Electrical Connections (All Models)
Ceiling (Top) Mount
Wall Mount (Back Power Feed)
IMPORTANT: Two grounding pigtail leads are provided. In ceiling mounted applications, both grounding
pigtails must be properly connected to building utility ground for safety reasons.
1
1.
.Attach unit housing to back plate
by plastic hinge straps provided.
To complete installation, see Final Assembly instructions on back page.
Grounding
pigtail leads
(Refer to
“IMPORTANT”
note below)
COMBO UNIT INSTALLATION INSTRUCTIONS
1
1.
.Remove center 3/4” K.O. in unit back
plate.
2
2.
.Remove appropriate back plate K.O.s for
electrical box screws.
3
3.
.Feed wires through center K.O. and
mount back plate to electrical box.
4
4.
.Using appropriate hardware, mechanically secure unit backplate to wall
surface through keyhole K.O.s
1
1.
.Feed building wires through threaded
nipple in ceiling mount base plate and
affix the plate to electrical box using
screws provided with box.
2
2.
.Attach unit
mounting bracket
to screw studs in
base plate using
two screws pro-
vided.
3
3.
.Remove 4 appropriate
K.O.s in unit back plate
mounting pattern and
3/4” K.O. in unit back
plate top flange.
4
4.
.Place unit back plate onto screw studs in bracket assembly and secure with #8 lock-
ing hardware provided. Make sure threaded nipple (used as wiring channel) extends
from base plate through the 3/4” hole in unit back plate top flange. 33..Connect remote lighting load to yellow and blue (fused)
pigtail leads provided (remote capacity models only).
4
4.
.Route ribbon cable through housing
as shown and plug connector into
LED printed circuit board assembly.
2
2.
.Connect building wires to transformer leads.
• Black and white wires for 120V
(Use wire nut to cap off red wire)
• Red and white wires for 277V
(Use wire nut to cap off black wire)
• Brown and blue wires for 220/240V
• Make proper connection to ground
5
5
.
.
Fire Alarm Panel Option (-FAP)
Connect two violet pigtail leads from flasher
module on PC board to appropriate 24 volt AC or
DC fire alarm panel. Wiring connections may be
made inside unit housing or within electrical box.
Battery Installation and Connections
On models shipped with battery uninstalled, check that battery
security strap is positioned as shown above.
Battery Security Strap
Lead-Calcium Battery Models
1) Place battery in housing as shown above in front of security
strap.
2) Fasten by tightening security strap.
Battery Connections:
Connect yellow circuit board
lead to battery negative (–)
terminal.
Note: On factory installed
batteries, yellow battery lead
is shipped connected.
Connect red circuit board
lead to battery positive (+)
terminal.
Nickel-Cadmium Battery Models
1) Remove double-sided tape protective layer on bottom of
battery assembly.
2) Position battery in housing in front of security strap as
shown above and press battery firmly in place.
3) Fasten by tightening security strap.
Battery Connections:
Connect battery harness
leads from circuit board to
corresponding leads from
battery assembly.