Hytek TA3A.P Instruction manual

S826/6
Technical Data
HYTEK ATEX APPROVED
TANK ALARM
Applies to the following models only:
- TA3A.P - TA3A.PR
- TA3A.B - TA3A.BR
Please read carefully before commencing installation
Registered Office: HYTEK (GB) LIMITED, Delta House, Green Street, Elsenham, Bishop’s Stortford
CM22 6DS UK. Registered in England No. 1915382
Web: www.hytekgb.com

S826/6
ENVIRONMENTAL INFORMATION
European Directive 2012/19/EU requires that the equipment bearing
this symbol on the product and/or its packaging must not be disposed
of with unsorted municipal waste. The symbol indicates that this
product must be disposed of separately from regular household waste
streams. It is your responsibility to dispose of this and other electric
and electronic equipment via designated collection facilities appointed
by the government or local authorities.
PRODUCT DESCRIPTION
The Hytek Tank Alarm is designed to provide visual and audible alarms
whenever a predetermined level in a storage tank is reached.
The system consists of a maximum of three-weighted float switches and
an enclosure weatherproof to an IP54 standard which contains the visual
and audible alarms and the electronic PCB.
This alarm is approved to operate with flammable liquids classed as
category 1, 2 or 3 in accordance with European Regulation No. 1272/2008.
It is ATEX certified in accordance with EN 60079-0:2012 and EN 60079-
11:2012. It is also IECEx certified in accordance with IEC 60079-0:2011 Ed
6 and IEC 60079-11:2011 Ed 6.
The alarm box, featuring the warning devices and test/mute buttons, must
be located outside any hazardous zone and bears the following certification
marking and number:
The float sensor(s) can be located in hazardous zones 0,1 or 2 and bears
the following certification marking and number:
CML 16ATEX2355X
IECEx CML 16.0128X
CML 16ATEX2356X
IECEx CML 16.0129X
II 1 G
Ex ia IIA T3 Ga
-
20°C to +40°C
CML16ATEX2355X
IECEx CML 16.0128X
II 1 G
[Ex ia IIA Ga]
-20°C to +40°C
2503

S826/6
CONDITIONS OF CERTIFICATION
1. Due to safety critical internal creepage and clearance distances in the
control unit, if installed in a location other than a clean and dry
environment, the user shall ensure that the control unit is additionally
provided with protection having an ingress protection rating of at least
IP54 and is maintained throughout the lifetime of the equipment.
2. The float switch incorporates an isolated metal part which could
become either charged in use or be a discharge point for charged
liquids upon filling or emptying. The float switch shall only be used in
applications where static generated via contact liquids are controlled so
not to be considered an ignition source.
3. The relay contacts in normal operation shall not switch more
than 5Arms, 250Vrms or 100VA in accordance with IEC 60079-11:2011
Clause 6.3.14.
4. Where applicable, only alkaline batteries of the same make shall be
used as replacements. All batteries shall be replaced at the same
time.
IMPORTANT WARNING NOTES
1. This alarm is designed for use with liquids classed as category 1, 2 or 3
in accordance with European Regulation No. 1272/2008, including
petrol, diesel, gas oil, water, hydraulic oil and heating oil. It can be used
with Anti-freeze or Adblue if the optional stainless steel float switch
assembly is fitted.
2. The alarm box featuring the warning devices and test/mute buttons
must not be installed in a hazardous zone or below ground level. The
float sensor can be located in zones 0, 1 or 2 with the supplied
connecting wire running to the alarm box.
3. The user must ensure that chemicals present in the atmosphere do not
affect the performance or degrade the polycarbonate enclosure.
4. Only the correct ATEX/IECEx certified float switches supplied by Hytek
can be used with the Tank Alarm.
5. Installation of this equipment and its associated tank, pipe work and
fittings should only be carried out by qualified fuel installation
engineers.

S826/6
6. The installation must be carried out in accordance with the
requirements of EN 60079-14 the latest relevant electrical and local
authority regulations and standards.
7. It must not be used with any liquids or applications other than those
specified. We will accept no warranty claims or liability if it is used for
other liquids or applications.
8. This product must not be used if it is damaged.
SPECIFICATION
MAINS VERSION
- 230V 3-channel alarm.
- IP55 weatherproof enclosure, for outside mounting.
- Each channel can be used as an overfill, low level or bund alarm.
- High power alarm sounder.
- High visibility flashing zenon beacon.
- Test button checks float switches as well as beacon & sounder.
ATTERY VERSION
- Battery 3 channel alarm.
- Each channel can be used as an overfill, low level or bund alarm.
- High power alarm sounder.
- No zenon beacon, but individual channel LED’s.
- Test button checks float switches as well as batteries & sounder.
- Battery life depends on number of test & alarm incidents.
INSTALLATION INSTRUCTIONS
MOUNTING
The float switch assembly is supplied with 5 metres of 2-core PUR fuel
resistant cable that may be extended, as necessary, up to 100 metres.
1. Remove front display lid from alarm box and disconnect ribbon cable.
Place the lid somewhere clean and safe.
2. Using wall-mounting bracket, fix alarm box into position.
3. Self-adhesive product labels are supplied and are to be fixed alongside
the corresponding channel LED indicator on the front of the alarm unit.

