IDS X64 User guide

IDS X64 Installer Manual 700-398-02D Issued August 2010
1

IDS X64 Installer Manual 700-398-02D Issued August 2010
2

IDS X64 Installer Manual 700-398-02D Issued August 2010
3
Contents
1. Introduction to the IDS X64........................................................................................... 10
1.1 Features of the IDS X64......................................................................................................... 10
2. Installation and Wiring ..................................................................................................11
2.1 Installation Requirements ...................................................................................................... 12
2.1.1 End-of-Line Resistors ............................................................................................................ 12
2.1.2 Box Tamper Input .................................................................................................................. 12
2.1.3 Connecting the Telephone Communicator - Advanced ........................................................ 12
2.1.4 Programmable Outputs ......................................................................................................... 12
2.1.5 Key-Switch or Remote Control Unit ....................................................................................... 13
2.2 Installing a Zone Expander Module ....................................................................................... 13
2.3 IDS Remote Receiver............................................................................................................. 13
2.4 Radio Transmitter Connection ............................................................................................... 13
3. Hardware Default Switch ..............................................................................................13
4. Enrolling Keypads and Other Bus-wired Peripherals .................................................14
4.1 Replacing a Damaged Keypad / Bus-wired Peripheral ......................................................... 14
4.2 Defaulting Keypads ............................................................................................................... 15
5. Event Log ...............................................................................................................15
6. Access Codes ...............................................................................................................15
6.1 Normal User Code................................................................................................................. 15
6.1.1 Master User Code.................................................................................................................. 15
6.1.2 Maid‟s Code (Arm to Disarm Code) ...................................................................................... 16
6.1.3 Duress Code.......................................................................................................................... 16
6.2 Installer Code .................................................................................................................... 16
6.3 Maintenance Code ................................................................................................................ 16
6.4 Download Code16
7. How to Read Location Values.......................................................................................17
8. Programming of the Panel............................................................................................18
8.1 Entering Installer or Maintenance Mode ................................................................................ 19
8.2 Programming Standard Locations......................................................................................... 19
8.3 Programming Extended Locations ........................................................................................ 20
8.3.1. Using the String Method........................................................................................................ 20
8.3.2. Using Sub-locations .............................................................................................................. 21
8.4 Programming a Location or Sub-location with a Bitmap ....................................................... 21
9. Programming Location Summary................................................................................. 22
9.1 Zones .................................................................................................................... 23
9.2 Global Setup .................................................................................................................... 26
9.3 Daylight Savings .................................................................................................................... 33
9.4 Miscellaneous - Advanced..................................................................................................... 35
9.5 Communications Setup - Advanced...................................................................................... 36
9.6 Phone Numbers .................................................................................................................... 40

IDS X64 Installer Manual 700-398-02D Issued August 2010
4
9.7 Zone Properties .................................................................................................................... 43
9.8 No Movement - Advanced..................................................................................................... 45
9.9 Auto Arm - Advanced............................................................................................................. 47
9.10 Security Codes .................................................................................................................... 49
9.11 Partition Options .................................................................................................................... 50
9.12 Delays .................................................................................................................... 53
9.13 Options to Configure Keypads .............................................................................................. 54
9.14 Reporting Codes - Advanced ................................................................................................ 57
9.14.1 Global Reporting Codes ........................................................................................................ 57
9.14.2 Zone Reporting Codes .......................................................................................................... 59
9.14.3 Partition Reporting Codes...................................................................................................... 63
9.14.4 User Reporting Codes ........................................................................................................... 65
9.15 Programmable Outputs ......................................................................................................... 67
9.15.1 Output Disarm Clear.............................................................................................................. 67
9.15.2 Partition Event Driven Outputs - Advanced............................................................................ 69
9.15.3 Zone Programmable Output Events ...................................................................................... 72
9.15.4 Output Pulse Timing - Advanced........................................................................................... 74
9.15.5 Output Scheduling On Time - Advanced............................................................................... 74
9.15.6 Output Scheduling Off Time - Advanced............................................................................... 75
9.15.7 Output Scheduling On/Off Days - Advanced......................................................................... 76
9.16 Event Reporting Options - Advanced .................................................................................... 78
10. Keypad Information....................................................................................................... 84
11. Panel Information..........................................................................................................84
Index of Programming Locations.................................................................................................... 85
Cross Reference Lookup ...............................................................................................................94
Programming Quick Reference Guide............................................................................................95

