IDEC HS6E Series User manual

B-1906-1(0)
INSTRUCTION SHEET - HS6E Series Solenoid Type Safety Switch
( 1 / 6 )
2016.08
1Type
2Specifications and Ratings
CAUTION
Solenoid lock type
•
This safety switch is designed to lock the actuator while the solenoid is energized
and to release it when deenergized.
•
When the power to the solenoid is interrupted by accident, such as disconnection,
the lock is released before a machine stops ompletely. Then, the worker may be
exposed to hazards.
•
This safety switch can be used only for limited applications which do not especially
need to be locked for safety.
Ratings approved by safety agencies
(1)TÜV rating
Main circuit, Look monitor circuit
AC-15 125V/1A
DC-13 125V/0.22A
DC-13 30V/1A
Door monitor circuit
AC-15 240V/0.75A
DC-13 250V/0.27A
DC-13 30V/2.3A
(4) KOSHA rating
Main circuit, Look monitor circuit
AC-15 125V/1A
DC-13 125V/0.22A
Door monitor circuit
AC-15 240V/0.75A
DC-13 250V/0.27A
(2) UL, c-UL rating
Main circuit,Look monitor circuit
1A, 125V ac, Pilot Duty
0.22A, 125V dc, Pilot Duty
1A, 30V dc, Pilot Duty
Door monitor circuit
C300 0.75A, 240V ac, Pilot Duty
Q300 0.27A, 250V dc, Pilot Duty
(3) CCC rating
Main circuit, Look monitor circuit
AC-15 125V/1A
DC-13 30V/1A
Door monitor circuit
AC-15 240V/0.75A
DC-13 30V/2.3A
*1 Basic insulation of 2.5kV, 1.5kV impulse withstand voltage is ensured between
different contact circuits and between contact circuits and LED or solenoid in he
enclosure. When both SELV (safety extra low voltage) or PELV (protective extra
low voltage) circuits and other circuits (such as 230V AC circuits) are used for he
solenoid power and contact circuits at the same time, the SELV or PELV
requirements are not met any more.
*2 The actuator locking strength is rated at 500N of static load. Do not apply a load
higher than the rated value. When a higher load is expected to work on the
actuator, provide an additional system consisting of another safety switch without
lock (such as the HS6B/HS7A safety switch) or a sensor to detect door opening
and stop the machine.
*3 F1max. is maximum force. The actuator’s guard-locking force Fzh is calculated in
accodance with GS-ET-19:
*4 Make sure that a fast acting fuse for short-circuit protection trips before
overheating of the wires.
Main Door Monitor Lock Monitor
Circuit Circuit Circuit
L : 1NC+1NC 2NC 1NO
M : 1NC+1NC 2NC 1NC
N : 1NC+1NC 1NC, 1NO 1NO
P : 1NC+1NC 1NC, 1NO 1NC
VL : 3NC 1NC, 1NO
VM : 3NC 2NC
VN : 2NC, 1NO 1NC, 1NO
VP : 2NC, 1NO 2NC
Solenoid Voltage / Lock Mechanism
4 : 24V DC / Spring Lock
7Y : 24V DC / Solenoid Lock
Indicator Voltage
4 : 24V DC
Cable Length
01 : 1m
03 : 3m
05 : 5m
Pilot Light Color
G : Green
Circuit Code
HS6E-L44B01-G
Housing Color
B : Black
Confirm that the delivered product is what you have ordered.
Read his instruction sheet to make sure of correct operation.
In this operating instruction sheet, safety precautions are categorized to Warning and
Caution:
Warning notices are used to emphasize that improper operation may cause severe
personal injury or death.
Caution notices are used where inattention might cause personal injury or damage to
equipment.
