Janus Sv Series User manual

FM-200® Fill Manual
Sv Series, Mv Series, Lv Series
Issued August 16, 2010
DOC180 REV B

BLANK

Page: iii
FM-200® FILL MANUAL
Revision B Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
BLANK
Contents
1 GENERAL INFORMATION 1
1.1 Listings and Approvals 1
1.2 Extinguishing Agent 1
1.3 Safety Considerations 1
2 CYLINDER ASSEMBLY 3
2.1 Cylinder 3
2.1.1 Rupture Disc 3
2.1.2 Liquid Level Indicator 3
2.2 Dip Tube 4
2.3 Cylinder Valve 4
2.3.1 Sv Series Valve Features 5
2.3.2 Mv Series Valve Features 6
2.3.3 Lv Series Valve Features 7
3 FILL COMPONENTS 9
3.1 Fill Adapter 9
3.1.1 Sv Series Fill Adapter 9
3.1.2 Mv Series Fill Adapter 9
3.1.3 Lv Series Fill Adapter 9
3.2 Cylinder Fill Assembly 10
3.2.1 Pump Connection Port 10
3.2.2 Cylinder Connection Port 10
3.2.3 Gauge Connection Port 10
3.2.4 Nitrogen Pressurization Port 11
3.3 Nitrogen Regulator/Hose Assembly 11
3.3.1 Valve Closing Line 11
3.3.2 Cylinder Pressurization Line 11
3.4 Valve Closing Adapter 12
3.5 Agent Supply Tank 12
3.6 Agent Fill Station 12
3.6.1 Fill Station Displays 13
3.6.2 Selector Control Knob 13
3.6.3 Pump Control Knob 13
3.6.4 Agent/Nitrogen Selection Knob 13
4 FILL PROCEDURE 15
4.1 Log and Weigh Empty Cylinder 15
4.2 Agent Fill Procedure 15
4.2.1 Seating Cylinder Valve 17
4.2.2 Cylinder Weighing 17
4.2.3 OverllRetrievalProcedure 18
4.3 Pressurization Procedure 19
4.3.1 Finalization Procedure 22
5 SYSTEM RECHARGE AND RESET 23
5.1 Piping and Nozzles 23
5.2 Recharging 23
5.2.1 Removing The Cylinder 23
5.2.2 Cleaning and Servicing The ValveAssembly 24
5.2.3 Recharge Procedure 25
APPENDIX A - MATERIAL SAFETY DATASHEET 27
APPENDIX B - ASSORTED CHARTS 35
APPENDIX C - LIQUID LEVEL INDICATOR REPLACEMENT 49

Page: iv
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Diagram Index
Figure 2.3.1 Sv Cylinder Valve Assembly 5
Figure 2.3.2 Mv Cylinder Valve Assembly 6
Figure 2.3.3 Lv Cylinder Valve Assembly 7
Figure 3.1.1 Sv Series Fill Adapter 9
Figure 3.1.2 Mv Series Fill Adapter 9
Figure 3.1.3 Lv Series Fill Adapter 9
Figure 3.2 Cylinder Fill Assembly 10
Figure 3.3 Nitrogen Regulator/Hose Assembly 11
Figure 3.6 Agent Fill Station 12
Figure 3.4 Valve Closing Adapter 12
Figure 4 Cylinder Fill P&ID Diagram 15
Figure C.1 LLI Exterior 50
Figure C.2 LLI Interior 50
Figure C.3 Ball Float 51
Table Index
Table 2.1 Cylinder Capacities 3
Table 5.2.2 Valve Replacement Components 25
Table B.1 - Approximate Container Pressure vs. Temperature 36
Table B.2a U.S. Standard to Metric Conversion Factors (Approximate) 37
Table B.2b Metric to U.S. Standard Conversion Factors (Approximate) 37
Table B.3a Liquid Level Chart – 250 lb Cylinder (U.S. Standard) 38
Table B.3b Liquid Level Chart – 250 lb Cylinder (Metric) 39
Table B.4a Liquid Level Chart – 420 lb Cylinder (U.S. Standard) 40
Table B.4b Liquid Level Chart – 420 lb Cylinder (Metric) 41
Table B.5a Liquid Level Chart – 600 lb Cylinder (U.S. Standard) 42
Table B.5b Liquid Level Chart – 600 lb Cylinder (Metric) 43
Table B.6a Liquid Level Chart – 900 lb Cylinder (U.S. Standard) 44
Table B.6b Liquid Level Chart – 900 lb Cylinder (Metric) 45
Table B.7a Liquid Level Chart – 1000 lb Cylinder (U.S. Standard) 46
Table B.7b Liquid Level Chart – 1000 lb Cylinder (Metric) 47