IDS X64 Installer Manual 700-398-02D Issued August 2010
5
Figures
Figure 1: Connection Diagram without Tamper per Zone....................................................................... 11
Figure 2: How Telephone Numbers Work................................................................................................ 41
Figure 3: Paging Indication on the Classic Keypad ................................................................................ 50
Figure 4: Paging Indication on the Curved Keypad ................................................................................ 50
Tables
Table 1: Values Represented by each Zone LED .................................................................................... 17
Table 2: Binary Coded Decimal Four Digit Display ................................................................................. 17
Table 3: Hexadecimal Values ................................................................................................................... 18
Table 4: Defaulting Data........................................................................................................................... 22
Table 5: Zone Types ................................................................................................................................. 24
Table 6: Zone Types in String Format...................................................................................................... 26
Table 7: Zone Types in Sub-location Format........................................................................................... 26
Table 8: Loop Response Time Data......................................................................................................... 27
Table 9: Global Options Data................................................................................................................... 28
Table 10: Trouble Display Options .......................................................................................................... 30
Table 11: Number of Digits Data.............................................................................................................. 33
Table 12: Month Data ............................................................................................................................... 33
Table 13: Day of Week Data ..................................................................................................................... 34
Table 14: Week of Month Data ................................................................................................................. 34
Table 15: Auto Test Interval Data............................................................................................................. 35
Table 16: Download Code Disable Data .................................................................................................. 36
Table 17: Default Switch Disable Data..................................................................................................... 36
Table 18: Communications Format Data ................................................................................................. 37
Table 19: Reporting Communications Options Data............................................................................... 38
Table 20: Download Options Data ........................................................................................................... 39
Table 21: Phone Number Example........................................................................................................... 41
Table 22: Zone Type Properties Data ...................................................................................................... 44
Table 23: Arm/ Disarm Days Data ............................................................................................................ 48
Table 24: Zones per Partition Page.......................................................................................................... 50
Table 25: Partition Arm Options Data ...................................................................................................... 52
Table 26: Extended Partition Options Data.............................................................................................. 53
Table 27: Keypad Options Data ............................................................................................................... 56
Table 28: Clear Programmable Onboard Outputs Data .......................................................................... 68
Table 29: Clear Programmable Zone Expander Outputs Data................................................................ 68
Table 30: Clear Programmable Keypad Outputs Data ............................................................................ 68
Table 31: Partition Programmable Output Events for Locations 390-410 .............................................. 69
Table 32: Partition Programmable Output Events for Locations 411-414 .............................................. 70
Table 33: Output Address Physical Mapping Data.................................................................................. 70
Table 34: Output Actions Data ................................................................................................................. 71
Table 35: Default Programmable Events Data......................................................................................... 71
Table 36: Default Programmable Events Data with no Default Action.................................................... 71
Table 37: Global Programmable Output Events Default Data................................................................. 73
Table 38: Output Scheduling On/Off Days Data...................................................................................... 76
Table 39: Outputs per Location................................................................................................................ 77
Table 40: Split Reporting Zones Bitmap Data ......................................................................................... 78
Table 41: Global Split Reporting 1 Bitmap Data...................................................................................... 79
Table 42: Global Split Reporting 2 Bitmap Data...................................................................................... 80
Table 43: Global Split Reporting 3 Bitmap Data...................................................................................... 81
Table 44: Global Split Reporting 4 Bitmap Data...................................................................................... 82
Table 45: Split Reporting Partitions 1-8 Data .......................................................................................... 83