INSTRUCTION SHEET
Original Instructions
Solenoid Type Safety Switch
HS6E Series
SAFETY PRECAUTIONS
CAUTION
WARNING
* In order to verify if the product
you are interested in is certified
with the S mark, please check
the following section on our
website: "List of type numbers
certified with the S mark"
(Main circuit・
Door monitor circuit)
Interlocking device Type
/the level of coded Type 2 Interlocking device
/ low level coded actuator (EN ISO / ISO14119)
Resistive load
(AC-12)
Inductive load
(AC-15)
AC
Main
Circuit,
Look
monitor
circuit
30V 125V 250V
- 2A -
- 1A -
‹Ue, Ie›
Contact Ratings
Thermal Current ‹Ith›
Rated Insulation voltage ‹Ui›
Impulse withstand voltage ‹Uimp›
Altitude
Pollution degree
Operating Humidity
Condition Operating Temperature
Applicable Directives
Standards for Use
Applicable Standards
0.5A (≥ 2 circuits)
1.0A (1 circuit)
35°C ≤ Operating temperature ≤ 50°C
1.0A (≥ 3 circuits)
2.5A (≤ 2 circuits)
-25°C ≤ Operating temperature < 35°C
30V(Between ground and LED,solenoid circuit)
300V(Door monitor circuit)
150V(Main,Lock monitor circuit)
0.5kV(Between ground and LED,solenoid circuit)
2 5kV(Door monitor circuit)
1 5kV(Main,Lock monitor circuit)
2,000m maximum
3(Inside 2)
45 to 85%RH(no condensation)
-25 to +50°C (no freezing)
Machinery Directive, Low Voltage Directive
IEC60204-1, EN60204-1
GS-ET-19, UL508, CSA C22.2 No.14
IEC60947-5-1, EN60947-5-1
EN ISO / ISO14119, GB14048.5
Fzh
=
maximum force (F1max.)
Safety coefficient (=1.3)
Rated Power Consumption
Illumination Color
Light Source
Turn OFF Voltage
Turn ON Voltage
Rated Current
Rated Operating Voltage
Resistive load
(DC-12)
Inductive load
(DC-13)
Resistive load
(AC-12)
Inductive load
(AC-15)
Resistive load
(DC-12)
Inductive load
(DC-13)
DC
AC
DC
Door
monitor
circuit
-
2A 0.4A -
1A 0.22A -
- 2.5A 1.5A
- 1.5A 0.75A
2.5A 1.1A 0.55A
2.3A 0.55A 0.27A
Approx. 2.7W
Green
LED
Rated voltage x 10% minimum (at 20°C)
Rated voltage x 85% maximum (at 20°C)
110 mA (solenoid 100mA, LED 10mA : initial value)
DC24V 100% duty cycle
Rated Operating Voltage DC24V 100% duty cycle
Use 250V / 10A fast acting type fuse *4
50A (250V)
NEMA Type12 (operating temp. -25 to 45°C)
IP67 (IEC60529)
300 m Ω maximum (initial value, 1m cable)
60 N minimum
8 mm minimum
24V AC/DC 0.1A Resistive Load)
(900 operations / hour,
1,000,000 operations minimum.
AC-12 125V 2A, DC-12 125V 0.4A)
(900 operations / hour,
100,000 operations minimum.
1,000,000 operations minimum. (GS-ET-19)
2,000,000 (EN ISO 13849-1 AnnexC Table C.1)
0.05 to 1.0 m/s
900 operations/hour
Class II (IEC61140) *1
Short-circuit Protective Device
Conditional short circuit current
Degree of Protection
Contact Resistance
Direct Opening Force
Direct Opening Travel
Actuator Tensile Strength
when Locked
Electrical Durability
Mechanical Durability
B10d
Operating Speed
Operating Frequency
Class of Protection
Shock Resistance
Vibration Resistance
Operating Extremes:100m/s
2
, Damage Limits:1,000m/s
2
Operating Extremes:10 to 55 Hz, half amplitude 0.35mm
Damage Limits: 30 Hz, half amplitude 1 5mm
Fzh=500N minimum
F1max.=650N minimum (GS-ET-19) *2, *3
(Fzh=100N minimum: HS9Z-A62 actuator)
SolenoidIndicator
※

