Janus 3M Novec 1230 User manual

Rell Manual for
3M™ Novec™ 1230 Fire Protection Fluid
Sv Series, Mv Series, Lv Series
Issued May 31, 2011
DOC181 REV E
(June 23, 2020)

BLANK

Page: iii
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Contents
1 GENERAL INFORMATION 1
1.1 Listings and Approvals 1
1.2 Extinguishing Agent 1
1.3 Safety Considerations 1
2 CYLINDER ASSEMBLY 3
2.1 Cylinder 3
2.1.1 Rupture Disc 3
2.1.2 Liquid Level Indicator 3
2.2 Dip Tube (Siphon Tube) 4
2.3 Cylinder Valve 4
2.3.1 Sv Series Valve Features 5
2.3.2 Mv Series Valve Features 6
2.3.3 Lv Series Valve Features 7
3 FILL COMPONENTS 9
3.1 Fill Adapter 9
3.1.1 Sv Series Fill Adapter 9
3.1.2 Mv Series Fill Adapter 9
3.1.3 Lv Series Fill Adapter 9
3.2 Cylinder Fill Assembly 10
3.2.1 Pump Connection Port 10
3.2.2 Cylinder Connection Port 10
3.2.3 Gauge Connection Port 10
3.2.4 Nitrogen Pressurization Port 11
3.3 Nitrogen Regulator/Hose Assembly 11
3.3.1 Valve Closing Line 11
3.3.2 Cylinder Pressurization Line 11
3.4 Valve Closing Adapter 12
3.5 Agent Supply Tank 12
3.5.1 IBC Container 12
3.5.1.1 IBC Coupler Kit 12
3.5.1.2 Low Pressure Nitrogen Regulator 12
3.5.2 Supply Drum 13
3.6 Agent Fill Station 13
3.6.1 Fill Station Displays 14
3.6.2 Selector Control Knob 14
3.6.3 Pump Control Knob 14
3.6.4 Agent/Nitrogen Selection Knob 14
4 FILL PROCEDURE 15
4.1 Log and Weigh Empty Cylinder 15
4.2 Agent Fill Procedure 15
4.2.1 Seating Cylinder Valve 17
4.2.2 Cylinder Weighing 17
4.2.3 Overll Retrieval Procedure 18
4.3 Pressurization Procedure 19
4.3.1 Finalization Procedure 22
4.3.2 Leak Checking 22

Page: iv
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
5 SYSTEM RECHARGE AND RESET 25
5.1 Piping and Nozzles 25
5.2 Recharging 25
5.2.1 Removing The Cylinder 25
5.2.2 Cleaning and Servicing The Valve Assembly 26
5.2.3 Recharge Procedure 27
APPENDIX A - MATERIAL SAFETY DATASHEET 29
APPENDIX B - ASSORTED CHARTS 37
APPENDIX C - LIQUID LEVEL INDICATOR REPLACEMENT 51

Page: v
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Diagram Index
Figure 2.3.1 Sv Cylinder Valve Assembly 5
Figure 2.3.2 Mv Cylinder Valve Assembly 6
Figure 2.3.3 Lv Cylinder Valve Assembly 7
Figure 3.1.1 Sv Series Fill Adapter 9
Figure 3.1.2 Mv Series Fill Adapter 9
Figure 3.1.3 Lv Series Fill Adapter 9
Figure 3.2 Cylinder Fill Assembly 10
Figure 3.3 Nitrogen Regulator/Hose Assembly 11
Figure 3.4 Valve Closing Adapter 12
Figure 3.5.1.1 IBC Coupler Kit 12
Figure 3.6 Agent Fill Station 13
Figure 4 Cylinder Fill P&ID Diagram (IBC) 15
Figure 4.3.2 Connection Points to Check for Leaks 24
Figure C.1 LLI Exterior 52
Figure C.2 LLI Interior 52
Figure C.3 Ball Float 53
Table Index
Table 2.1 Cylinder Capacities 3
Table 5.2.2 Clean Agent Valve Replacement Components 27
Table B.1 - Approximate Container Pressure vs. Temperature 38
Table B.2a U.S. Standard to Metric Conversion Factors (Approximate) 39
Table B.2b Metric to U.S. Standard Conversion Factors (Approximate) 39
Table B.3a Liquid Level Chart – 250 lb Cylinder (U.S. Standard) 40
Table B.3b Liquid Level Chart – 250 lb Cylinder (Metric) 41
Table B.4a Liquid Level Chart – 420 lb Cylinder (U.S. Standard) 42
Table B.4b Liquid Level Chart – 420 lb Cylinder (Metric) 43
Table B.5a Liquid Level Chart – 600 lb Cylinder (U.S. Standard) 44
Table B.5b Liquid Level Chart – 600 lb Cylinder (Metric) 45
Table B.6a Liquid Level Chart – 900 lb Cylinder (U.S. Standard) 46
Table B.6b Liquid Level Chart – 900 lb Cylinder (Metric) 47
Table B.7a Liquid Level Chart – 1000 lb Cylinder (U.S. Standard) 48
Table B.7b Liquid Level Chart – 1000 lb Cylinder (Metric) 49