IDS X64 Installer Manual 700-398-02D Issued August 2010
6

IDS X64 Installer Manual 700-398-02D Issued August 2010
7

IDS X64 Installer Manual 700-398-02D Issued August 2010
8

IDS X64 Installer Manual 700-398-02D Issued August 2010
9

Section: 1
IDS X64 Installer Manual 700-398-02D Issued August 2010
10
1. Introduction to the IDS X64
Thank you for purchasing an IDS Alarm Panel.
The IDS X64 is a versatile, Bylaw 25 compliant, expandable Alarm Panel. It has up to 8 partitions and can
be expanded from 8-64 zones. Most features are configurable and may be programmed directly through
a keypad or via serial PC connection or telephone system, using the IDS Download Software and
appropriate modem (P/N: 860-36-0001).
There are up to 64 programmable burglary zones, a dedicated panic zone, monitored siren output,
auxiliary power output, and 5 onboard programmable outputs expandable to 25, which may be
programmed to perform various trigger/switching functions.
For correct operation, the IDS X64 must be used in conjunction with the specified transformer / battery
combination (ask your sales representative for a copy of the IDS Power Budget spreadsheet to identify
your needs) and appropriate peripheral sensors and signalling devices.
NOTE:
X-SERIES products are not compatible with any previous IDS products, such as the IDS816 and
IDS1632.
1.1 Features of the IDS X64
Zones and Partitions:
8 onboard zones, expandable to 16 onboard zones with a X64 8-zone Plug-in Expander
(P/N: 860-06-X-08PI) –A very cost-effective 16 zone solution
Further expandable to 64 zones with the use of up to 6 bus-wired X64 8-zone Unpowered
Expander modules (P/N: 860-06-X-08S) or 8 keypad zones - 1 per keypad
8 partitions
4 stay profiles per partition
Users:
128 users
Options to set user codes as Master, Duress, Maid, Arm only, Disarm only or Programmable
Output.
System Options:
Tamper reporting per zone using double end-of-line resistors (12K and 4K7)
5 programmable outputs on the Alarm Panel, expandable to 25 when using zone expanders (2
per expander), and keypads (1 per keypad)
Event log (1000 events) date and time relative
Auto arm/disarm capability per partition and by day of the week.
No movement auto arm and medical reporting
Panel firmware installer upgradable via serial data cable
Telephone communicator that supports Ademco, FBI, Silent Knight, Contact ID, and SIA
Fax defeat/answering machine override
Dual reporting provides for duplicated reporting to two independent central base stations
Split reporting to report to either 1 of 2 dual reporting number pairs
Comprehensive lightening protection
Dynamic battery self test
Low battery monitoring and cut-out circuit
Dual power supply, with an independent battery charging circuit, means more onboard power for
simplified alarm installation

Section: 2
IDS X64 Installer Manual 700-398-02D Issued August 2010
11
2. Installation and Wiring
Please refer to: Figure 1: Connection Diagram without Tamper per Zone and familiarise yourself with the
following sections.
*The kick start jumper must be in-circuit when using only a battery (i.e. no AC). Simply short
the pins out with a screwdriver, or use a jumper. Remove the short/jumper once the Panel
Status LED lights up (indicating power up), as leaving it on disables the low battery cut-out.*
Figure 1: Connection Diagram without Tamper per Zone