Page: v
FM-200® FILL MANUAL
Revision B Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Revision Description of Change Date
--- Initial Printing 16-Aug-2010
A Caution beginning "Ensure that the pilot actuation port pipe plug" added to Sections
2.3.1, 2.3.2, 2.3.3, and 4.2. All references to "Dow Corning No. 4" replaced with
"Molykote 55 by Dow Corning (P/N 19056)".
31-May-2011
B Appendix C added. 02-Apr-2012
Revision History

Page: vi
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
BLANK

Page: vii
FM-200® FILL MANUAL
Revision B Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Preface
This manual is intended for use with the Janus Fire Systems® Sv Series, Mv Series, and Lv Series FM-200®
EngineeredFireExtinguishingSystems.Thoseresponsiblefortheagentlloragentrellofthesesystemsshould
read this entire manual.
All design, implementation, and maintenance of the Janus Fire Systems® Engineered Fire Extinguishing Systems
must be performed in compliance with the National Fire Protection Association (NFPA) 2001 - Standard on Clean
Agent Fire Extinguishing Systems, NFPA 70 - The National Electrical Code, NFPA 72 - The National Fire Alarm
Code, and the guidelines outlined in this manual.
AllsystemdesignsarepreformedinconjunctionwiththeJanusDesignSuite®hydraulicowcalculationsoftware
and in compliance with the Janus Design Suite® Flow Calculation Software Manual, DOC106.
Janus Fire Systems® reserves the right to revise and improve its products as it deems necessary without prior
notication.ThismanualdescribesthestateofJanusFireSystems®productsatthetimeofitspublicationandmay
notreectthoseproductsatalltimesinthefuture.
All references to Codes or Standards in this manual refer to the latest edition of that Code or Standard unless
otherwise indicated.
Compressed gases shall be handled and used only by persons properly trained in accordance with Compressed
Gas Association, Inc. (CGA) pamphlets C-1, C-6, and P-1.
CGA pamphlets are published by the Compressed Gas Association Inc. (www.cganet.com).
The contents of this manual may not be reproduced in any form without the express written consent of Janus Fire
Systems.
Copyright © 2010 Janus Fire Systems. All Rights Reserved. Janus Fire Systems® and Janus Design Suite® are registered trademarks of
Janus Fire Systems.
FM-200® is a registered trademark of E.I. du Pont de Nemours and Company used under license by Janus Fire Systems.
Janus Fire Systems
1102 Rupcich Drive
Millennium Park
Crown Point, IN 46307
TEL: (219) 663-1600 FAX: (219) 663-4562
e-mail:info@janusresystems.com·www.janusresystems.com
BLANK