B-1906-1(0)
INSTRUCTION SHEET - HS6E Series Solenoid Type Safety Switch
( 2 / 6 )
2016.08
4Precautions for Operation
For Mounting
• Do not apply an excessive shock to the safety switch when opening or closing the
door.A shock to the safety switch exceeding 1,000m/s2may cause failure.
• Provide a door guide, and ensure that force is applied on the safety switch only in
the actuator insertion direction.
• Do not pull the actuator while it is locked. Also, regardless of door types, do not use
the safety switch as a door lock. Install a separate lock as shown in section 3.
• Entry of foreign objects in the actuator entry slot may affect the mechanism of the
switch and cause a breakdown. If the operating atmosphere is contaminated, use a
protective cover to prevent the entry of foreign objects into the switch through the
actuator entry slots.
• Make sure to install the product in a safe place out of reach. Make sure to conduct a
proper risk assessment evaluation before using the product, and use a shield or a
cover to protect the product if need be.
• While the solenoid is energized, the switch temperature rises approx-
imately 35°C above the ambient temperature (to approximately 85°C
while the ambient temperature is 50°C). Keep hands off to prevent
burns. If cables come into contact with the switch, use heat-resistant
cables.
The Adjustable (vertical/horizontal) Actuator
• Using the angle adjustment screw (M3 hexagon socket set screw), the actuator
angle can be adjusted up to 20°(refer to dimensions).
• The larger the actuator angle, the smaller the applicable radius of the door swing.
After installing the actuator, open the door. Then adjust the actuator angle so that he
actuator enters the entry slot of the safety switch properly.
• After adjusting the actuator angle, apply loctite or the like on the adjustment screw to
prevent loosening. Use screw locking agent that is compatible with the base
material.
Base : PA66 (66 nylon) of glass reinforced grade
Angle adjustment screws : stainless steel
Installing the Safety Switch and Actuator
• When installing the actuator, position the
actuator using the actuator stop (for
positioning the entry slot center and
mounting reference position).
• As shown on the right, the mounting
reference position of the actuator when
inserted in the safety switch is where the
actuator stop touches the actuator.
• Install a door stop as shown on the right
to protect the safety switch and actuator
against excessive force. Do not use the
safety switch as a door stop, otherewise
the safety switch will be damaged.
0.8mm
Safety Switch Latch
Actuator Stop
HS9Z-A61
Actuator Door Stop
Mounting
Reference
Door Stop
• After removing the actuator stop, ensure that the actuator is installed within the
tolerances shown below.
From he entry slot center of the safety switch (*5, 6) : ±1.0mm
The gap between the actuator shoulder and the safety switch surface (*7)
HS9Z-A61/-A62/-A65/-A66 : 1.9mm or shorter
HS9Z-A62S : 1.3mm or shorter
• To ensure correct operation, it is recommended to fasten the door using a latch to
achieve the above tolerance values.
• Make sure the actuator can be inserted into the entry slot without any issue.
• Perform operation test before starting operation in order to confirm the open/close
operation of contacts and locking/unlocking operation.
• When the actuator is pulled while locked in the safety switch, the actuator moves
within the range shown below.
HS9Z-A61/-A62/-A65/-A66 : 4.1mm maximum from the safety switch surface
HS9Z-A62S : 3.5mm maximum from the safety switch surface
The open/close status of the contacts are maintained within the range.When a gap is
caused because of actuator relocation, make sure that the gap does not lead to new
risks.
±1.0mm
(*6)
±1.0mm
(*5)
Entry
Direction
1.9mm(*7)
When using
HS9Z-A61
Safety Switch
Surface
Minimum Radius of Hinged Door
• When using the safety switch for a hinged door, the minimum radius of the applica-
ble door is shown in the following figures.
When the center of the hinged
door ison the extension line of the
actuatormounting surfase.
When the center of the hinged
door ison he extension line of
the contact surfaceof actuator
and safety switch.
HS9Z-A62/-A62S
R1
230mm
70mm
(Horizontal Swing)
R2
230mm
70mm
(Vertical Swing)
R3
160mm
50mm
(Horizontal Swing)
R4
160mm
50mm
(Vertical Swing)
Minimum Radius
HS9Z-A65/-A66
CAUTION
The values shown above are based on the condition that the
actuator enters and exits the actuator entry slot smoothly
when the door is closed or opened.
Since there may be devia ion or dislocation of the hinged
door, make sure of correct operation in the actual applica-
tion before installation.
When inserting an actuator into the slot, make sure to
arrange the shapes in the same direction, as shown on
the right.
R3
Minimum
Radius
Door
Hinge
Door
Hinge
Door
Hinge
Door
Hinge
R4
Minimum
Radius
Minimum
Radius
R1
Minimum
Radius
R2
Recommended Screw Tightening Torque
Name or Use
For mounting the safety switch ( M4 screw ) *8
For mounting the actuator ( M4 screw ) *8
Screw Tightening Torque
1.0 to 1 5 N•m
1.0 to 1 5 N•m
HS9Z-A61, HS9Z-A62, HS9Z-A62S ACTUATOR
• When there is a displacement of safety switch and actuator, the actuator may hit the
entry lot of safety switch hardly, thus damaging the entry slot and actuator. The
rubber cushions on the HS9Z actuator prevent the actuator from damaging the entry
slit by absorbing the shock with movement flexibility. Do not, however, exert exces-
sive shocks, otherwise the failure of safety switch may be caused.
• The rubber cushions may deteriorate depending on the operatiing environment and
conditions. Immediately replace the deformed or crasked rubber cushions with new
ones.
CAUTION
*8 When he torque is not enough to recommended screw tightening torque, make
sure that he screw do not become loose by using adhesive sealants etc. to
keep right operation and mounting positioning.
Mounting HS9Z-A62S actuator
Using two M4 screws and plate, fasten the
actuator securely on the door.
Plate has directionality. Do not lose the
plate. The actuator may fall off from the
door if there is no plate, and the actuator
does not properly.
The tensile strength of the HS9Z-A62
actuator is 100N. If an excessive tensile
force is applied, the actuator may fall off
the door. When a tensile force exceeding 100N is expected, use the HS9S-A62S
actuator with a plate.
Rubber Cushion
Plate(supplied)
M4 Screw
Door
M4 Mountion holes
3Mounting Examples
(Examples of Mounting on Sliding Doors) (Examples of Mounting on Hinged Doors)
Door
Door Stop
HS9Z-A62S
Actuator
HS9Z-A61
Actuator
Latch
HS6E
Safety Switch
• Install the interlock switch on the immovable machine or guard, and install the
actuator on the movable door. Do not install both interlock switch and actuator on
themovable door, otherwise the angle of insertion of the actuator to the safety switch
may become inappropriate, and failure will occur.