Section: 2
IDS X64 Installer Manual 700-398-02D Issued August 2010
12
2.1 Installation Requirements
A suitable transformer with an output voltage of 16 Vac ±10% with a 32VA minimum rating must
be used. A 48VA transformer is recommended for larger installations.
A 12V sealed lead acid battery with a minimum capacity of 7AH must be used. The backup
period after mains failure will depend on the number of keypads, sensors, and bus-wired
peripheral devices connected to the system.
Connect a 12V self-driven siren or piezo siren (not a horn speaker) to the siren output.
The panel can supply a total continuous current of 750mA to bus-wired peripheral devices such
as keypads, remotes, receivers, passives etc; from Aux 12V terminals.
2.1.1 End-of-Line Resistors
All zones, including Panic zones, are end-of-line supervised.
All zones, whether they are used or unused, need to be terminated with a 3K3 resistor (resistor
colour-code is orange, orange, red, gold).
For maximum security, the end-of-line resistor must be placed inside or as close to the sensor as
possible.
For tamper by zone, 4K7 and 12K end-of- line resistors must be connected instead of a single
3K3 resistor.
If the panel is unarmed and a tamper condition occurs, the siren will not sound but a tamper
condition will be reported if it is enabled to do so. See Table 40 to enable/disable this option.
If the panel is armed and a tamper condition occurs, an audible alarm will register, and a tamper
condition AND zone violation will be reported.
2.1.2 Box Tamper Input
The box tamper input does not require an end-of-line resistor, but does require a normally closed
contact. The panel is shipped with the box tamper input bypassed with tamper. To use it, remove the
jumper and connect a normally closed contact onto the terminals. Refer to Figure 1 for the box tamper
position on the Alarm Panel.
2.1.3 Connecting the Telephone Communicator - Advanced
Refer to: Figure 1: Connection Diagram without Tamper per Zone.
For optimum lightning protection, connect a low resistance earth to the communicator earth
input.
Always connect the telephone communicator in line seizure mode and never in parallel with the
telephone.
Ensure the telephone receiver is connected to the communicator terminals marked “phone” and
the incoming line to the terminals marked “line”.
2.1.4 Programmable Outputs
An IDS Relay Board (P/N: 861-004) must be used when any device requiring a current greater than 50mA
is connected to a programmable output. The programmable output circuitry consists of a 12V source with
a 56 series resistor. Current sink is via a 1, 000 resistor to ground. The maximum output voltage is
13.6Vdc. The maximum output current is 25mA. Programmable outputs are primarily connected for radio
transmitter. However, they are also used for connecting, LEDs, sirens, bus-wired peripherals, etc.

Section: 2
IDS X64 Installer Manual 700-398-02D Issued August 2010
13
2.1.5 Key-Switch or Remote Control Unit
A key-switch or non-IDS remote receiver may be connected to any zone to allow remote arm/disarm and
remote panic capability.
When using a key-switch or remote control unit, a 3K3 resistor must be connected between the
zone input and ground.
Use only a spring-loaded momentary key-switch or non-latching remote control unit.
2.2 Installing a Zone Expander Module
When installing a zone expander module refer to the document supplied with the module. Note that up to
6 bus-wired, 8-zone expander modules (P/N: 860-06-X-08S) and 1 plug-in expander (P/N: 860-06-X-08PI)
may be added to the IDS X64 Alarm Panel. Zones 9-16 are reserved for the Plug-in Zone Expander
module.
2.3 IDS Remote Receiver
Up to 4 IDS Remote Receivers (P/N: 860-07-X02-DI) may be connected to the keypad Bus. Using this
facility allows remote arming and disarming of the panel while providing user identification for a maximum
of 128 remotes.
For a full list of features and benefits of the receiver, please see the manual that comes with it.
2.4 Radio Transmitter Connection
When connecting a radio transmitter, use the TX terminal provided on the panel to supply power to the
transmitter. This output is protected by a 4 Amp fuse.
3. Hardware Default Switch
Use the hardware default switch (refer to Figure 1) to return the panel to its factory default settings.
The procedure to default the panel is as follows:
1. Remove the battery and AC power from the panel
2. If you are only using a battery make sure that the kick-start jumper is in circuit
3. Hold down the default switch and reapply power to the panel (battery or AC)
4. Wait for the Panel Status LED to flash
5. Release the default switch
6. Remove the kick-start jumper, if one was used
7. Defaulting is complete once the Panel Status LED starts flashing
The effects of applying the default:
1. Factory default values are restored to all locations
2. All attached keypad IDs are defaulted
3. The event log is not defaulted
4. The “system default” event is logged to the event log
NOTE:
The hardware default switch can be disabled in location 35.
See also: Defaulting the Panel or Master User Code –location 0.