Page: vi
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Revision Description of Change Date
--- Initial Printing 31-May-2011
A All references to "Dow Corning No. 4" replaced with "Molykote 55 by Dow Corning
(P/N 19056)".
02-Mar-2012
B Appendix C added. 02-Apr-2012
C Figure 3.6 revised. 31-May-2013
D Section 4.3.2 added. Sentence beginning "For a ll station to be UL Listed," and
Table 1.1 added to Section 1.1. Note added to Section 1.2. Sentence beginning "An
accurate thermometer" added to Note in Section 4.2. Phrase "400 psig" in Section
4.2.1 changed to "100 psig". Note and Warning added to Section 4.3.1. MSDS in
Appendix A updated to latest revision.
25-Nov-2013
E All applicable references to 'll' changed to 'rell' for clarity. Sentence beginning
"For a ll station to be UL Listed," and Table 1.1 removed from Section 1.1. Sec-
tion 4.3.2 rewritten. Figure 4.3.2 added. Section 5 rewritten.
23-Jun-2020
Revision History

Page: vii
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Preface
This manual is intended for use with the Janus Fire Systems® Sv Series, Mv Series, and Lv Series Clean Agent
Engineered Fire Extinguishing Systems utilizing 3M™ Novec™ 1230 Fire Protection Fluid. Those responsible for
the agent ll or agent rell of these systems should read this entire manual.
All design, implementation, and maintenance of the Janus Fire Systems® Engineered Fire Extinguishing Systems
must be performed in compliance with the National Fire Protection Association (NFPA) 2001 - Standard on Clean
Agent Fire Extinguishing Systems, NFPA 70 - The National Electrical Code, NFPA 72 - The National Fire Alarm
Code, and the guidelines outlined in this manual.
All system designs are preformed in conjunction with the Janus Design Suite® hydraulic ow calculation software
and in compliance with the Janus Design Suite® Flow Calculation Software Manual For Use with 3M™ Novec™
1230 Fire Protection Fluid, DOC173.
Janus Fire Systems® reserves the right to revise and improve its products as it deems necessary without prior
notication. This manual describes the state of Janus Fire Systems® products at the time of its publication and may
not reect those products at all times in the future.
All references to Codes or Standards in this manual refer to the latest edition of that Code or Standard unless
otherwise indicated.
Compressed gases shall be handled and used only by persons properly trained in accordance with Compressed
Gas Association, Inc. (CGA) pamphlets C-1, C-6, and P-1.
CGA pamphlets are published by the Compressed Gas Association Inc. (www.cganet.com).
The contents of this manual may not be reproduced in any form without the express written consent of Janus Fire
Systems.
Copyright © 2011 Janus Fire Systems. All Rights Reserved. Janus Fire Systems® and Janus Design Suite® are registered trademarks of
Janus Fire Systems.
3M™ and Novec™ are trademarks of 3M Company.
Janus Fire Systems
1102 Rupcich Drive
Millennium Park
Crown Point, IN 46307
TEL: (219) 663-1600 FAX: (219) 663-4562
e-mail: info@janusresystems.com · www.janusresystems.com