B-1906-1(0)
INSTRUCTION SHEET - HS6E Series Solenoid Type Safety Switch
( 3 / 6 )
2016.08
minimum
radius
30mm
( 70 )
( 50 )
Conduit
5Contact Operation
CAUTION
• Before manually unlocking the safety switch, make sure the machine has come to
a complete stop. Manual unlocking during operation may unlock the switch before
the machine stops, and the function of safety switch with solenoid is lost.
• While the solenoid is energized, do not unlock the actuator manually (solenoid
lock type).
• Do not apply excessive force (0.45 N•m or more) to the manual unlock key.
Otherwise the manual unlock switch will be damaged.
• Do not leave the manual unlock key attached to the switch during operation. This
is dangerous because the switch can always be unlocked while the machine is in
operation. Do not attach the key to the switch intentionally (the key is designed to
fall off when the operator's hand is off he key).
• Unlocking by pushing the plate inside the safety switch must be perfomed in
emergency only. After unlocking, make sure to tighten the M4 screw to the
tightening torque of 0.3 to 0.5 N•m. Do not apply excessive force to the M4 screw.
Otherwise the safety switch is damaged. Make sure that all screws are installed,
otherwise the waterproof capability is lost.
Contact Configuration and Operation
(Actuator
Completely Inserted)
(Actuator
Pulled Out)
Contact Operation (reference)
11-42
53-54
33-34
21-22
11-42
21-22
31-32
51-52
51-52
33-34
21-22
21-22
Approx
27.4
3433
11-42
11-42
31-32
53-54
5251
2221
53 54
33 34
21 22
51 52
3231
5453
Approx.
5.0
2221
31 32
2221
11 12 4241
41 421211
11 12 4241
41 421211
(
-
)(+)
A2 A1
Door
Monitor Lock
Monitor
HS6E-L□
HS6E-M□
HS6E-N□
HS6E-P□
Main Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Main Circuit :
Main Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Main Circuit :
Contact Configuration *9
Approx.
4.7
Approx.1.1 (Lock)
(Travel: mm)
Type
0(Actuator Mounting Reference Position)
HS6E-VL□
HS6E-VM□
HS6E-VN□
HS6E-VP□
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
Monitor Circuit :
11-12
21-22
41-42
51-52
3433
5251
22
53 54
34
21 22
51 52
3231
5453
2221
31 32
2221
11 12 4241
41 421211
11 12 4241
41 421211
31-32
11-12
21-22
41-42
53-54
31-32
11-12
21-22
41-42
53-54
33-34
11-12
21-22
41-42
51-52
33-34
21
33
Contact closed
Contact open
• When the actuator is locked or unlocked, the NC lock monitor contacts and NO
unlock monitor contacts cause bouncing. When designing a control circuit, take the
bouncing into consideration (reference values: 20ms).
• Solenoid has polarity. Be sure to wire correctly and do not apply reverse voltage
otherwise the solenoid will be damaged. Do not apply voltage that exceed the rated
voltage, otherwise the solenoid will be burnt out.
• Do not fasten or loosen the conduit at the bottom of he safety switch.
• When wiring, make sure that liquid such as water and oil does not intrude from the
end of the cable.
• When bending the cable during wiring, secure the
cable radius of 30mm at the minimum. Do not
apply an excessive shock, such as tensile and
compressing force, to the connection part of the
cabel and switch.
• Use the proprietary actuators only. Other actua-
tors will cause damage to the switch.
• Ensure that the safety switch is installed on a flat
mounting surface, and provide sufficient strength
to the mounting surface so that it will not be
distorted during operation. Make sure that no
foreign objects are caught between the safety
switch and mounting surface. Uneven surface,
distorted surface, or foreign objects may result in
the malfunction of safety switch.
For Manual Unlocking
