JABLOTRON ALARMS a.s.
Pod Skalkou 4567/33 46601 Jablonec n. Nisou
Czech Republic www.jablotron.com
||
|
The JA-110ST Bus combined smoke and heat fire detector
The JA-110ST Bus combined smoke and heat fire detector 1 / 2 MLW51605
The JA-110ST is a component of the JABLOTRON JA-100 system.
It is used to detect fire hazards in a building interior. The product is not
designed to be installed in industrial premises. The JA-110ST consists
of an optical smoke detector and a heat detector. The optical smoke
detector is very sensitive to large dust particles which are present in
dense smoke. It is less sensitive to smaller particles generated by the
combustion of liquids such as alcohol. That is why the fire detector also
contains a built-in heat detector which has a slower reaction but is
much better at detecting fire which generates only a small amount of
smoke. The detector has a status reaction (reports its activation and
deactivation). The detector should be installed by a trained technician
with a valid certificate issued by an authorized distributor.
Detector location
The smoke detector must be installed so that any smoke easily drifts
into the detector owing to natural thermal currents (usually on the
ceiling). The detector can only be used in enclosed interiors. It is not
suitable for interiors where smoke can disperse over a large area and
cool down (e.g. interiors with extremely high ceilings – above 5 m) – the
smoke would not reach the detector position.
The detector must always be placed in the section leading to the exit
of the building (escape route), see Figure 1. If the building has a floor
area greater than 150 m2, installation of an additional detector in some
other suitable place is required, see Fig.2.
1
2
3 4
5
Fig 1
1
2
3 4
5
6
Fig 2
1
2
3
6
Fig 3
1. kitchen,
2. living room,
3. – 6.
bedrooms
y/
basic
coverage
{
recommended
coverage
It is recommended to place additional detectors in rooms where
people sleep.
Installation on level ceilings
Place the detector in the centre of the room if possible. The detector
must not be recessed into the ceiling due to the possible existence
of a cool air layer on the ceiling. Never place the detector in the
corner of the room (always keep at least a 0.5 m distance from the
corner) see Fig 4. There is an insufficient circulation of air in corners.
Installation on sloping ceilings
If the ceiling is not suitable for mounting on a level surface (e.g. a
room under a roof ridge), the detector can be installed as in Fig. 5.
0.5m
TOP
Fig 4
0,9 m
Fig 5
centre of the room, best location
acceptable location
Walls, partitions, barriers and lattice ceilings
The JA-110ST detector must not be installed closer than 0.5 m
from any wall or partition. A narrow space with a width of less than
1.2m requires the detectors to be placed at a distance of at least one
third of its width away. In a case when a room is separated into
sections with furniture, racks or semi partition walls which do not reach
the ceiling, the space is considered to be fully separated if the gap
between the top of these and the ceiling does not exceed 0.3 m.
A free space of at least 0.5m is required under and around the detector.
Any irregularities of the ceiling (e.g. girders) exceeding 5 % of the
ceiling height should be considered a wall and the above-mentioned
limitations should apply.
Ventilation and air circulation
The detectors must not be installed directly by ventilation or air
conditioning vents, etc. In the case of air being supplied through a
perforated ceiling, each detector must be placed so that no perforation
hole occurs within 0.6 m of the detector.
Avoid installing the detector in the following locations:
places with poor air circulation (niches, corners, apexes of
A-shaped roofs, etc.)
places exposed to dust, cigarette smoke or steam
places with over-intense air circulation (close to ventilators, heat
sources, air conditioning outlets, etc.)
in kitchens and other cooking places (because steam, smoke or
oily fumes can cause false alarms or reduce detector sensitivity).
beside fluorescent lights or energy-saving light bulbs (electrical
interference can cause a false alarm)
in areas with lots of small insects
Warning: Most false alarms are caused by improper
detector location.
See CEN/TS 54-14 standards for detailed installation guidelines.
Installation
When installing the detector, abide by the procedures
recommended in the previous paragraphs.
1 2
3
BUS
1400- 0 0- 0000- 000 1
5
4
6
Fig 6: 1– detector cover opening (removal); 2 – detector cover closing
(insertion); 3 – optical signalling; 4 – arrow showing where to insert the
detector; 5 – bus connection terminals; 6 – production code;
1. open the detector cover, by turning it anti-clockwise
2. Insert the bus cable and attach the plastic base to the selected
place using screws.
3. Connect the bus cable.
The JA-110ST Bus combined smoke and heat fire detector
The JA-110ST Bus combined smoke and heat fire detector 2 / 2 MLW51605
When connecting the module to
the bus, always switch the power off.
4. Proceed according to the control panel installation manual. Basic
procedure:
a. When the device is powered, the yellow LED starts flashing
repeatedly to indicate that the module has not been enrolled
into the system.
b. Go to the F-Link program, select the required position in the
Devices window and launch the enrollment mode by clicking
on the Enroll option.
c. Insert the detector into the plastic base. It can only be inserted
in the position marked with arrows on both plastic parts. Close
the detector by turning it clockwise. The tamper contact inside
the detector is thus triggered and the detector is enrolled. The
yellow LED indicator goes off.
Detector settings
Go to the Devices window in the F-Link program. When you are at
the detector position, use the Internal settings option to open a dialog
window where you can set:
LED indication enabled: allows disabling the red LED used to
indicate activation.
Means of detecting – smoke only, heat only, smoke and heat at the
same time, smoke or heat.
Detector testing and maintenance
The functioning of the detector can be tested with a special spray
designed for smoke detector testing to simulate fire. The valid EN
standards recommend you to perform detector testing once in 30
days. The detector must be regularly cleaned of dust, cobwebs, etc.
Warning: never test the detector with fire.
Fault indication
The detector checks its functioning automatically. When it discovers a
fault, it indicates it with the yellow LED indicator. In such a case,
disconnect the power supply for 1 minute and then reconnect it. If the
LED indicator starts lid permanently again after 1 minute, send the
detector to a service centre.
Technical specifications
Power from control panel digital bus 12 V (9…15 V)
Current consumption in standby mode 5 mA
Current consumption for cable selection 10 mA
Dimensions diameter 126 mm, height 50 mm
Smoke detection optical light scattering
Smoke detector sensitivity m = 0.11 - 0.13 dB/m pursuant to EN 54-7
Heat detection class A2 according to EN 54-5
Alarm temperature 60°C to 70°C
Operating temperature range -10°C to +80°C
Complies with EN 54-5, EN 54-7
EN 50130-4, EN 55022
JABLOTRON ALARMS a.s. hereby declares that the JA-110ST module is in
compliance with the essential requirements and other relevant provisions of
Directive 89/106/EEC a 2004/108/EC. The original of the conformity assessment
can be found at www.jablotron.com - Technical Support section
Note: Although this product does not contain any harmful materials
we suggest you return the product to the dealer or directly to the
producer after use. For more detailed information visit
www.jablotron.com.