Page: viii
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
BLANK

Page: 1
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 1 General Information
1 GENERAL INFORMATION
is manual describes the procedure for recharging/refilling Janus Fire Systems® Sv Series, Mv Series, and
Lv Series cylinder assemblies with Novec 1230 Fire Protection Fluid.
1.1 Listings and Approvals
To maintain FM Approval for Janus Fire Systems® Fire Suppression Systems, cylinder recharge must be
performed at a Janus Fire Systems® recognized facility.
1.2 Extinguishing Agent
Novec 1230 fluid (FK-5-1-12) is formed from the elements carbon, fluorine and oxygen (CF3CF2C(O)
CF(CF3)2 - dodecafluoro-2-methylpentan-3-one). e primary extinguishing mechanism of Novec 1230
fluid is heat absorption, with a secondary chemical contribution from the thermal decomposition of Novec
1230 fluid in the flame. Novec 1230 fluid leaves no residue and is safe for use in occupied spaces.
Novec 1230 fluid is a highly fluorinated ketone containing no chlorine or bromine. As a result, the Ozone
Depletion Potential (ODP) for Novec 1230 fluid is zero, meaning it has no effect on stratospheric ozone.
Novec 1230 fluid has an atmospheric lifetime of 0.014 years. It has a Global Warning Potential of 1.
Janus Fire Systems® Engineered Fire Suppression Systems store Novec 1230 fluid as a liquid in steel
cylinders. e liquid Novec 1230 fluid is superpressurized with nitrogen to 360 psig (24.8 bar) at 70°F
(21.1°C). When discharged, Novec 1230 fluid is atomized at the discharge nozzles and becomes thoroughly
mixed with the air throughout the protected area reaching a predetermined design concentration.
NOTE: Bulk Novec 1230 fluid must be purchased from Janus Fire Systems and must bear the UL and FM
marks on the container.
1.3 Safety Considerations
All safety guidelines contained in this manual must be read and understood before filling any Janus Fire
Systems® cylinder. All applicable guidelines shall be followed before, during, and after the fill procedure
including any additional local standards or regulations determined by the authority having jurisdiction
(AHJ). Where the guidelines in this manual and local guidelines or regulations conflict, the most stringent
requirement should be followed.
ose individuals responsible for the filling of a Janus Fire Systems® cylinder assembly with Novec 1230
Fire Protection Fluid must be trained.

Page: 2
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 1 General Information
At a minimum, Janus Fire Systems recommends the following safety equipment be worn at all times during
the fill procedure:
• Work boots with protective toe guards
• Safety glasses or goggles
• Gloves to prevent injury of the hands or fingers.
• Properly fitting clothing.
• Properly fitting ear plugs or other hearing protection.
Cylinder filling must be performed in a well ventilated area.
When Novec 1230 uid is exposed to temperatures greater than 1300°F (700°C), the potentially hazardous
byproduct hydrogen uoride (HF) will be formed during agent decomposition. Heat sources such as space
heaters, torches, welding equipment, or lit cigarettes are capable of reaching temperatures that initiate agent
decomposition. All such potential heat sources must be cleared from the work area before beginning ll process.
Smoking in the vicinity of the lling equipment or agent storage containers shall be prohibited.
e Material Safety Data Sheet (MSDS) on Novec 1230 Fire Protection Fluid can be found in Appendix
A of this manual and shall be read and understood before working with the agent.
Accidental discharge of an unsecured cylinder may result in property damage, injury, or death from
violent cylinder movement. Cylinder assemblies must be restrained at all times during the ll procedure. Anti-
recoil safety plugs and devices must be in place at all times the cylinder assembly is not connected to agent ll
lines or discharge piping. Do not transport the cylinder unless the anti-recoil safety device is in place. Handle the
cylinder assembly with care even when the safety device in is place.
e technical manual supplied with the fill station or pump must be read and understood prior to filling
cylinder assemblies. All procedures contained in the aforementioned manual must be followed and all
warnings or safety guidelines noted. Refer also to 3M™ Novec™ 1230 Fire Protection Fluid Storage and
Handling document 60-5002-0131-8.
The lling station or pump designated for use with Novec 1230 uid shall not be used with any other agents. Each
agent stored at a ll facility must have its own separate lling station or pump. Use of multiple agents with a single
lling station may result in contamination of agent and dilute its eectiveness as a means of suppression.

