Instructions
Switching power supply/Battery charger providing 3.2A @ 13.8V 5
English
Signalling
The LED indicators [H] signal the presence of the mains voltage on the input terminals
and the proper operating capacity of the switching power-supply unit and its batteries.
The Fault signal can be obtained through the “STATUS” input [F] via the two Open-
Collector outputs “OC1” and “OC2”.
Removal of the jumper from the Earth fault signalling connector [I] deactivates the
Earth fault check.
If this appliance is used with a control panel all the obligatory status and fault signals
must be provided for and made available.
Installation
IPS12060G must be installed inside a fireproof enclosure (e.g. the control panel metal
case).
Using the two mounting holes [J], secure the device into its housing.
Connect the mains wiring to the input terminal board [A].
ATTENTION!
This appliance must be earthed.
Using the plastic cable band, bunch the mains wires and fasten them close to the mains
wire entry on the Switching power-supply unit.
The cables used for the wiring of the product must have an adequate section and
comply with the IEC 60332-1-2 or IEC 60332-2-2 standards.
For an installation that meets standard requirements, it is necessary to fit a suitable
sectioning device (bipolar) and protection on the electrical-wiring upstream of the
switching power-supply unit in accordance with the laws in force (DM37/08).
The output voltage can be drawn from either terminals [C] (“+V, -V”), or from the
connector [D] (“+V, -V”).
The output connector is also has “FAULT” and “RTH” terminals which are reserved for
connection to INIM control panels.
If you are installing a ProbeTH thermal probe, connect it to connector [E].
Attach the thermal probe to one of the batteries in such a way as to achieve an optimal
level of thermal conductivity.
Note
The backup batteries of the equipment power supply are not included. The installer must use only
valve regulated lead-acid batteries (VRLA) for stationary use, compliant with IEC 60896-21 and
IEC 60896-22 standards.
The battery casing must have V-2 flame rating or higher.
If this appliance is used with a fire detection control panel, it is obligatory to fit it with a thermal
probe.
Maintenance
The following maintenance operations must be performed regularly:
• Check that all wiring and connections are intact.
• Check that the appliance is operating properly.
• Check the battery efficiency.
Note
These maintenance operations must be performed by qualified persons only.
Signalling Off On Blinking
fast slow
Green LED (DL1) Switching power-supply unit
Off Switching power-supply unit
operating Overheated Output overload
Yellow LED (DL2) Mains operating properly Mains operating fault Earth fault /
Yellow LED (DL3) Batteries operating properly Battery fault / /
Output OC1 Operating properly Switching power-supply unit
fault //
Output OC2 Mains operating properly Mains operating fault / /