• Spring lock type : The HS6E allows manual unlocking of the actuator to precheck
proper door operation before wiring or turning power on, as well as for emergency
use such as a power failure.
• Solenoid lock type : If the actuator is not unlocked although the solenoid is deener-
gized, the actuator can be unlocked manually.
Manual Unlocking Method
• When using the manual unlock key :
To change the normal position to the manual unlocking position as shown above,
turn the key fully (90 degrees) using the propietary key supplied with the switch.
Using the switch with the key being not fully turned (less than 90 degrees) may
cause damage to the switch or errors.
Note: When manually unlocked, the switch will keep the main circuit disconnected
and the door unlocked.
• When unlocking by pushing he plate insaide the safety
switch :
Remove the screw at the side of the safety switch and
insert a small screwdriver. Push the plate inside the
safety switch toward the LED pilot light using a small
screwdriver until the actuator is unlocked. See the
figure on the right.
CAUTION
• HS6E Series Safety Switches are Type 2 low-level coded interlocking devices (EN
ISO / ISO14119). The following system installation & mounting instructions are EN
ISO / ISO14119 requirements to prevent function failure from the interlock switch.
1. Using permanent fixing methods (e.g. welding, rivets, special screws...etc) to
prevent dismantling or de-positioning of the interlock device. However, perma-
nent fixing methods are not an adequate solution if you expect the interlock
device to fail during the machinery lifetime, or if you need to replace the prod-
uct in quick manner. In these situations, other measures (see 2.) should be put
in place to reduce the risks of function failure.
2. At least one of the following measures should be applied to prevent function
failure.
(1) Mounting the interlock device in a place out of reach from workers
(2) Using shielding protection to prevent physical obstruction of the device
(3) Mounting the interlock device in a hidden position
(4) Integrate status monitoring & cycling testing of the device to the control
system to prevent product failure.
• Regardless of door types, do not use the safety switch as a door stop.
Install a mechanical door stop to the end of the door to protect the safety switch
against excessive force. When a higher load works on the lock portion of the
safety switch, the actuator may not unlock.
• Mount the actuator so that it will not hit the operator when the door is open, other-
wise injury may be caused.
• Pay attention to the management of spare actuator. Safety function of door inter-
lock switch will be lost in case the spare actuator is inserted into the interlock
switch.
• Do not cut or remodel the actuator, otherwise failure will occur.
• If multiple safety components are wired in series, the Performance Level to
EN ISO 13849-1 will be reduced due to he restricted error detection under certain
circumstance.
• The entire concept of the control system, in which the safety component is
integrated, must be validated to EN ISO 13849-2.
Manual Unlock Key
(supplied with
safety switch)
UNLOCK UNLOCK
LOCK
LOCK
Normal
Position
Manual
Unlocking
Posi ion
Manual Unlocks
(one each on the front and the back)
Driver
WARNING
• Turn off the power to the safety switch before starting installation, removal, wiring,
maintenance, and inspection on the safety switch. Failure to turn power off may
cause electrical shocks or fire hazard.
• Do not disassemble or modify the switch. Also do not attempt to disable the
interlock switch function, otherwise a breakdown or an accident will result.