Page: viii
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
BLANK

Page: 1
FM-200® FILL MANUAL
Revision B Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 1 General Information
1 GENERAL INFORMATION
is manual describes the procedure for lling Janus Fire Systems® Sv Series, Mv Series, and Lv Series
cylinder assemblies with FM-200® agent.
1.1 Listings and Approvals
To maintain FM Approval for Janus Fire Systems® Fire Suppression Systems, cylinder recharge must be
performed at a Janus Fire Systems® recognized facility.
1.2 Extinguishing Agent
FM-200® (HFC-227ea) is a colorless, non-toxic gas and a clean, eective, environmentally acceptable,
electrically non-conductive re suppression agent. It is formed from the elements carbon, uorine and
hydrogen (CF3CHFCF3 - heptauoropropane). e primary extinguishing mechanism of FM-200® is
heat absorption, with a secondary chemical contribution from the thermal decomposition of FM-200® in
the ame.
Most metals, such as aluminum, brass, steel, and stainless steel, as well as plastics, rubber, and electronic
components, are not aected by exposure to FM-200®.
In Janus Fire Systems® FM-200® Fire Suppression Systems, the FM-200® agent is stored as a liquid in steel
cylinders and superpressurized with nitrogen to 360 psig (24.8 bar) at 70°F (21.1°C) to improve its ow
characteristics. When discharged, FM-200® vaporizes at the discharge nozzles and becomes thoroughly
mixed with the air throughout the protected area reaching a predetermined design concentration.
1.3 Safety Considerations
All safety guidelines contained in this manual must be read and understood before lling any Janus Fire
Systems® cylinder. All applicable guidelines shall be followed before, during, and after the ll procedure
including any additional local standards or regulations determined by the authority having jurisdiction
(AHJ). Where the guidelines in this manual and local guidelines or regulations conict, the most stringent
requirement should be followed.
ose individuals responsible for the lling of a Janus Fire Systems® FM-200® cylinder assembly must be
trained.
At a minimum, Janus Fire Systems recommends the following safety equipment be worn at all times during
the ll procedure:
• Work boots with protective toe guards
• Safety glasses or goggles
• Gloves to prevent injury of the hands or ngers.
• Properly tting clothing.
• Properly tting ear plugs or other hearing protection.
BLANK

Page: 2
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 1 General Information
Cylinder lling must be performed in a well ventilated area.
When FM-200® is exposed to temperatures greater than 1300°F (700°C), the potentially hazardous byproduct
hydrogenuoride(HF)willbeformedduringagentdecomposition.Heatsourcessuchasspaceheaters,torches,
welding equipment, or lit cigarettes are capable of reaching temperatures that initiate agent decomposition. All
suchpotentialheatsourcesmustbeclearedfromtheworkareabeforebeginningllprocess.Smokinginthe
vicinityofthellingequipmentoragentstoragecontainersshallbeprohibited.
e Material Safety Data Sheet (MSDS) on FM-200® can be found in Appendix A of this manual and shall
be read and understood before working with the agent. Refer also to DuPont FM-200® Fire Extinguishing
Agent Properties, Uses, Storage and Handling document K23261 found at www2.dupont.com/FE/en_US/
tech_info/index.html for specic agent handling procedure.
Accidental discharge of an unsecured cylinder may result in property damage, injury, or death from
violent cylinder movement.Cylinderassembliesmustberestrainedatalltimesduringthellprocedure.Anti-
recoilsafetyplugsanddevicesmustbeinplaceatalltimesthecylinderassemblyisnotconnectedtoagentll
lines or discharge piping. Do not transport the cylinder unless the anti-recoil safety device is in place. Handle the
cylinder assembly with care even when the safety device in is place.
e technical manual supplied with the ll station or pump must be read and understood prior to lling
cylinder assemblies. All procedures contained in the aforementioned manual must be followed and all
warnings or safety guidelines noted.
ThellingstationorpumpdesignatedforusewithFM-200®shallnotbeusedwithanyotheragents.Eachagent
storedatallfacilitymusthaveitsownseparatellingstationorpump.Useofmultipleagentswithasinglelling
station may result in contamination of agent and dilute its effectiveness as a means of suppression.