Page: 3
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 2 Cylinder Assembly
2 CYLINDER ASSEMBLY
e cylinder assembly consists of the cylinder, dip tube, and cylinder valve.
2.1 Cylinder
e Novec 1230 fluid is stored as a liquid inside a welded steel cylinder. e cylinders are superpressurized
with dry nitrogen to a pressure of 360 psig (24.8 bar) at 70°F (21°C). Every cylinder has a minimum fill
density of 35 lb/ft3(561 kg/m3) and a maximum fill density of 70 lb/ft3(1121 kg/m3). e capacity of a
cylinder varies according to the design requirements and the Series designation (See Table 2.1.1 for a list of
available capacities).
Standard domestic cylinders
are manufactured according
to the requirements of
the U.S. Department of
Transportation (USDOT)
andTransport Canada1(TC)
for compressed gas and are
fitted with an identification
label indicating the fill
quantity of Novec 1230
fluid. Each cylinder has
internal neck threads to
allow for connection to the
cylinder valve.
2.1.1 Rupture Disc
A frangible rupture disc is fitted to the Lv Series cylinder body. It functions as an emergency relief device in
the event of excessive internal pressure within the cylinder. Its rupture point is between 850 psi (58.6 bar)
and 1000 psi (68.9 bar).
is feature is not found on the Sv Series or Mv Series cylinder. Instead, a rupture disc is located on the side
of Sv Series and Mv Series cylinder valve as detailed in sections 2.3.1 and 2.3.2.
2.1.2 Liquid Level Indicator
e liquid level indicator consists of a sealed non-magnetic tube containing an external measurement tape
fitted with a magnet. A second magnet with an opposing polarity is installed on the outside of the tube
and is exposed to the liquid Novec 1230 fluid. As the tape is extracted from the tube, it will engage with
the second magnet creating a noticeable change in tension. e measure on the tape when this change in
tension occurs indicates the current liquid level inside the cylinder and can then be compared to a chart
located in Appendix B of this manual to determine the current fill weight of the cylinder.
e liquid level indicator assembly is threaded into an outlet on the head (top) of the Mv Series and Lv
Series cylinders.
is feature is not found on the Sv Series cylinder.
Table 2.1 Cylinder Capacities
Valve
Series
Nominal
Cylinder
Size P/N Fill Capacity Empty
Weight
Minimum Maximum
lb kg lb kg lb kg
Sv 40 lb 20503 22 10.0 49 19.5 36 16.3
Sv 80 lb 20504 41 18.6 81 36.7 65 29.5
Sv 130 lb 20505 66 29.9 131 59.4 77 35.0
Mv 250 lb 20506 126 57.2 252 114.3 213 96.6
Mv 420 lb 20507 211 95.7 422 191.4 279 126.6
Lv 600 lb 20508 304 137.9 609 275.3 346 157.0
Lv 900 lb 20509 455 206.4 910 412.7 471 213.6
Lv 1000 lb 20510 561 254.5 1000 453.6 766 346.5
Ordering Instructions: Specify the Cylinder Assembly P/N followed by a dash
and the ll weight in pounds expressed in three digits.
1 1000 lb Cylinders are not Transport Canada approved.

Page: 4
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
2.2 Dip Tube (Siphon Tube)
A rigid dip tube is threaded into the cylinder valve and extends down the entire length of the cylinder.
2.3 Cylinder Valve
A differential pressure operated cylinder valve controls the release of Novec 1230 fluid from the cylinder. It
is made of forged brass and is threaded onto the cylinder neck. e features and design of each valve vary
according to the Series designation.
Section 2 Cylinder Assembly

Page: 5
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 2 Cylinder Assembly
2.3.1 Sv Series Valve Features
(See Figure 2.3.1)
e Sv Series valve has six key features:
1. Valve Actuation Connection: A threaded connection located on top of the cylinder valve serves as the
attachment point for the electric (primary) or pneumatic (slave) valve actuator.
2. Pressure Gauge: A pressure gauge is mounted to the cylinder valve exterior to provide a visual measure
of the cylinder’s internal pressure. e gauge shall not be removed while the cylinder is under pressure.
3. Rupture Disc: A frangible rupture disc is fitted to the valve body opposite the pressure gauge. It
functions as an emergency relief device in the event of excessive internal pressure within the cylinder.
Its rupture point is between 850 psi (58.6 bar) and 1000 psi (68.9 bar). e rupture disc shall not be
removed while the cylinder is under pressure.
4. Low-Pressure Supervisory Switch: A low-pressure supervisory switch is mounted to the cylinder valve
and continuously monitors the internal pressure of the cylinder. It shall not be removed while the
cylinder is under pressure.
5. Discharge Outlet: A 1 1/4 in (32 mm) FNPT connection serves as the attachment point for the
discharge piping.
6. Pilot Actuation Port: A 3/8 in (10 mm) FNPT connection (shipped with a pipe plug) serves as the
attachment point for the pilot actuation piping in multiple cylinder systems, providing the actuation
pressure used to open the slave cylinder valve(s). is can also be used for attachment of the discharge
pressure switch in single cylinder arrangements. e pipe plug shall remain in place at all times when
the port is not connected to pilot actuation piping or a discharge pressure switch.
Figure 2.3.1 Sv Cylinder Valve Assembly
Pilot Actuation
Port
Pipe Plug
Rupture Disc (3)
Pressure Gauge (2)
Low-Pressure
Supervisory Switch (4)
Discharge Outlet
Anti-Recoil
Safety Plug
Safety Cap
Discharge
Outlet (5)
Pilot
Actuation
Port (6)
Low-Pressure
Supervisory Switch (4)
Valve Actuation
Connection (1)
Ensure that the pilot actuation port pipe plug is in place before attempting to ll the cylinder assembly. Failure to
do so may result in agent leaking out of the pilot actuation port during the ll procedure.

