Page 10 www.123filter.com | +1 (678) 261-7611 | support@123filter.com
Step 5. Connect the drain hose and clamp to the system tightly to ensure a secure connection.The other
end of the drain hose goes to the sewage pipe.
There must be sufficient space (~10 cm) between the outlet of the drain hose and the sewage level to
prevent sewage from flowing back to the product. The sewage pipe should be 30 cm higher than the
ground, and the drain hose should be fixed on the sewage pipe.
Step 6. Plug in the power adapter and connectthe other end of the socket to supply power to the system.
Step 7. Rotate the bypass valve knobs to the bypass position.
Step 8. Slowly turn on the main water supply.
Step 9. Open a cold water tap nearby and let the water run for a few minutes till the water runs clean
or until the system is free of foreign material caused by plumbing work. Then close the tap.
Step 10. Then, slowly open the water inlet knob on the bypass valve (the valve should be opened at an
angle of about 45°). Start regeneration and wait for the "BACKWASH" text on display to stop
flashing and start to count down, then unplug thepowersupply, and keep the device in the backwash
state. All keys will lock after3minutes during thestandby status. Pressandhold the "MENU"
key for 3 seconds to unlock.
Step 10. a. To perform the regeneration processes, press and hold the "SET/REGEN" key for 3
seconds in the unlocked state to enter manual regeneration mode.
Step 10. b. Press the "SET/REGEN" button again to select "IMMEDIATE REGENERATION".
Step 11. Let the water run until the air is purged from the unit (the exhaust sound disappears, and water
steadily flows out of the drain hose), fully open the water inlet knoband let the water run until the
water is clear, then reconnect the power supply. Press the "SET/REGEN" button to skip the rest
of the regeneration process and until back to standby.
Step 12. Rotate the bypass valve knobs to the service position and observe whether there is water
leakage or any other leakage at each connection. After ensuring safety, rotate the knobs to the bypass
position and soak the filter material for 10 minutes.
Step 13. Rotate the bypass valve knobs to the service position. Next, perform at least two filter material
washing processes.
Step 13. a. To perform the filter material washing processes, press and hold the "↑"/"↓" keys for
3 seconds in the unlocked state to enter the user menu settings.
Step 13. b. Press the "SET/REGEN" button to confirm the parameter setting and enter the next
parameter setting option.
Step 13. c. Press the "↑" /"↓" keys to adjust the value.
Step 13. d. Press the "SET/REGEN" button again to confirm the parameter setting and until
"PROGRAMMING COMPLETE".
Step 13. e. Press and hold the "SET/REGEN" button for 3 seconds to enter the manual regeneration
mode.
Step 13. f. Press the "SET/REGEN" button again to select "IMMEDIATE REGENERATION".
Filter material washing process: backwash (5-10 minutes) and rinse (5 minutes).
Step 14. Open a cold water tap nearby and let the water run for at least 5 minutes or until the water is
clear. Then close the tap. Verify the water is completely clear before use.
Step 15. Check again for any water leakage in the pipeline and whether the fittings at the connection
parts with the original pipeline cause loosening or water seepage from construction.
Step 16. Set up the system parameters of the equipment (see Programming the Central Water Filtration
System for details, page 11-13).
Default regeneration process: backwash (15 minutes) and rinse (10 minutes).
Step 17. Clean the installation site.