Page: 3
FM-200® FILL MANUAL
Revision B Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 2 Cylinder Assembly
2 CYLINDER ASSEMBLY
e cylinder assembly consists of the cylinder, dip tube, and cylinder valve.
2.1 Cylinder
e FM-200® agent is stored as a liquid inside a welded steel cylinder. e cylinders are superpressurized
with dry nitrogen to a pressure of 360 psig (24.8 bar) at 70°F (21°C). Every cylinder has a minimum ll
density of 35 lb/ft3(561 kg/m3) and a maximum ll density of 70 lb/ft3(1121 kg/m3). e capacity of a
cylinder varies according to the design requirements and the Series designation (See Table 2.1 for a list of
available capacities).
Standard domestic cylinders
are manufactured according
to the requirements of
the U.S. Department of
Transportation (USDOT)
andTransport Canada1(TC)
for compressed gas and are
tted with an identication
label indicating the ll
quantity of FM-200®.
Each cylinder has internal
neck threads to allow for
connection to the cylinder
valve.
2.1.1 Rupture Disc
A frangible rupture disc is tted to the Lv Series cylinder body. It functions as an emergency relief device in
the event of excessive internal pressure within the cylinder. Its rupture point is between 850 psi (58.6 bar)
and 1000 psi (68.9 bar).
is feature is not found on the Sv Series or Mv Series cylinder. Instead, a rupture disc is located on the side
of Sv Series and Mv Series cylinder valve as detailed in sections 2.3.1 and 2.3.2.
2.1.2 Liquid Level Indicator
e liquid level indicator consists of a sealed non-magnetic tube containing an external measurement tape
tted with a magnet. A second magnet with an opposing polarity is installed on the outside of the tube and
is exposed to the FM-200® liquid. As the tape is extracted from the tube, it will engage with the second
magnet creating a noticeable change in tension. e measure on the tape when this change in tension
occurs indicates the current liquid level inside the cylinder and can then be compared to a chart located in
Appendix B of this manual to determine the current ll weight of the cylinder.
e liquid level indicator assembly is threaded into an outlet on the head (top) of the Mv Series and Lv
Series cylinders.
is feature is not found on the Sv Series cylinder.
Table 2.1 Cylinder Capacities
Valve
Series
Nominal
Cylinder
Size P/N Fill Capacity Empty
Weight
Minimum Maximum
lb kg lb kg lb kg
Sv 40 lb 18583 22 10.0 49 19.5 36 16.3
Sv 80 lb 18584 41 18.6 81 36.7 65 29.5
Sv 130 lb 18585 66 29.9 131 59.4 77 35.0
Mv 250 lb 18525 126 57.2 252 114.3 213 96.6
Mv 420 lb 18526 211 95.7 422 191.4 279 126.6
Lv 600 lb 18527 304 137.9 609 275.3 346 157.0
Lv 900 lb 18528 455 206.4 910 412.7 471 213.6
Lv 1000 lb 18529 561 254.5 1000 453.6 766 346.5
Ordering Instructions: Specify the Cylinder Assembly P/N followed by a dash
andthellweightinpoundsexpressedinthreedigits.
11000 lb Cylinders are not Transport Canada approved.

Page: 4
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
2.2 Dip Tube
A rigid dip tube is threaded into the cylinder valve and extends down the entire length of the cylinder.
2.3 Cylinder Valve
A dierential pressure operated cylinder valve controls the release of FM-200® from the cylinder. It is made
of forged brass and is threaded onto the cylinder neck. e features and design of each valve vary according
to the Series designation.
Section 2 Cylinder Assembly