S826/6
POWER SUPPLY
4. The TA3A.P and TA3A.PR are designed to have a continual 230V AC
supply fused at a rating of 6 amps max. The TA3A.B and TA3A.BR
have an internal battery power supply. See Connections diagram.
CONNECTIONS DIAGRAM
FLOAT SWITCH INSTALLATION
5. To ensure the float switch is positioned at the correct depth in the tank,
locate the gland, fitted to the gland plate, at the appropriate point along
the float switch cable.
Carefully install float switch through a 30mm hole in the top of the tank,
ensuring the sealing gasket is in place. Secure the gland plate to the
tank using two self-tapping screws (not supplied). See Float switch
installation diagram (page 3). Alternatively, for steel tank installations,
an optional 11/2” brass cap (Hytek order ref - TA.CAP) can be used.
NB: Installation of the float switch should be as far away from the fill
point of the tank as possible
.

S826/6
FLOAT SWITCH INSTALLATION DIAGRAM
FLOAT SWITCH ACTIVATION AND CONFIGURATION
6. Connect the float switch cables to the float switch terminals inside the
alarm box as per connections diagram.
7. After connecting the desired amount of float switches, activate the
corresponding channels by setting the appropriate channel activation
dipswitch to "ON" position. See Dip switch settings diagram.
NB: If a channel activation dipswitch is in the "OFF" position and a
float switch connected to the corresponding terminals is operated,
the alarm will not function.
8. Set the high/low level dipswitches to the appropriate position (NORM =
high level activation, INVERT = low level activation) to enable the
corresponding float switches to detect either a high or low-level situation.
See Dip switch settings diagram.

S826/6
DIPSWITCH SETTINGS DIAGRAM
EXTERNAL RELAY OUTPUTS
9. Where external output relays have been fitted connect external cabling
as per connections diagram. The relay contacts are rated at 250 volts, 5
amps / 100VA max.
NB: The relays are a switch only and do not offer a power source for
any external equipment. The relays MUST NOT be used to activate any
equipment such as fuel pumps or safety valves.
COMPLETION OF INSTALLATION
10. Install batteries provided (TA3A.B & TA3A.BR Only).
11. Refit lid to alarm box ensuring that ribbon cable is reconnected to the
main PCB and the lid seal is in place.
12. Switch on power. The green "POWER" LED should illuminate
(TA3A.P, TA3A.PR only).
OPERATION
(HIGH LEVEL) (LOW LEVEL)

S826/6
POWER STATUS
MAINS VERSION: The Power LED will remain illuminated to indicate that
there is mains power to the unit
BATTERY VERSION: The Battery LED will flash every 2 seconds to
indicate that there is battery power to the unit. If the battery charge is too
low then the sounder will activate intermittently to indicate this.
ALARM CONDITION
When a high or low-level alarm condition occurs the corresponding channel
LED on the tank alarm lid is illuminated and the sounder/beacon will
activate. The external relay will also be activated.
FLOAT SWITCH FAULT INDICATION
If any of the channel LEDs flashes repeatedly then this indicates a fault
with the float switch.
ALARM MUTE
Pressing the mute button for 1.5 seconds will silence the sounder and stop
the beacon flashing when an alarm condition is occurring. This will not de-
activate any relays (if fitted). The relays will only be de-activated when float
switch returns to its normal position.
If the mute button is not depressed the sounder will silence after 20
minutes leaving the beacon and channel LED on.
The channel LED will remain on until the alarm condition has been rectified
(float switch returns to its normal position).
ALARM TEST
To test the Tank Alarm, push and hold the test button on the lid. If the Tank
Alarm is functioning correctly the sounder should activate, the beacon will
flash (if fitted) and all activated channel LEDs will illuminate.
If any of the channel LEDs flashes repeatedly then this indicates a fault
with the float switch.
Battery version: If no sounder is heard and no channel LED’s illuminate,
check batteries and change as necessary.
NB: Always push the Tank Alarm test button before filling the tank.