Section: 4
IDS X64 Installer Manual 700-398-02D Issued August 2010
14
4. Enrolling Keypads and Other Bus-wired Peripherals
Keypads must be enrolled on the system before they can be used. Keypads are allocated an ID in the
order in which they are enrolled. To enrol a keypad:
1. Wire it to the keypad BUS
2. Press the [#] key
Repeat this process with the remaining keypads where more than 1 keypad is used. The first keypad
enrolled will have an ID of 1, the second enrolled will have an ID of 2, the third an ID of 3 etc.
NOTE:
All the zone and LEDs will flash on a keypad that does not have an ID.
The POWER and READY LEDs will be on for a keypad that has an ID and no zone violations.
Only the POWER LED will be on for a keypad that has an ID with a zone violation. The LED for
that zone will also flash.
Trouble shooting
If the ID process, for an LED keypad, has failed zones 1-8, and zones 9-16 will flash alternately. At this
point press the [#] key to retry.
If the flashing persists, try the following steps:
1. Check all wiring
2. Check that you have not exceeded 8 keypads on the bus
3. Contact the IDS helpdesk for further support
NOTE:
To enrol other devices (IDS Remote Receivers or Zone Expanders); consult the installation manuals for
those devices. The IDS X64 Alarm Panels can accept 6 zone expanders and 4 remote receivers.
4.1 Replacing a Damaged Keypad / Bus-wired Peripheral
To replace a damaged device (non-dipswitch –like a keypad):
1. Disconnect only the faulty device.
2. Program a value of [4] into location 0 to free up all redundant IDs (previously unallocated IDs
remain free), wait for approximately 10 seconds then continue to step 3.
3. Connect the replacement device and enrol it –by pressing [#] for keypads –it will now be
enrolled in the first available address.
NOTE:
If other devices are disconnected (or damaged), at the time of performing step 2, their addresses
will also be freed. Any new devices being enrolled will automatically be allocated addresses
beginning from the lowest free address.
When you free up the ID of the damaged unit, the panel settings, relevant to the ID, will be
defaulted too. Therefore, the keypad will need to be re-added to a partition.
If a new keypad was enrolled, go to location 243 to check the keypad‟s ID (1-8).
Solution
If there are problems with device IDs on a complex installation, do not assign IDs randomly, rather, at the
end of the installation, default all device IDs and then enroll them in sequence.
To re-enrol a Zone Expander or a Remote Receiver (dipswitch); consult the installation instructions for the
particular device.

Section: 4
IDS X64 Installer Manual 700-398-02D Issued August 2010
15
4.2 Defaulting Keypads
To default the ID of an individual keypad:
1. Remove power to the keypad (or the whole panel if easier).
2. Hold down the [1]and [3]keys simultaneously until the beep (for at least 3 seconds).
3. Restore the power.
4. Wait for three seconds and then release the keys (there will not be a beep).
5. All the keypad LEDs will flash simultaneously indicating that the keypad has been de-registered
4. Wait for five seconds and ensure that the Panel Status LED on the panel is flashing.
5. Press the [#] key to allocate a new ID to the defaulted keypad. Keypad IDs are allocated
incrementally.
6. The ID of any (correctly registered) keypad can be viewed in location 243 from the keypad of
interest.
To default the ID of ALL keypads:
1. Enter a value of [3] into location 0.
[INSTALLER CODE] [*] [0] [*] [3] [*]
2. On pressing the final [*],wait a few seconds and ALL the keypad LEDs will begin flashing. (Do
NOT press the [#] key at the end of this sequence, unless you wish the keypad you are using to
be registered in the first address).
3. Re-enrol all keypads by pressing the [#] key on each keypad –in the CORRECT sequence to
ensure that keypad zone and partition allocation is as required by the user.
5. Event Log
A comprehensive log of the 1 000 most recent events is retained in the non-volatile EEPROM. The log
may be retrieved using the up/download software, or on the LCD keypad. (See the LCD Keypad Manual
or User Manual to see how to view the event log).
The IDS Download Software is available for Inhep account customers, at no cost, to collect your event
logs via direct serial download, or via a modem.
6. Access Codes
The panel supports up to 128 users. The user codes can have various properties assigned to them.
These properties allow the user codes to have different functions.
6.1 Normal User Code
A normal user code is used to arm/disarm the panel, and to access certain user options.
6.1.1 Master User Code
When assigned to a user, this property allows the user to act as a master user. The Master User Code
has full access to programming all the user options. For a full list of user programmable options, refer to
the X64 User Manual.

