manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. IDEAL
  6. •
  7. Cables And Connectors
  8. •
  9. IDEAL APP SBE 320 User manual

IDEAL APP SBE 320 User manual

1. CONNECTOR RATINGS
2. TOOLING CHART
3. REDUCING BUSHING
SBE®320 & SBX®350 Connectors
Assembly instruction for SBE160, SBE320, SBX175 and SBX350 Series two pole battery connectors with option for
auxiliary contacts.
FOR INSTALLATION BY A QUALIFIED ELECTRICIAN IN ACCORDANCE WITH NATIONAL AND
LOCAL ELECTRICAL CODES AND THE FOLLOWING INSTRUCTIONS. THE SUITABILITY OF
THIS TYPE OF TERMINATION MUST BE EVALUATED BY UNDERWRITERS’ LABORATORIES,
INC.AND CANADIAN STANDARDS. ASSOCIATION FOR THE END USEAPPLICATION: Assemble
contactstothe cablesaccordingto theequipmentmanufacturer’sassemblyinstructions.Thefollowing
instructions are supplied as a reference. Please note: instructions are included with each crimp tool
for proper use.
Max Cable Size
Series Amperes Volts AWG mm²
SBE160 160 150 1/0 50
SBE320 320 150 350 mcm 185
SBX175 175 600 1/0 50
SBX350 550 600 350 mcm 150
Bushing Wire Size For Use With
Part Number AWG (mm²) SBE160 / SBX175 SBE320 / SBX350
5687 #1 (42.4) 6384G1 contact 6354 contact + 5918 bushing
5690 #2 (33.6) 6384G1 contact 6354 contact + 5918 bushing
5693 #4 (21.2) 6384G1 contact 6354 contact + 5918 bushing
5663 #6 (13.3) 6384G1 contact 6354 contact + 5918 bushing
5648 #10 (5.3) 6384G1 contact 6354 contact + 5918 bushing
5920 N/A(16) 6384G2 contact 6394 contact
5918 1/0 (53.5) N/A 6354 contact
Contact Wire Pneumatic Dieless
Part Number Size Bench Tool + Die + Locator or Hydraulic Tool
6384G2 35 mm² 1387G1 1388G3 1389G3 1368
6384G1 1/0AWG 1387G2 1303G2 1304G2 1368
6354 2/0AWG 1387G1 1388G2 1389G2 1368
6354 2/0AWG 1387G2 1303G12 1304G28 1368
6355 3/0AWG 1387G2 1303G12 1304G31 1368
6356 4/0AWG 1303G12 1303G12 1304G31 1368
6358 300 MCM N/A N/A N/A 1368
6358 350 MCM N/A N/A N/A 1368
1341G1 50 mm² 1387G2 1303G8 1304G35 1368
1341G2 70 mm² 1387G2 1303G7 1304G27 1368
1341G3 95 mm² 1387G2 1303G12 1304G35 1368
Contains one (1) housing and two (2) contacts.
4. CABLE STRIPPING DIMENSIONS FOR PRIMARY POWER CONTACTS
CAUTION: When using cable with jacket diameter less than 0.423 inches (11mm) on the SBE160 / SBX175 and less than 0.709 inches
(18mm) on the SBE320 / SBX350 thin wall heat shrink insulation should be evenly applied. For SBX350/SBE320 using a cable with a
jacket diameter over 1.00” [28mm], it will not fit into the connector. Shrink tube should be applied.
SHRINK WRAP USAGE
• For SBE160 / SBX175 - When using a cable with a jacket diameter of (.420/11mm) or smaller the following Shrink tubing
should be applied per instructions: to insure finger protection.
• For SBE320 / SBX350 - When using a cable with a jacket diameter of (.700/18mm) or smaller the following Shrink tubing
should be applied per instructions: to insure finger protection.
• For SBE320/SBX350 - When using a cable with a jacket diameter over (1/25mm) or larger the following shrink tubing should
be applied per instructions: to insure finger protection.
Use Shrink wrap with a diameter (A) with 2:1 shrink ratio
• Operating temp -30 to +105°C (or higher)
• min. shrink temperature 80°C
• Recovered wall thickness (B)
• Cut shrink wrap to (C)
• Place shrink wrap over crimped contact as shown (D).
• Align edge of shrink wrap tubing to the bottom of the last crimp as shown (D).
• Heat shrink wrap as required to form around the contact, cabling and the cable’s insulation.
6. RECOMMENDED SOLDERING TECHNIQUES
(Use rosin flux solder only). Wrap cable strands, melt solder into well; heat and insert stripped cable. Continue heating well until solder
flows into wire being careful not to over flow onto contact surfaces. DO NOT SOLDER DIP CONTACTS when contacts are soldered to
unsupported lead. Underwriters’ Laboratories, Inc. requires use of cable clamps, listed in table below.
Connector For Two Single
Ampere Rating Conductor Cables
SBE320 / SBX350 911G2
SBE160 / SBX175 945G2
SBE160/SBX175 SBE320/SBX350 SBE320/SBX350
0.420 / 11mm 0.700 / 18mm 1.00 / 25mm
A0.71 / 18mm 0.95 / 24mm 1.57 / 40 mm
B0.04 in / 1.1 mm 0.04 in / 1.1mm 0.051 / 1.3mm
C0.5 in / 13mm 0.5 in / 13mm 3 in / 76 mm
D1 & 1A 1 & 1A 2 & 2A
Figure 2
Figure 2A
(76.2 mm) 3 inches
Figure 1A
Figure 1
Connector Strip “X” To
Series Inches mm
SBEX350 / SBE320 1 3/8 35
SBEX350 / SBE320 1 1/8 29
SBEX350 / SBE320 2 1/2 64
With 350MCM Cable
X
7. CABLE / CONTACT & HOUSING ASSEMBLY