B-1906-1(0)
INSTRUCTION SHEET - HS6E Series Solenoid Type Safety Switch
( 4 / 6 )
2016.08
6Wiring
CAUTION
*10 Do not attempt manual unlocking when the solenoid is energized.
*11 Do not energize the solenoid for a long time while the door is open or when the
door is unlocked manually.
Door States
Door Manual Unlock Key
Door Monitor Circuit 11-12
21-22
31-32
Door Monitor Circuit 33-34
Lock Monitor Circuit 41-42
51-52
Lock Monitor Circuit 53-54
Solenoid Power A1-A2
Door is locked.
The machine can
be operated.
The machine can
not be operated.
Door is unlocked.
The machine can
not be operated.
Door is unlocked.
The machine can
not be operated.
On
Open
Open
Closed
-
Closed
Closed
Off
Closed
Open
Closed
-
Closed
Open
Off/On *11
Closed
Closed
Open
-
Open
Open
Off *10,11
Closed
Open
Closed
Closed
Open
・Solenoid Lock Type (HS6E-V□7Y)
Operation Cycle
• Spring Lock Type (HS6E-□4)
・Solenoid Lock Type (HS6E-□7Y)
Turn the keyto
unlock position.
Turn the keyto
unlock position.
Door States
Door Manual Unlock Key
Main Circuit 11-42
Door Monitor Circuit 21-22
31-32
Door Monitor Circuit 33-34
Lock Monitor Circuit 51-52
Lock Monitor Circuit 53-54
Solenoid Power A1-A2
On
Open
Closed
Open
Closed
-
Closed
Door is locked.
The machine can
be operated.
Closed
Off/On *11
Closed
Open
Closed
Open
-
Open
The machine can
not be operated.
Open
Off *10, *11
Closed
Open
Open
Open
Closed
Door is unlocked.
The machine can
not be operated.
Closed
Off
Closed
Open
Open
Open
-
Closed
Door is unlocked.
The machine can
not be operated.
Closed
Door States
Door Manual Unlock Key
Main Circuit 11-42
Door Monitor Circuit 21-22
31-32
Door Monitor Circuit 33-34
Lock Monitor Circuit 51-52
Lock Monitor Circuit 53-54
Solenoid Power A1-A2
Off
Open
Closed
Open
-
Closed
On
Open
Open
Open
-
Closed
Off/On
Open
Open
-
Open
Off
Open
Open
Open
Turn the keyto
unlock position.
Closed
Door is locked.
The machine can
be operated.
The machine can
not be operated.
Door is unlocked.
The machine can
not be operated.
Door is unlocked.
The machine can
not be operated.
Closed Open Closed
Closed
Closed
ClosedClosedClosed
Closed
Closed
Wiring
• Cable specifications
UL style 2464, 12c×No.22AWG, (80°C 300V)
• Wire identification
Wires are identified by the color and white line printed on
the wire.
Do not use wire which is Gray, Gray / White.
Terminal number identification
• When wiring, the terminal number on each contact is identified by wire color. The
following table shows the identification of terminal numbers.
• When wiring, cut unnecessary wires such as unused wires to avoid incorrect wiring.
Insulator Color
Orange / White
Gray / White
White
Black
Insulator Color
Blue / White
Gray
Pink
Orange
No.
5
6
7
8
Insulator Color
Pink / White
Brown / White
Brown
Blue
No.
9
10
11
12
No.
1
2
3
4
Jacket
Colored Insulator
CAUTION
*9 The Actuator is inserted, and HS6E is locked.
• Contact operation is based on the condition that the actuator is inserted into the
center of the safety switch slot.
• Contact operation shows the HS9Z-A61, A62, A65, A66 actuators. (For HS9Z-A62S
actuator, decreases 0.6mm to contact operations)
• Terminals 12-41 are connected together internally. Use terminals 11-42 for safety
circuit inputs.(without HS6E-V□)
• Indicator turns on when solenoid is energized.
Door States
Door Manual Unlock Key
Door Monitor Circuit 11-12
21-22
31-32
Door Monitor Circuit 33-34
Lock Monitor Circuit 41-42
51-52
Lock Monitor Circuit 53-54
Solenoid Power A1-A2
Off
Open
Open
Closed
-
Closed
On
Closed
Open
Closed
-
Closed
Off/On
Closed
Closed
Open
-
Open
Off
Closed
Open
Closed
Turn the key
to unlock position.
Closed
Door is locked.
The machine can
be operated.
The machine can
not be operated.
Door is unlocked.
The machine can
not be operated.
Door is unlocked.
The machine can
not be operated.
Closed Open Open Open
• Spring Lock Type (HS6E-V□4)
CAUTION
When using the outputs from the HS6E-V safety switch as inputs to safety circuits,
connect the door monitor circuits (11-12, 21-22, 31-32) and lock monitor circuits
(41-42, 51-52) in series. (GS-ET-19)
Then, the contact rating for he lock monitor circuit is applied.(HS6E-V□)
Circuit No.
11
12 / 42 (without HS6E-V□)
21
22
31, 33
32, 34
41 (HS6E-V□)
42 (HS6E-V□)
51, 53
52, 54
A1(-)
A2(+)
Insulator Color
Blue
Blue / White
Brown
Brown / White
Orange
Orange / White
Gray
Gray / White
Pink
Pink / White
Black
White
(without HS6E-V□)

