be damaged.
● A UPS can be used to serve resistive-capacitive loads, resistive loads, and
micro-inductive loads. It is recommended that a UPS not be used for pure
capacitive loads, pure inductive loads, and half-wave rectication loads. A UPS
does not apply to regeneration loads.
● The UPS can be congured with a backfeed protection dry contact to work
with an external automatic circuit breaker, preventing the voltage from
owing back to input terminals over static bypass circuits. If the installation
and maintenance personnel do not need backfeed protection, paste labels on
external mains and bypass input switches, informing that the UPS is
connected to a backfeed protection card. Disconnect the backfeed protection
card from the UPS before operating the UPS.
Environmental Requirements
● The UPS operating environment must meet the requirements for the climate
indicator, mechanically active substance indicator, and chemically active
substance indicator in ETSI EN 300 019-1 class 3.6.
● Ensure that the equipment is used in an environment that meets the product
design specications (including power grid, temperature, and humidity).
Otherwise, the equipment may become faulty, and the resulting equipment
malfunction and component damage are not covered under the warranty.
● After unpacking the UPS, you are advised to power it on as soon as possible.
If the UPS is not in operation, take appropriate measures to prevent moisture,
dust, and foreign matter from entering the UPS.
● Any operation on any electrical equipment in an environment that has
inammable air can cause extreme danger. Strictly obey the operating
environmental requirements specied in related user manuals when using or
storing the equipment.
● Do not use the UPS in the following places:
– Environments that are close to ammable or explosive materials, dust,
corrosive gases or dust, conductive or magnetic dust, abnormal vibration,
or collision
– Rooms or outdoor environments where temperature and humidity are
not controlled (with high temperature, low temperature, moisture, direct
sunlight, or heat sources)
–Non-conned environments near the ocean (0–3.7 km) and indoor or
semi-indoor environments where the temperature and humidity are not
controllable, such as simple equipment rooms, civil houses, garages,
corridors, and direct ventilation cabinets near the ocean; or houses with
only roofs, railway station platforms, gymnasiums, and aquariums
– Environments that are conducive for the growth of microorganisms such
as fungus or mildew
UPS2000-G-6KRTLL
User Manual 1 Safety Information
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 4