Other jablotron Smoke Alarm manuals

jablotron SD-283ST User manual

jablotron

jablotron SD-283ST User manual

jablotron SD-503ST User manual

jablotron

jablotron SD-503ST User manual

jablotron JA-82ST User manual

jablotron

jablotron JA-82ST User manual

jablotron JA-151ST User manual

jablotron

jablotron JA-151ST User manual

jablotron JA-60SP User manual

jablotron

jablotron JA-60SP User manual

jablotron SD-212 User manual

jablotron

jablotron SD-212 User manual

jablotron SD-209 User manual

jablotron

jablotron SD-209 User manual

jablotron JA-185ST User manual

jablotron

jablotron JA-185ST User manual

jablotron SD-280 User manual

jablotron

jablotron SD-280 User manual

jablotron SD-212SP User manual

jablotron

jablotron SD-212SP User manual

jablotron JA-65ST User manual

jablotron

jablotron JA-65ST User manual

jablotron JA-150ST User manual

jablotron

jablotron JA-150ST User manual

jablotron JA-85ST User manual

jablotron

jablotron JA-85ST User manual

jablotron JA-85ST User manual

jablotron

jablotron JA-85ST User manual

jablotron JA-111ST-A User manual

jablotron

jablotron JA-111ST-A User manual

jablotron JA-110ST User manual

jablotron

jablotron JA-110ST User manual

jablotron JA-82ST User manual

jablotron

jablotron JA-82ST User manual

jablotron JA-60SR User manual

jablotron

jablotron JA-60SR User manual

jablotron JA-63ST User manual

jablotron

jablotron JA-63ST User manual

jablotron SD-728 User manual

jablotron

jablotron SD-728 User manual

Popular Smoke Alarm manuals by other brands

Fireye SP-48-NG-FD-S instruction manual

Fireye

Fireye SP-48-NG-FD-S instruction manual

Visonic WST-400 installation instructions

Visonic

Visonic WST-400 installation instructions

BAT BT 166 manual

BAT

BAT BT 166 manual

American Sensor SA360 user manual

American Sensor

American Sensor SA360 user manual

First Alert SA150B user manual

First Alert

First Alert SA150B user manual

Honeywell ADEMCO 5806 installation instructions

Honeywell

Honeywell ADEMCO 5806 installation instructions

ADEMCO 5808LSTA installation instructions

ADEMCO

ADEMCO 5808LSTA installation instructions

Firex 2650-560 installation instructions

Firex

Firex 2650-560 installation instructions

Firex 2650-660 Product overview

Firex

Firex 2650-660 Product overview

Universal Security Instruments SS-775-LR instructions

Universal Security Instruments

Universal Security Instruments SS-775-LR instructions

Bosch FERION 4000 O instructions

Bosch

Bosch FERION 4000 O instructions

Orientalert VST-IS588 user manual

Orientalert

Orientalert VST-IS588 user manual

Alecto SA-19/5 manual

Alecto

Alecto SA-19/5 manual

ELRO FZ5002R instruction manual

ELRO

ELRO FZ5002R instruction manual

Firex 591S Specification sheet

Firex

Firex 591S Specification sheet

Arton SPD-3.4 user manual

Arton

Arton SPD-3.4 user manual

Smartlink Medi Minder Guardian user manual

Smartlink

Smartlink Medi Minder Guardian user manual

Siemens OH921 installation instructions

Siemens

Siemens OH921 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.