B-1906-1(0)
INSTRUCTION SHEET - HS6E Series Solenoid Type Safety Switch
( 5 / 6 )
2016.08
*Connect 21-22 and 51-52 in series.
*
DC24V
S3
F1
K4
K3
DC0V
A1(
-
)
A2(+)
52
S1
12
11
HR1S-AF Safety relay module
13
14
ESC
K4
K3 S2
51
42
41
22
21
S33 S34
13 23
A1
S11 S22
14 24
A2
S12 S21
34
33
DC24V
S3
F1
K4
K3
DC0V
A1(
-
)
A2(+)
52
S1
12
11
HR1S-AF Safety relay module
13
14
ESC
K4
K3 S2
51
42
41
22
21
S33 S34
13 23
A1
S11 S22
14 24
A2
S12 S21
34
33
S4
1
2
L1(+)
N(−)
L1(+)
N(−)
7Example of wiring Diagram realizing Safety Category
Example of a circuit diagram for Safety Category 4
(attainable PL = e)
Example of a circuit diagram for Safety Category 3
(attainable PL = d)
(Condi ion 1: To apply the fault exclusion of mechanical structural parts including the actuator
→ Make sure to use the product within the product specification range described in this
manual and the version of the manual provided with the product )
(Condi ion 2: Documentation of the reason for he machine/equipment manufacturer to have
applied the fault exclusion based on ISO13849-1, ISO13849-2 or IEC62061 )
Output Circuit Output Circuit
S1: HS6E-P4 Safety Switch with Solenoid
S2: Starting Switch (HW Series Momentary)
S3: Unlocking Enabling Switch
S4: Safety limit Switch
ESC: Outside start condition
K3, 4: Safety Contactor
F1: Outside fuse of safety relay module at power supply line
Note: Use the monitoring device(Safety relay module) provided the capavility to
detect a cross short circuit. The insulation of the cable has to withstand
environmental influences. If a control device o her than the one shown in the
draft is used, the used control device has to be equipped with a cross short
circuit monitor.
Guard Open Guard Open
One of the example of
the circuit ; Safety
relay module, HR1S-AF
series manufactured
by IDEC CORPORATION
One of the example of
the circuit ; Safety
relay module, HR1S-AF
series manufactured
by IDEC CORPORATION
Used as open/close
monitor of guard
Used as open/close
monitor of guard
HS6E-P4
Safety Switch with Solenoid
HS9Z-A61 Actuator
HS6E-P4
Safety Switch wi h Solenoid
HS9Z-A61 Actuator