Section: 6
IDS X64 Installer Manual 700-398-02D Issued August 2010
16
6.1.2 Maid’s Code (Arm to Disarm Code)
This property may be used to limit access to the premises. A Maid's Code will only disarm the system if
the same code was used for arming. If armed with a code other than this code, the system will view an
attempt to disarm using a Maid's Code as an invalid entry. Any valid user code will disarm the system if it
has been armed with a Maid‟s Code.
6.1.3 Duress Code
This property denotes a user code as a special code to be used in the unique situation where an intruder
forces one to disarm the system "under duress".
When the [DURESS CODE] is entered, the Alarm Panel disarms normally - however a DURESS
REPORTING CODE is transmitted to the monitoring company to inform them that you have been forced
to disarm the Alarm Panel by an intruder.
It is advisable to choose a code that can easily be remembered by all family (or staff) members.
6.2 Installer Code
The Installer Code (location 197) is used by the installer to program and configure the Alarm Panel. It has
full access to all installer mode menus as listed in this manual.
6.3 Maintenance Code
The Maintenance Code (location 199) acts in a similar way to the Installer Code, but it has limited access
to installer menus. The default Maintenance Code is 8888, or 888888 for a 6-digit code. This code is used
to access the following locations:
Locations 17 –18 : Siren Time and Delay
Locations 20 –22 : Keypad Lockout and Sleep
Locations 25 –31 : Daylight Savings
Locations 171 –173 : No Movement, Auto Arm
Locations 174 –176 : No Movement, Medical Alarm
Locations 180 –190 : Auto Arm Times
The assignment of this property to a user allows the relevant user to perform certain “maintenance” tasks
that would ordinarily require the use of the installer code.
6.4 Download Code
The Download Code, location 198, (in conjunction with the Installer Code) is required for download
access via the IDS Download Software. The default Download Code is 9999 or 999999 for a 6-digit code.
NOTE:
It is possible to program location 34 to either allow or disallow defaulting of the Download Code.

Section: 7
IDS X64 Installer Manual 700-398-02D Issued August 2010
17
7. How to Read Location Values
Values within a data program location will be displayed by the zone LEDs in binary coded decimal format
i.e. zone LEDs 1-4 indicate units (ones) and zone LEDs 5-8 indicate tens (tens), and so on.
To read a binary value on the keypad, add up the values represented by each lit LED as shown in Table
1.
Table 1: Values Represented by each Zone LED
Zone LED
Value
Digit
Zone LED
Value
Digit
Zone 1
1
Units
Zone 9
1
Hundreds
Zone 2
2
Zone 10
2
Zone 3
4
Zone 11
4
Zone 4
8
Zone 12
8
Zone 5
1
Tens
Zone 13
1
Thousands
Zone 6
2
Zone 14
2
Zone 7
4
Zone 15
4
Zone 8
8
Zone 16
8
EXAMPLE:
Imagine the following zone LEDs are on: Zone 1, Zone 3 and Zone 5.
Units are represented by the sum of Zone 1 and Zone 3 (i.e. 1 + 4).
Tens of units are represented by the value of Zone 5 (i.e. 1 x ten).
Therefore, the displayed value is (1+4) + (10) = 15.
Values within a time program location are displayed in a similar format as per Table 2.
Table 2: Binary Coded Decimal Four Digit Display
Zone LED
Calculation
Unit
Zone LED
Calculation
Unit
1
(x 1 = 1)
M
9
(x 1 = 1)
S
2
(x 2 = 0)
10
(x 2 = 2)
3
(x 4 = 4)
11
(x 4 = 4)
Mm:Ss
4
(x 8 = 0)
12
(x 8 = 0)
= 45:36
5
(x 1 = 1)
m
13
(x 1 = 1)
s
M = LEDs 4 through 1
6
(x 2 = 0)
14
(x 2 = 2)
m = LEDs 5 through 8
7
(x 4 = 4)
15
(x 4 = 1)
S = LEDs 12 through 9
8
(x 8 = 0)
16
(x 8 = 0)
s = LEDs 16 through 13
Using an LCD keypad means that data and time information can be read directly without a need to
convert.