Page: 5
FM-200® FILL MANUAL
Revision B Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 2 Cylinder Assembly
2.3.1 Sv Series Valve Features
(See Figure 2.3.1)
e Sv Series valve has six key features:
1. Valve Actuation Connection: A threaded connection located on top of the cylinder valve serves as the
attachment point for the electric (primary) or pneumatic (slave) valve actuator.
2. Pressure Gauge: A pressure gauge is mounted to the cylinder valve exterior to provide a visual measure
of the cylinder’s internal pressure. e gauge shall not be removed while the cylinder is under pressure.
3. Rupture Disc: A frangible rupture disc is tted to the valve body opposite the pressure gauge. It
functions as an emergency relief device in the event of excessive internal pressure within the cylinder.
Its rupture point is between 850 psi (58.6 bar) and 1000 psi (68.9 bar). e rupture disc shall not be
removed while the cylinder is under pressure.
4. Low-Pressure Supervisory Switch: A low-pressure supervisory switch is mounted to the cylinder valve
and continuously monitors the internal pressure of the cylinder. It shall not be removed while the
cylinder is under pressure.
5. Discharge Outlet: A 1 1/4 in (32 mm) FNPT connection serves as the attachment point for the
discharge piping.
6. Pilot Actuation Port: A 3/8 in (10 mm) FNPT connection (shipped with a pipe plug) serves as the
attachment point for the pilot actuation piping in multiple cylinder systems, providing the actuation
pressure used to open the slave cylinder valve(s). is can also be used for attachment of the discharge
pressure switch in single cylinder arrangements. e pipe plug shall remain in place at all times when
the port is not connected to pilot actuation piping or a discharge pressure switch.
Figure 2.3.1 Sv Cylinder Valve Assembly
Pilot Actuation
Port
Pipe Plug
Rupture Disc (3)
Pressure Gauge (2)
Low-Pressure
Supervisory Switch (4)
Discharge Outlet
Anti-Recoil
Safety Plug
Safety Cap
Discharge
Outlet (5) Pilot
Actuation
Port (6)
Low-Pressure
Supervisory Switch (4)
Valve Actuation
Connection (1)
Ensurethatthepilotactuationportpipeplugisinplacebeforeattemptingtollthecylinderassembly.Failureto
dosomayresultinagentleakingoutofthepilotactuationportduringthellprocedure.

Page: 6
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 2 Cylinder Assembly
2.3.2 Mv Series Valve Features
(See Figure 2.3.2)
e Mv Series cylinder valve has six key features:
1. Valve Actuation Connection: A threaded connection located on top of the cylinder valve serves as the
attachment point for the electric (primary) or pneumatic (slave) valve actuator.
2. Pressure Gauge Connection: A female connection serves as the attachment point for the pressure
gauge. It is tted with a Schrader valve to allow the removal of the gauge while the cylinder is
pressurized.
3. Low-Pressure Supervisory Switch Connection: A female connection serves as the attachment point
for the low-pressure supervisory switch. A Schrader valve allows for the removal of the pressure switch
while the cylinder is pressurized.
4. Rupture Disc: A frangible rupture disc is tted to the valve body opposite the discharge outlet. It
functions as an emergency relief device in the event of excessive internal pressure within the cylinder.
Its rupture point is between 850 psi (58.6 bar) and 1000 psi (68.9 bar). e rupture disc shall not be
removed while the cylinder is under pressure.
5. Discharge Outlet: A 2 in (50 mm) grooved connection serves as the attachment point for discharge
piping.
6. Pilot Actuation Port: A 1/4 in (8 mm) NPT connection (shipped with a pipe plug) serves as the
attachment point for the pilot actuation piping in multiple cylinder systems, providing the actuation
pressure used to open the slave cylinder valve(s). is can also be used for attachment of the discharge
pressure switch in single cylinder arrangements. e pipe plug shall remain in place at all times when
the port is not connected to pilot actuation piping or a discharge pressure switch.
Figure 2.3.2 Mv Cylinder Valve Assembly
Pressure Gauge
Connection (2)
Grooved
Coupling (Part
of Anti-Recoil
Safety Device)
Low-Pressure
Supervisory Switch
Connection (3)
Pilot Actuation
Port (6)
Safety
Cap
Rupture
Disc (4)
Valve Actuation
Connection (1)
Discharge
Outlet (5)
Pressure Gauge
Connection (2)
Ensurethatthepilotactuationportpipeplugisinplacebeforeattemptingtollthecylinderassembly.Failureto
dosomayresultinagentleakingoutofthepilotactuationportduringthellprocedure.

