General Operation
Familiarize yourself with the Control Box. We have created a simple to use 4 BUTTON user interface,
consisng of a UP, STOP, DOWN, and LEVEL buons. These are the basic funcons for the oper-
ang the HarborHoistTM G1.5 li. Internal to the Control are state of the art valve controls and circuitry
that will insure that your li comes up level each and every me you li your boat from the water.
Lowering the Li:
• Make sure the Power LED is illuminated and ashing
• Press the DOWN buon. This will open the valves.
• Allow the li to submerge (Walkways will remain above water)
• Une li safety lines from boat
• Everyone may board the boat aer the boat clears the li
Raising the Li:
• Float boat into established pick up posion on li
• Tie o safety lines to the boat
• Everyone must exit the boat before liing.
• Press UP buon
• Once the li is fully raised, air bubbles will be visible exing from all tanks.
• Press STOP on Control
Leveling the Li:
In the raise funcon the controller will keep the li within ±2 degrees for speed of operaon. If the li
needs to be leveled once all the way up, press the yellow LEVEL buon and the li will automacally
level the li. The controller will release air our of the appropriate tank(s) to level the li within ± 0.5 de-
grees.
Beyond Level Limits Lockout:
In the instance where the li would get out of level by ±10 degrees or greater, which could occur over
me do to a burping reacon or if the air system springs a leak, the controller will lock itself out and not
allow any addional funconality . The CENTER PORT and STARBOARD LED’s on the controller will ash
back and forth. To UNLOCK CONTROLLER:
• Press STOP buon to clear lockout error
• Press LEVEL and DOWN buons together and hold for 5 seconds. All PORT and STARBOARD LED’s will
turn on indicang all air valves are open allowing the li to submerge. When the li is completely
submerged you can then re-li the vessel by pressing the UP buon
If this issue persists have the air system inspected for leaks.