Section: 8
IDS X64 Installer Manual 700-398-02D Issued August 2010
18
8. Programming of the Panel
The X64 can be fully programmed using the X64 LED keypad; the system is optimised to use an LCD
keypad. The following section describes how programming data is represented in the X64 and how to
program it, specifically with the LED keypad.
For all programming procedures, the [*] key functions as the <ENTER> key and the [#] hash key
functions as a <CLEAR> or an <EXIT> program key.
Invalid data entries are indicated by means of an error beep consisting of 3 short beeps of the keypad
buzzer.
There are two location categories:
Standard locations which are single tiered and do not contain any sub-locations.
Extended locations, which are double tiered and have strings or sub-locations depending on the
installers programming preference.
Both standard and extended locations may contain further sub-categories referred to as bitmapped
locations.
For both main categories, clear visual keypad prompts are provided, which aid the programming
process.
NOTE:
When you use the [*] key to scroll through a bitmapped location, it will scroll through the pages.
When using the [*] key to scroll through numbered locations, it will scroll through the bytes.
Alpha-numeric locations (location 51 - telephone number), will show 1 digit per press of the [*]
key.
Numeric locations (location 197 –installers code), will show 2 digits per press of the [*] key.
To view how the data is represented, please see Table 1.
Below are various programming symbols you will see throughout the manual:
Indicates programming a standard location
Indicates programming using the string method
Indicates programming a sub-location
Indicates programming a location/sub-location with a bitmap
Where a hexadecimal number must be programmed, use the [MODE] key as per Table 3.
Table 3: Hexadecimal Values
Hex Value
Decimal Value
Key Strokes
A
10
[MODE] key then [0] key
B
11
[MODE] key then [1] key
C
12
[MODE] key then [2] key
D
13
[MODE] key then [3] key
E
14
[MODE] key then [4] key
F
15
[MODE] key then [5] key

Section: 8
IDS X64 Installer Manual 700-398-02D Issued August 2010
19
NOTE:
The hex values of A-F can be used for account codes. Only B-F can be used for telephone numbers.
This means that for locations 50-54, Ais NOT a hex number –but is rather used to CLEAR a telephone
number.
8.1 Entering Installer or Maintenance Mode
The following steps show how to enter into installer or maintenance mode.
1. Ensure that all partitions are unarmed.
2. Press the [#] key followed by the [INSTALLER CODE] or the [MAINTENANCE CODE].
3. The default installer code is 9999 or alternatively 999999 should a 6-digit default installer code
have been used.
4. Press the [*] key and a long beep will confirm entry into program mode. If a correct code has
been entered, the green READY LED will flash.
NOTE:
This will not work if the dialler is active at the time, or if one of the partitions are armed.
8.2 Programming Standard Locations
The following steps show how to program standard locations.
1. Ensure the panel is in program mode - the READY LED will be flashing.
2. Enter the [LOCATION NO.] of the program location you wish to view or change.
3. Press the [*] key, until the beep. The READY LED will become solid and the AWAY LED will flash.
4. The zone LEDs will display the data stored in the program location in binary format.
5. Enter the [NEW DATA] followed by the [*] key. A long beep will indicate a valid entry and the
AWAY LED will turn off. The READY LED will flash.
6. If you do not wish to change the data, press the [#] key. The READY LED will continue flashing
and the AWAY LED will turn off.
7. Repeat steps 2 - 5 until all the necessary locations have been programmed.
8. Press the [#]key to exit program mode.
9. The READY LED will stop flashing and the panel will return to the standby mode.
When programming a standard location, any attempt to enter invalid data will result in an error beep (3
short beeps).
The AWAY LED will remain on after the error beeps. Re-enter the correct data. There is no need to press
the [#] key.
EXAMPLE:
[INSTALLER CODE] [*] [0] [*] [VALUE] [*]
NOTE:
When you enter a standard location and press the [*] key, you will NOT be entering a sub-location –as
there is no sub-location to enter. What will happen is that you will scroll through the information in that
location. If you enter a digit, you will be changing the information stored in that position of the location, or
the location itself.