Page: 7
FM-200® FILL MANUAL
Revision B Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 2 Cylinder Assembly
2.3.3 Lv Series Valve Features
(See Figure 2.3.3)
e Lv Series cylinder valve has ve key features:
1. Valve Actuation Connection: A threaded connection located on top of the cylinder valve serves as the
attachment point for the electric (primary) or pneumatic (slave) valve actuator.
2. Pressure Gauge Connection: A female connection serves as the attachment point for the pressure
gauge. It is tted with a Schrader valve to allow the removal of the gauge while the cylinder is
pressurized.
3. Low-Pressure Supervisory Switch Connection: A female connection serves as the attachment point
for the low-pressure supervisory switch. A Schrader valve allows for the removal of the pressure switch
while the cylinder is pressurized.
4. Discharge Outlet: A 3 in (80 mm) grooved connection serves as the attachment point for discharge
piping.
5. Pilot Actuation Port: A 1/4 in (8 mm) NPT connection (shipped with a pipe plug) serves as the
attachment point for the pilot actuation piping in multiple cylinder systems, providing the actuation
pressure used to open the slave cylinder valve(s). is can also be used for attachment of the discharge
pressure switch in single cylinder arrangements. e pipe plug shall remain in place at all times when
the port is not connected to pilot actuation piping or a discharge pressure switch.
Figure 2.3.3 Lv Cylinder Valve Assembly
Pressure Gauge
Connection (2)
Low-Pressure
Supervisory Switch
Connection (3)
Pilot Actuation
Port (5)
Safety
Cap
Valve Actuation
Connection (1)
Discharge
Outlet (4)
Pressure Gauge
Connection (2)
Grooved
Coupling (Part
of Anti-Recoil
Safety Device)
Ensurethatthepilotactuationportpipeplugisinplacebeforeattemptingtollthecylinderassembly.Failureto
dosomayresultinagentleakingoutofthepilotactuationportduringthellprocedure.

Page: 8
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 2 Cylinder Assembly
BLANK

Page: 9
FM-200® FILL MANUAL
Revision B Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 3 Fill Components
3 FILL COMPONENTS
e following components are necessary to ll a Janus Fire Systems® cylinder assembly with FM-200®.
3.1 Fill Adapter
A ll adapter is installed into the discharge outlet of the cylinder valve during the ll procedure to
accommodate the attachment of the cylinder ll assembly. Each Series valve requires a dierent type of ll
adapter.
3.1.1 Sv Series Fill Adapter
P/N 99515 (See Figure 3.1.1)
e Sv Series ll adapter consists of a 1-1/4 in (32 mm) MNPT
pipe plug tted with a 1/4 in (8 mm) male quick-connect tting.
e 1-1/4 in (32 mm) MNPT connection attaches to the Sv Series
discharge valve in place of the anti-safety recoil device. e 1/4 in (8
mm) male quick-connect tting attaches to a 1/4 in (8 mm) female
quick-connect tting on the cylinder ll assembly. e male quick-
connect tting contains an internal check valve that prevents agent
from owing through the tting unless it is connected to the cylinder
ll assembly.
3.1.2 Mv Series Fill Adapter
P/N 99514 (See Figure 3.1.2)
e Mv Series ll adapter consists of a 2 in (50 mm) grooved pipe
plug tted with a 1/4 in (8 mm) male quick-connect tting. Pipe
plug attaches to the Mv Series discharge valve using the 2 in (50
mm) grooved coupling shipped with the cylinder assembly as part of
the anti-safety recoil device. e 1/4 in (8 mm) male quick-connect
tting attaches to a 1/4 in (8 mm) female quick-connect tting on
the cylinder ll assembly.e male quick-connect tting contains an
internal check valve that prevents agent from owing through the
tting unless it is connected to the cylinder ll assembly.
3.1.3 Lv Series Fill Adapter
P/N 99513 (See Figure 3.1.3)
e Lv Series ll adapter consists of a 3 in (80 mm) grooved pipe
plug tted with a 1/4 in (8 mm) male quick-connect tting. Pipe
plug attaches to the Lv Series discharge valve using the 3 in (80
mm) grooved coupling shipped with the cylinder assembly as part of
the anti-safety recoil device. e 1/4 in (8 mm) male quick-connect
tting attaches to a 1/4 in (8 mm) female quick-connect tting on
the cylinder ll assembly.e male quick-connect tting contains an
internal check valve that prevents agent from owing through the
tting unless it is connected to the cylinder ll assembly.
BLANK
Figure 3.1.1 Sv Series Fill Adapter
Figure 3.1.2 Mv Series Fill Adapter
Figure 3.1.3 Lv Series Fill Adapter
1/4" (8 mm)
Male Quick-Connect
1/4" (8 mm)
Male Quick-Connect
1/4" (8 mm)
Male Quick-Connect