Observing polarity of markings, push each contact into rear of housing until notched side snaps over spring, tug on cable to make sure
contact is locked into place.
DISASSEMBLING CONNECTORS (see illustration)
Switch off power first. Remove contact by inserting extraction tool (cat. no. SBE160 / SBX175 - 969P1, SBE320 / SBX350 - 970P1) as
shown below (steps 1, 2, & 3).
CAUTION: Replace contacts individually on battery leads to reduce potential danger of shorting.
1. Insert extraction tool as shown between contact and housing to pointA.
2. Press down to release contact from spring.
3. Pull cable to remove contact.
3. Pull cable to remove contact.
Contains two each of : housings, contacts, retaining pins & cable ties.
1. Single conductors use #12 to #18AWG wire only. Strip to 0.31 inch (7.9 mm) off end of insulation.
2. Twin conductorcable #12to #18.Strip backouter jacket5.50 inches(139 mm).(See illustration).Then strip conductor insulation as in
(figure 1).
3a.To crimp: use the recommended tool. Crimping by other means may disturb contact position in housing and or produce high
resistance joints.
3b. To Solder: Not recommended.
Extraction Tool
2
3
PointA
Extraction Tool
Catalog Wire Retaining
Number Application Contact Size Pin Length
6344 SBE80,SBE160,SBO60, SBX175 1331 #12/16 0.85
6305G1 SBE320, SBX350 1331 #12/16 1.00
6310G1 SBE320, SBX350 1332 #16/20 1.00
Crimp Tool Catalog Number
Manual - cycle controlled 1309G2
Pneumatic - cycle controlled 1367G1
ASSEMBLY INSTRUCTIONS
NOTE: These assembly instructions apply only to the catalog numbers listed below
(SBE®, SBX®, SBO®).
[139]
5.5
[7.9]
0.31
Figure 1
4. Thread or push one or two auxiliary contacts and wires through the rear of the connector before inserting into auxiliary housings.
Push into auxiliary housings through rear until notched side of contact tip snaps over spring. Tug wires to make sure wires are secure.
5.SlidetwoauxiliaryPowerpole®housingstogether by dovetails to stack vertically.They cannot be inserted separately into SBE / SBX
housing. The rear of each of the Powerpole housings must be flush.
6. Slide stacked auxiliaries back into connector housing until seated. The male dovetail should be on top as shown in (figure 1). Make
sure side grooves of auxiliaries are aligned for retaining pins and insert tubular pins. Tap pins in holes from top, as shown in (figure 1).
7. Cable ties are supplied to secure the auxiliary leads or cable to one of the main power cables. Leave slack or loop in leads to
Powerpole®contacts when applying cable ties. Wraps to be placed approximately 1 inch (25.4 mm) apart as shown in (figure 2).
8. To remove auxiliary housings, punch out retaining pins from bottom of the connector housing with an 0.06 inch (1.5 mm) diameter
steel rod or pin driver. Pull auxiliary housings out of the SBE®/SBX®connector housing. Use contact insertion-extraction tool kit (part
number 111038G2), to remove contacts from auxiliary housings see (figure 3).
WARNING: UTMOST CAUTION SHOULD BE USED WHEN WORKING ON LIVE CONNECTOR CONTACTS
UL and CSAReference - These connectors are recognized under the component program of Underwriters’ Laboratories, File E26226,
as well as Canadian StandardsAssociation, Report LR25154.
© 2019Anderson Power Products, Inc. All rights reserved. APP®,A®,Anderson Power Products®, SBE®, SBX®, SBO®, Powerpole®and
theAPPLogoareregistered trademarksofAndersonPower Products,Inc. Anderson™isa trademarkofAndersonPower Products,Inc.
Anderson™ will use reasonable efforts to include accurate and up-to-date content in the assembly instruction. All product information
contained in the instruction sheet including ordering information, illustrations, specifications, and dimensions, are believed to be reliable
as of the date of publishing, but is subject to change without notice.Anderson™ makes no warranty or representation as to its accuracy.
Contentinthe instruction sheet maycontaintechnicalinaccuracies,typographical errors and may bechangedorupdatedwithout notice.
Anderson™ may also make improvements and/or changes to the products and/or to the programs described in the content at any time
without notice. Current sales drawings and specifications are available upon request.
HEADQUARTERS: AndersonPower Products®,13Pratts Junction Road, Sterling, MA01564-2305 USA www.andersonpower.com
All Data Subject To Change Without Notice 2019-0013, 1S6556 REV 4
Retaining Pin
Top
Male Dovetail
Figure 1
Loop Wire
[25]
1.0
Figure 2
Figure 3