Section: 8
IDS X64 Installer Manual 700-398-02D Issued August 2010
20
EXAMPLE:
If you want to scroll through all the entries within a location with a LED keypad, you will input the following
data:
[INSTALLER CODE] [*] [LOCATION NO.] [*] [*] [*] [*], etc.
Scrolling through with the [*] key will show you all the numbers in a location. At the end of the allowed
locations, there will be a long beep to indicate that you are back at entry one of the location.
If you go to location 61 –Primary Account Codes, and then press the [*] key again followed by a digit,
you will be changing just the digit in that string.
8.3 Programming Extended Locations
The following steps show you how to program extended locations. These are locations that have sub-
locations. There are two ways to program extended locations: the string method or by using sub-
locations.
8.3.1. Using the String Method
Using the string method is a fast and efficient way to program the X64. By filling in the
programming sheets, the installer can first plan the installation, and then very quickly program multiple
locations.
1. Ensure that the panel is in program mode - the READY LED will be flashing.
2. Enter the [LOCATION NO.] of the program location that you wish to view or change.
3. Press the [*] key. The READY LED is on and the ARM and AWAY LEDs will flash.
4. The first sub-location of data on the LED keypad is displayed.
5. Enter the [STRING] for the program locations that you wish to change.
6. Press the [*] key, a long beep indicates a valid data entry.
7. The ARM and AWAY LEDs turn off and the READY LED will flash for the next location.
8. If you do not wish to change the data within this location, press the [#] key. The READY LED will
continue flashing and the ARM and AWAY LEDs will turn off.
9. Repeat steps 2 - 7 until all extended locations have been programmed.
10. Press the [#] key again to exit from program mode.
11. The READY LED will stop flashing and the panel will return to standby mode.
NOTE:
To view the rest of the string, use the [*] key to advance one sub-location at a time. At the end of the
allowed locations, there will be a long beep to indicate that you are back at entry one of the location. The
mode automatically reverts to Sub-location Mode - see “Using Sub-locations”.
When programming using the string method, any attempt to enter invalid data will result in an error beep
(3 short beeps).
The AWAY and ARM LEDs will remain on after the error beeps. Re-enter the correct data. There is no
need to press the [#] key.
EXAMPLE:
[INSTALLER CODE] [*] [1] [*] [0102040404040404] [*]
Other manuals for X64
6
Table of contents
Other IDS Keypad manuals
Popular Keypad manuals by other brands

SCS Sentinel
SCS Sentinel XO 006A Installation and user manual

Honeywell Home
Honeywell Home PROSIXLCDKP Series Installation and setup guide

International Electronics
International Electronics 212iL installation manual

Iget
Iget SECURITY EP13 quick start guide

HIK VISION
HIK VISION DS-PKFS-4 manual

Paradox
Paradox DigiplexNE DGP2-641 Reference and installation manual

Masterlock
Masterlock 27213 Guide

XPR Access
XPR Access LCS-RS user manual

Contro l4
Contro l4 Decora C4-KCB Series installation guide

Keyautomation
Keyautomation EGKTR Instructions and warnings for installation and use

Digi-Code
Digi-Code DGA installation manual

Contro l4
Contro l4 C4-KP2-Z-x installation guide