Page: 10
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 3 Fill Components
3.2 Cylinder Fill Assembly
P/N 99517 (See Figure 3.2)
e cylinder ll assembly is formed from a series of interconnected ttings and valves to serve as a connection
point between the agent ll station and the cylinder assembly.
e manual agent ll valve is a 1/4 in (8 mm)
manually actuated ball valve used to open and
close the cylinder ll assembly, allowing agent
to ow from the ll station into the cylinder
assembly.
e cylinder ll assembly has four connection
points. When connected to the cylinder valve
and ll station as recommended,two connection
pointsare oriented vertically andtwo connection
points are oriented horizontally as depicted in
Figure 3.2. e vertical connection points are
referred to as the gauge connection port and
the nitrogen pressurization port.e horizontal
connection points are referred to as the pump
connection port and cylinder connection port.
3.2.1 Pump Connection Port
e pump connection port is a 1/4 in (8 mm) male quick-connect tting attached directly to the manual
agent ll valve and serves as the connection point for the agent ll station. e male quick-connect tting
of the pump connection port contains an internal check valve that prevents agent from owing through the
tting unless it is connected to the ll station.
3.2.2 Cylinder Connection Port
e cylinder connection port is located opposite of the pump connection port and is a 1/4 in (8 mm) female
quick-connect tting that serves as the connection point for the 1/4 in (8 mm) male quick-connect tting
on the ll adapter (refer to section 3.1). e female quick-connect tting of the cylinder connection port
contains an internal check valve that prevents agent from owing through the tting unless it is connected
to the ll adapter.
3.2.3 Gauge Connection Port
e gauge connection port is a 1/4 in (8 mm) male quick-connect tting that serves as the connection point
for the ll pressure gauge. It is located on the same side of the cylinder ll assembly as the handle for the
manual agent ll valve. When connected to the cylinder valve, the cylinder ll assembly must be oriented
so that the gauge connection port is perpendicular to the ground and pointing upwards. e male quick-
connect tting of the gauge connection port contains an internal check valve that prevents agent from
owing through the tting unless the ll pressure gauge has been installed to it.
1/4" (8 mm)
Male Quick-Connect
Nitrogen Pressurization Port
1/4" (8 mm)
Male Quick-Connect
Pump Connection Port
1/4" (8 mm)
Female Quick-Connect
Cylinder Connection Port
1/4" (8 mm)
Male Quick-Connect
Gauge Connection Port
1/4" (8 mm)
Manually Actuated Ball Valve
Manual Agent Fill Valve
Figure 3.2 Cylinder Fill Assembly