Page: 6
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 2 Cylinder Assembly
2.3.2 Mv Series Valve Features
(See Figure 2.3.2)
e Mv Series cylinder valve has six key features:
1. Valve Actuation Connection: A threaded connection located on top of the cylinder valve serves as the
attachment point for the electric (primary) or pneumatic (slave) valve actuator.
2. Pressure Gauge Connection: A female connection serves as the attachment point for the pressure
gauge. It is fitted with a Schrader valve to allow the removal of the gauge while the cylinder is
pressurized.
3. Low-Pressure Supervisory Switch Connection: A female connection serves as the attachment point
for the low-pressure supervisory switch. A Schrader valve allows for the removal of the pressure switch
while the cylinder is pressurized.
4. Rupture Disc: A frangible rupture disc is fitted to the valve body opposite the discharge outlet. It
functions as an emergency relief device in the event of excessive internal pressure within the cylinder.
Its rupture point is between 850 psi (58.6 bar) and 1000 psi (68.9 bar). e rupture disc shall not be
removed while the cylinder is under pressure.
5. Discharge Outlet: A 2 in (50 mm) grooved connection serves as the attachment point for discharge
piping.
6. Pilot Actuation Port: A 1/4 in (8 mm) NPT connection (shipped with a pipe plug) serves as the
attachment point for the pilot actuation piping in multiple cylinder systems, providing the actuation
pressure used to open the slave cylinder valve(s). is can also be used for attachment of the discharge
pressure switch in single cylinder arrangements. e pipe plug shall remain in place at all times when
the port is not connected to pilot actuation piping or a discharge pressure switch.
Figure 2.3.2 Mv Cylinder Valve Assembly
Pressure Gauge
Connection (2)
Grooved
Coupling (Part
of Anti-Recoil
Safety Device)
Low-Pressure
Supervisory Switch
Connection (3)
Pilot Actuation
Port (6)
Safety
Cap
Rupture
Disc (4)
Valve Actuation
Connection (1)
Discharge
Outlet (5)
Pressure Gauge
Connection (2)
Ensure that the pilot actuation port pipe plug is in place before attempting to ll the cylinder assembly. Failure to
do so may result in agent leaking out of the pilot actuation port during the ll procedure.

Page: 7
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 2 Cylinder Assembly
2.3.3 Lv Series Valve Features
(See Figure 2.3.3)
e Lv Series cylinder valve has five key features:
1. Valve Actuation Connection: A threaded connection located on top of the cylinder valve serves as the
attachment point for the electric (primary) or pneumatic (slave) valve actuator.
2. Pressure Gauge Connection: A female connection serves as the attachment point for the pressure
gauge. It is fitted with a Schrader valve to allow the removal of the gauge while the cylinder is pressurized.
3. Low-Pressure Supervisory Switch Connection: A female connection serves as the attachment point
for the low-pressure supervisory switch. A Schrader valve allows for the removal of the pressure switch
while the cylinder is pressurized.
4. Discharge Outlet: A 3 in (80 mm) grooved connection serves as the attachment point for discharge
piping.
5. Pilot Actuation Port: A 1/4 in (8 mm) NPT connection (shipped with a pipe plug) serves as the
attachment point for the pilot actuation piping in multiple cylinder systems, providing the actuation
pressure used to open the slave cylinder valve(s). is can also be used for attachment of the discharge
pressure switch in single cylinder arrangements. e pipe plug shall remain in place at all times when
the port is not connected to pilot actuation piping or a discharge pressure switch.
Figure 2.3.3 Lv Cylinder Valve Assembly
Pressure Gauge
Connection (2)
Low-Pressure
Supervisory Switch
Connection (3)
Pilot Actuation
Port (5)
Safety
Cap
Valve Actuation
Connection (1)
Discharge
Outlet (4)
Pressure Gauge
Connection (2)
Grooved
Coupling (Part
of Anti-Recoil
Safety Device)
Ensure that the pilot actuation port pipe plug is in place before attempting to ll the cylinder assembly. Failure to
do so may result in agent leaking out of the pilot actuation port during the ll procedure.