B-1906-1(0)
INSTRUCTION SHEET - HS6E Series Solenoid Type Safety Switch
( 6 / 6 )
2016.08
8Dimensions and Mounting (mm)
9Precaution for Disposal
Dispose of the HS6E safety switch as an industrial waste.
13 28 2
7.5
2.5
15
34
25
16.8
5.5
2
20°
R2.1
20°
0.8
1.2
3.5
25
Safety Switch dimensions
Straight Actuator ( HS9Z-A61 )
Mountiong Hole Layout
(when mounted on the front side)
Manual unlock key
(supplied)
L-shaped Actuator ( HS9Z-A62S )
Manual
unlocking
Manual unlocks
(one each on the
front and the back) R.P.
HS9Z-A61
Actuator
HS9Z-A62S Actuator
Actuator Stop *12
(supplied)
(supplied)
(supplied)
(supplied)
Actuator Stop *12
(supplied)
R.P.
3-M4 Screw
(Φ4 3 or M4 tapped )
20 to 22
Hole for
Manual
unlocking
Φ12
(reference)
Manual
unlock key
(supplied)
Type:HS9Z-A61
Type:HS9Z-A62
Type:HS9Z-A65
Joint
Actuator Stop *12
(supplied)
Actuator Stop *12
(Horizontal Adjustment)
Angle Adjusting Screw
(M3 Hexagon Socket Set Screw)
Base
Actuator Stop *12
Actuator Mounting Hole Layout
(Horizontal / Vertical Adjustment)
2-M4 Screws
(Φ4 3 or M4 Tap)
(Horizontal Adjustment) (Vertical Adjustment)
Angle Adjus ing Screw
(M3 Hexagon Socket Set Screw) Actuator Stop *12
Angle Adjusting Screw
(M3 Hexagon Socket Set Screw)
Note: HS9Z-A65 and HS9Z-A66 are different in the insertion direction of the metal key
(180°).
Factory defalut *13
(Vertical Adjustment)
Joint
(M4 Holes)
Angle Adjusting Screw
Base
Actuator Stop *12
(M3 Hexagon Socket Set Screw)
Factory defalut *13
*12 The actuator stop is used when
adjusting he actuator position.
Remove after he actuator
position is determined.
*13 The direction of adjustable
angle can be changed (vertical
or horizontal) by changing the
insertion direction of the joint
(white plastic part). See the
figures below. Do not lose the
joints. Actuators do not operate
normally without a joint.
(Horizontal Adjustment) (Vertical Adjustment)
Factory defalut
Joint
Accessories dimensions
(supplied)
Φ10
6.5
(24)
(24.5)
18
3
915
22.6±1
(14)
0.8
(6.2)
42 to (42.5)
20.5
41.8
28.5
30
LED
0.8
15
20
1
37
15
C12
20.5
(2.3)
41.8
28.5
46.1
10.4
10.1
(12.6±1)
(5)
(14)
4
4
R2.1
1
□75
35
30
4
4
Φ7.6
50.8 to (51.9)
5.5
(22 5)(22.5)
Φ4.4
Provide mounting holes as pecified, and install the
safety switch using three mounting screws.
Do not install the switch using only one or two
mounting screws, otherwise the safety switch will
not be fixated properly, resulting in the malfunction
of safety switch.
*Reversible Mounting Possible
R.P.: Actuator mounting reference position
14
35 9 28 2
(8.4)
14
3.5
1.2
When
installed on
the door (5)
2-Φ4.3
2-Φ9
14 15
Actuator Mounting Hole Layout
(Straight, L-shaped)
When installed on
he door (33 8)
28 2
1.2
14
13.1
(8.4)
3.5
34
14
2-Φ4.3
2-Φ9
Type:HS9Z-A66
20°
20°
http://www.idec.com
Manufacturer: IDEC CORP.
2-6-64 Nishimiyahara Yodogawa-ku, Osaka 532-0004, Japan
EU Authorized Representative: IDEC Elektrotechnik GmbH
Heselstuecken 8, D-22453 Hamburg, Germany
DECLARATION OF CONFORMITY
We, IDEC CORPORATION 2-6-64, Nishimiyahara Yodogawa-ku,Osaka 532-0004, Japan declare
under our sole responsibility that the product:
Description: Safety Switch
Model No: HS6E
to which this declaration relates is in conformity with the EC Directive on the following standard(s)
or other normative document(s). In case of alteration of the product, not agreed upon by us, this
declaration will lose its validity.
Applicable EC Directive : Low Voltage Directive (2014/35/EU)
Machinery Directive (2006/42/EC)
Applicable Standard(s) : EN 60947-5-1,GS-ET-19
When installed on
the door (5)
This manual suits for next models
20
Table of contents
Other IDEC Switch manuals

IDEC
IDEC HS1L Series User manual

IDEC
IDEC HS5E Series User manual

IDEC
IDEC SA1E Series User manual

IDEC
IDEC HS5L Series User manual

IDEC
IDEC HS1C Series User manual

IDEC
IDEC HS5D-11 User manual

IDEC
IDEC MICRO/I HG9Z-1D4PN05 User manual

IDEC
IDEC HS6B Series User manual

IDEC
IDEC HS1C Series User manual

IDEC
IDEC HS1E Series User manual

IDEC
IDEC HS1L Series User manual

IDEC
IDEC HS6B Series User manual

IDEC
IDEC HS5E-K User manual

IDEC
IDEC HS1T Series User manual

IDEC
IDEC SA1E Series User manual

IDEC
IDEC HE1B Series User manual

IDEC
IDEC HS5E Series User manual

IDEC
IDEC HS3A Series User guide

IDEC
IDEC SA1E Series User manual

IDEC
IDEC SA1E-L Series User manual