This manual suits for next models

3

Other IDEAL Cables And Connectors manuals

IDEAL APP SBE Series User manual

IDEAL

IDEAL APP SBE Series User manual

IDEAL FiberTEK III User manual

IDEAL

IDEAL FiberTEK III User manual

IDEAL APP 2300GX Series User manual

IDEAL

IDEAL APP 2300GX Series User manual

IDEAL APP SPEC Pak User manual

IDEAL

IDEAL APP SPEC Pak User manual

IDEAL 52 User manual

IDEAL

IDEAL 52 User manual

IDEAL APP SBS Series User manual

IDEAL

IDEAL APP SBS Series User manual

IDEAL APP PM1000G1 User manual

IDEAL

IDEAL APP PM1000G1 User manual

IDEAL APP SBS User manual

IDEAL

IDEAL APP SBS User manual

IDEAL APP Power Drawer User manual

IDEAL

IDEAL APP Power Drawer User manual

IDEAL APP SBE 80 Series User manual

IDEAL

IDEAL APP SBE 80 Series User manual

Popular Cables And Connectors manuals by other brands

nvent Raychem C20-01-F manual

nvent

nvent Raychem C20-01-F manual

Pentair CodeLine 40E60 user guide

Pentair

Pentair CodeLine 40E60 user guide

Airlink101 AC-USBVST user manual

Airlink101

Airlink101 AC-USBVST user manual

HP 11667B Operating and service manual

HP

HP 11667B Operating and service manual

Altinex RT300-126 user guide

Altinex

Altinex RT300-126 user guide

Erbe 20196-129 Notes on Use

Erbe

Erbe 20196-129 Notes on Use

Pentair DigiTrace E104 installation instructions

Pentair

Pentair DigiTrace E104 installation instructions

Kindermann 7449000024 Mounting instructions

Kindermann

Kindermann 7449000024 Mounting instructions

Danfoss ECpipeheat 10 V3 installation guide

Danfoss

Danfoss ECpipeheat 10 V3 installation guide

ELCART 42/12490-00 user manual

ELCART

ELCART 42/12490-00 user manual

Manhattan 205146 instructions

Manhattan

Manhattan 205146 instructions

Philips SWV2028W Specifications

Philips

Philips SWV2028W Specifications

Staubli MC-K PV-ADSP4-S2 Series Assembly instruction

Staubli

Staubli MC-K PV-ADSP4-S2 Series Assembly instruction

SALTEK HX-090 SMA F/M Installation instruction

SALTEK

SALTEK HX-090 SMA F/M Installation instruction

Insignia NS-GPS4CCK101 Quick setup guide

Insignia

Insignia NS-GPS4CCK101 Quick setup guide

Lütze LION microPLC operating instructions

Lütze

Lütze LION microPLC operating instructions

Siemens 6FX2003-0DE01 Assembly instructions

Siemens

Siemens 6FX2003-0DE01 Assembly instructions

CableMax DASL-102 user manual

CableMax

CableMax DASL-102 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.