Page: 11
FM-200® FILL MANUAL
Revision B Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 3 Fill Components
3.2.4 Nitrogen Pressurization Port
e nitrogen pressurization port is located opposite of the gauge connection port and is a 1/4 in (8 mm) male
quick-connect tting that serves as the connection point for the nitrogen supply used to superpressurize
the cylinder assembly. When connected to the cylinder valve, the cylinder ll assembly must be oriented
so that the nitrogen pressurization port is perpendicular to the ground and pointing downwards. e male
quick-connect tting of the gauge connection port contains an internal check valve that prevents agent
from owing through the tting unless it is connected to the nitrogen supply.
3.3 Nitrogen Regulator/Hose Assembly
P/N 99516 (See Figure 3.3)
e nitrogen regulator/hose assembly is comprised
of a self-relieving pressure regulator, a safety
relief valve, and two manually actuated ball valves
connected to hose lines ending in female quick-
connect ttings. e regulator-hose assembly serves
as a connection point between the nitrogen supply
and both the nitrogen pressurization port of the
cylinder ll assembly and the inlet port of the valve
closing adapter. e regulator has a CGA tting for
attaching to the nitrogen supply.
3.3.1 Valve Closing Line
e valve closing line refers to the ex hose and manually actuated ball valve in line with the pressure
regulator. e valve closing line ends with a 1/4 in (8 mm) female quick-connect tting that attaches to
the 1/4 in (8 mm) male quick-connect tting located on the inlet of the valve closing adapter (see Section
3.4). It is used to close the cylinder valve by applying pressure to the top of the cylinder valve piston. e
valve closing line quick-connect tting contains an internal check valve that prevents nitrogen from owing
through the tting unless it is connected to the valve closing adapter.
3.3.2 Cylinder Pressurization Line
e cylinder pressurization line refers to the ex hose and manually actuated ball valve branching o from
the valve closing line and is perpendicular to the outlet of the pressure regulator. e cylinder pressurization
line ends with a 1/4 in (8 mm) female quick-connect tting that attaches to the nitrogen pressurization
port of the cylinder ll assembly. It is used to supply the nitrogen required to superpressurize the cylinder
assembly following agent ll. e cylinder pressurization line quick-connect tting contains an internal
check valve that prevents the nitrogen from owing through the tting unless it is connect to the nitrogen
pressurization port.
Valve Closing Line
Cylinder Pressurization Line
1/4" (8 mm)
Female Quick-Connect
1/4" (8 mm)
CGA Fitting
1/4" (8 mm)
Female Quick-Connect
Nitrogen Regulator
850 psi
(58.6 bar)
Relief Valve
Figure 3.3 Nitrogen Regulator/Hose Assembly

Page: 12
FM-200® FILL MANUAL
Revision B
Document # DOC180
Issued: August 16, 2010
Revised: April 2, 2012
Section 3 Fill Components
3.4 Valve Closing Adapter
P/N 17292 (See Figure 3.4)
e valve closing adapter is threaded onto the valve actuation connection of
the cylinder valve and receives pressure from the nitrogen supply at the end of
the lling procedure to close the cylinder valve. A 1/4 inch (8 mm) male quick-
connect tting (P/N 99499) is installed in the 1/4 inch (8 mm) FNPT inlet
port of the valve closing adapter and is utilized to facilitate connection to the
valve closing line of the nitrogen regulator-hose assembly.
3.5 Agent Supply Tank
FM-200® agent is supplied in tanks of 160 lb (73 kg),1200 lb (544 kg), and 34,000 lb (15,422 kg) capacities.
Each supply tank has a valve marked as the vapor ll line and a valve marked as the liquid ll line.e liquid
ll line shall be utilized in lling a cylinder assembly.
3.6 Agent Fill Station
P/N 99502 (See Figure 3.6)
e agent ll station is necessary to pump the liquid agent from the agent supply tank into the empty
cylinder assembly. e station pump requires a dry compressed air supply capable of pressure between 100
and 120 psi (6.89 and 8.27 bar) at a minimum of 13 cubic feet per minute.
e agent ll station has an inlet hose (agent supply tank hose) designed to connect to the agent supply tank
and an outlet hose (cylinder ll hose) designed to connect to the cylinder ll assembly.
1/4" (8 mm)
Male Quick-Connect
Fitting (P/N 99499)
Figure 3.4 Valve Closing Adapter
Figure 3.6 Agent Fill Station
Selector
Control
Knob
Liquid/
Moisture
Indicator Discharge
Pressure
Gauge
Inlet Pressure Gauge
Pump Control
Knob Agent/Nitrogen
Selection Knob
This manual suits for next models
3
Table of contents
Other Janus Safety Equipment manuals
Popular Safety Equipment manuals by other brands

Federal Signal Corporation
Federal Signal Corporation TCLF2 Installation and wiring instructions

SKYLOTEC
SKYLOTEC PEANUT Instructions for use

S&S Northern
S&S Northern Merlin CT500S Installation, operation and maintenance manual

Knightsbridge
Knightsbridge EMLREC Installation & maintenance manual

CLiC-iT
CLiC-iT C-RACK OZON User instruction

ISC
ISC RP815 General Instructions for Use