S826/6
FITTING DIMENSIONS

S826/6
PARTS LIST
HYTEK TANK ALARM PARTS LIST
REF. PART NUMBER PART DESCRIPTION
1▼
TA3A.LID Tank alarm lid with all components -
MAINS
►
TA3A.LID.BAT Tank alarm lid with all components -
BATTERY
2 TA.BEACON Tank alarm amber beacon
3▼
TA3A.LABM Display lid label (mains)
►
TA3A.LABB3 Display lid label (battery)*
4 TA.SOUND Tank alarm sounder
5 TC.AT Tank alarm test button
6 TC.AS Tank alarm mute button
7 TA.GLND Cable gland PG7*
8 TA3A.BOX Tank alarm box (base only)
9▼
TA3A.PCBMR Alarm PCB 230Vac with Relays*
►
TA3A.PCBM Alarm PCB 230Vac*
►
TA3A.PCBR Alarm PCB 6Vdc Battery with Relays*
►
TA3A.PCBB Alarm PCB 6Vdc Battery*
10 TA.CONM Plug connector (230/110v mains)*
11 TA.CONR Plug connector (relays)*
12 TA.CONF Plug connector (floats)*
13 BLANK.12.7 12.7mm hole blank *
14 TA.LABP Product label (9 labels per sheet) *
15 TA.PCBDISP Alarm display PCB*
*not shown
SPARES
PART NUMBER DESCRIPTION
TA.FA5 5m universal float switch
TA.FA10 10m universal float switch
TA.FA.SS5 5m stainless steel float switch
TA.CAP 1 ½” threaded brass cap for steel tanks
TA.CABLE Extra cable to extend float switches
TA.CABEXT Use to join extra cable - IP68 rated
TA.BATTERY Type D battery (4 per unit)

S826/6
OUTSIDE VIEW
2
4
5
6
8
1
3
TA3A.P (230V AC) - SHOWN

S826/6
E.U. DECLARATION OF CONFORMITY
Company Name: Hytek (GB) Ltd
Address: Delta House, Green Street. Elsenham,
Bishops Stortford, Hertfordshire, CM22 6DS, UK
Date of Issue: 5
th
May 2017
Equipment Details: Hytek ATEX Tank Alarm
TA3A.P, TA3A.PR, TA3A.B, TA3A.BR
Applicable Directives: 2014/30/EU EMC Directive
& Standards EN 61326-1:2013
Electromagnetic compatibility (EMC) – Group 1, Class B Eq. (Emissions)
EN 61326-1:2013
Electromagnetic compatibility (EMC) – Industrial Environment (Immunity)
2014/35/EU Low Voltage Directive
2006/42/EC Machinery Directive
2012/19/EU Waste Electrical & Electronic Equipment Regulations
2011/65/EU Restriction of Hazardous Substances Directive (RoHS2)
2014/34/EU ATEX Directive
ATEX - EN 60079-0:2012 +A11:2013 and EN 60079-11:2012
IECEx - IEC 60079-0:2011 Ed 6 and IEC 60079-11:2011 Ed 6
EC Type examination Certificate No.:CML 16ATEX2355X
IECEx CML 16.0128X
Marking:
Alarm Box: Float Sensor
Notified Body: CML Ltd. Unit 1 Newport Business Park,
New Port Road, Ellesmere Port, CH65 4LZ UK
Notified Body Number CML 2503
Declaration Number: EU130/3
On behalf of the above named company, I declare under our sole responsibility that, on the date the
equipment accompanied by this declaration is placed on the market, the equipment conforms with all
technical and regulatory requirements of the above listed directives.
Clive Wellings, Technical Manager
THE INFORMATION CONTAINED IN THIS DOCUMENT IS PROTECTED BY COPYRIGHT © AND PROPERTY LAWS
AND IS THE SOLE PROPERTY OF HYTEK (GB) LTD. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT
THE WRITTEN PERMISSION OF HYTEK (GB) LTD IS PROHIBITED.
CML16ATEX2355X
IECEx CML 16.0128X
II 1 G
[Ex ia IIA Ga]
-20°C to +40°C
2503
CML 16ATEX2355X
IECEx CML 16.0128X
CML 16ATEX2356X
IECEx CML 16.0129X
II 1 G
Ex ia IIA T3 Ga
-
20°C to +40°C
This manual suits for next models
3
Table of contents
Popular Security System manuals by other brands

Honeywell
Honeywell Tuxedo Touch Wi-Fi user guide

CMX
CMX EVAC-500 Installation and operation manual

Alarmtech
Alarmtech HB 120 Installation instruction

Honeywell
Honeywell LYNX Touch Series Installation and setup guide

2gig Technologies
2gig Technologies GO!control 2GIG-CNTRL2 user guide

Sygonix
Sygonix 2523277 operating instructions

SEON
SEON Trooper Basic TR1-10 Quick reference guide

Metra Electronics
Metra Electronics Spyclops PRO MTH1295 quick start guide

Bosch
Bosch Plena Power Amplifier Software manual

IMOU
IMOU Alarm Station quick start guide

Powerex
Powerex FirstCall AAP7 operating & maintenance manual

Secure Care
Secure Care Advantage 500DE installation manual