Page: 8
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 2 Cylinder Assembly
BLANK

Page: 9
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 3 Fill Components
3 FILL COMPONENTS
e following components are necessary to fill a Janus Fire Systems® cylinder assembly with Novec 1230
fluid.
3.1 Fill Adapter
A fill adapter is installed into the discharge outlet of the cylinder valve during the fill procedure to
accommodate the attachment of the cylinder fill assembly. Each Series valve requires a different type of fill
adapter.
3.1.1 Sv Series Fill Adapter
P/N 99515 (See Figure 3.1.1)
e Sv Series fill adapter consists of a 1-1/4 in (32 mm) MNPT
pipe plug fitted with a 1/4 in (8 mm) male quick-connect fitting.
e 1-1/4 in (32 mm) MNPT connection attaches to the Sv Series
discharge valve in place of the anti-safety recoil device. e 1/4 in (8
mm) male quick-connect fitting attaches to a 1/4 in (8 mm) female
quick-connect fitting on the cylinder fill assembly. e male quick-
connect fitting contains an internal check valve that prevents agent
from flowing through the fitting unless it is connected to the cylinder
fill assembly.
3.1.2 Mv Series Fill Adapter
P/N 99514 (See Figure 3.1.2)
e Mv Series fill adapter consists of a 2 in (50 mm) grooved pipe
plug fitted with a 1/4 in (8 mm) male quick-connect fitting. Pipe
plug attaches to the Mv Series discharge valve using the 2 in (50
mm) grooved coupling shipped with the cylinder assembly as part of
the anti-safety recoil device. e 1/4 in (8 mm) male quick-connect
fitting attaches to a 1/4 in (8 mm) female quick-connect fitting on
the cylinder fill assembly.e male quick-connect fitting contains an
internal check valve that prevents agent from flowing through the
fitting unless it is connected to the cylinder fill assembly.
3.1.3 Lv Series Fill Adapter
P/N 99513 (See Figure 3.1.3)
e Lv Series fill adapter consists of a 3 in (80 mm) grooved pipe
plug fitted with a 1/4 in (8 mm) male quick-connect fitting. Pipe
plug attaches to the Lv Series discharge valve using the 3 in (80
mm) grooved coupling shipped with the cylinder assembly as part of
the anti-safety recoil device. e 1/4 in (8 mm) male quick-connect
fitting attaches to a 1/4 in (8 mm) female quick-connect fitting on
the cylinder fill assembly.e male quick-connect fitting contains an
internal check valve that prevents agent from flowing through the
fitting unless it is connected to the cylinder fill assembly.
Figure 3.1.1 Sv Series Fill Adapter
Figure 3.1.2 Mv Series Fill Adapter
Figure 3.1.3 Lv Series Fill Adapter
1/4" (8 mm)
Male Quick-Connect
1/4" (8 mm)
Male Quick-Connect
1/4" (8 mm)
Male Quick-Connect

Page: 10
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 3 Fill Components
3.2 Cylinder Fill Assembly
P/N 99517 (See Figure 3.2)
e cylinder fill assembly is formed from a series of interconnected fittings and valves to serve as a connection
point between the agent fill station and the cylinder assembly.
e manual agent fill valve is a 1/4 in (8 mm)
manually actuated ball valve used to open and
close the cylinder fill assembly, allowing agent
to flow from the fill station into the cylinder
assembly.
e cylinder fill assembly has four connection
points. When connected to the cylinder valve
and fill station as recommended,two connection
pointsareoriented verticallyand two connection
points are oriented horizontally as depicted in
Figure 3.2. e vertical connection points are
referred to as the gauge connection port and
the nitrogen pressurization port.e horizontal
connection points are referred to as the pump
connection port and cylinder connection port.
3.2.1 Pump Connection Port
e pump connection port is a 1/4 in (8 mm) male quick-connect fitting attached directly to the manual
agent fill valve and serves as the connection point for the agent fill station. e male quick-connect fitting
of the pump connection port contains an internal check valve that prevents agent from flowing through the
fitting unless it is connected to the fill station.
3.2.2 Cylinder Connection Port
e cylinder connection port is located opposite of the pump connection port and is a 1/4 in (8 mm) female
quick-connect fitting that serves as the connection point for the 1/4 in (8 mm) male quick-connect fitting
on the fill adapter (refer to section 3.1). e female quick-connect fitting of the cylinder connection port
contains an internal check valve that prevents agent from flowing through the fitting unless it is connected
to the fill adapter.
3.2.3 Gauge Connection Port
e gauge connection port is a 1/4 in (8 mm) male quick-connect fitting that serves as the connection point
for the fill pressure gauge. It is located on the same side of the cylinder fill assembly as the handle for the
manual agent fill valve. When connected to the cylinder valve, the cylinder fill assembly must be oriented
so that the gauge connection port is perpendicular to the ground and pointing upwards. e male quick-
connect fitting of the gauge connection port contains an internal check valve that prevents agent from
flowing through the fitting unless the fill pressure gauge has been installed to it.
1/4" (8 mm)
Male Quick-Connect
Nitrogen Pressurization Port
1/4" (8 mm)
Male Quick-Connect
Pump Connection Port
1/4" (8 mm)
Female Quick-Connect
Cylinder Connection Port
1/4" (8 mm)
Male Quick-Connect
Gauge Connection Port
1/4" (8 mm)
Manually Actuated Ball Valve
Manual Agent Fill Valve
Figure 3.2 Cylinder Fill Assembly

Page: 11
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 3 Fill Components
3.2.4 Nitrogen Pressurization Port
e nitrogen pressurization port is located opposite of the gauge connection port and is a 1/4 in (8 mm) male
quick-connect fitting that serves as the connection point for the nitrogen supply used to superpressurize
the cylinder assembly. When connected to the cylinder valve, the cylinder fill assembly must be oriented
so that the nitrogen pressurization port is perpendicular to the ground and pointing downwards. e male
quick-connect fitting of the gauge connection port contains an internal check valve that prevents agent
from flowing through the fitting unless it is connected to the nitrogen supply.
3.3 Nitrogen Regulator/Hose Assembly
P/N 99516 (See Figure 3.3)
e nitrogen regulator/hose assembly is comprised
of a self-relieving pressure regulator, a safety
relief valve, and two manually actuated ball valves
connected to hose lines ending in female quick-
connect fittings. e regulator-hose assembly serves
as a connection point between the nitrogen supply
and both the nitrogen pressurization port of the
cylinder fill assembly and the inlet port of the valve
closing adapter. e regulator has a CGA fitting for
attaching to the nitrogen supply.
3.3.1 Valve Closing Line
e valve closing line refers to the flex hose and manually actuated ball valve in line with the pressure
regulator. e valve closing line ends with a 1/4 in (8 mm) female quick-connect fitting that attaches to
the 1/4 in (8 mm) male quick-connect fitting located on the inlet of the valve closing adapter (see Section
3.4). It is used to close the cylinder valve by applying pressure to the top of the cylinder valve piston. e
valve closing line quick-connect fitting contains an internal check valve that prevents nitrogen from flowing
through the fitting unless it is connected to the valve closing adapter.
3.3.2 Cylinder Pressurization Line
e cylinder pressurization line refers to the flex hose and manually actuated ball valve branching off from
the valve closing line and is perpendicular to the outlet of the pressure regulator. e cylinder pressurization
line ends with a 1/4 in (8 mm) female quick-connect fitting that attaches to the nitrogen pressurization
port of the cylinder fill assembly. It is used to supply the nitrogen required to superpressurize the cylinder
assembly following agent fill. e cylinder pressurization line quick-connect fitting contains an internal
check valve that prevents the nitrogen from flowing through the fitting unless it is connect to the nitrogen
pressurization port.
Valve Closing Line
Cylinder Pressurization Line
1/4" (8 mm)
Female Quick-Connect
1/4" (8 mm)
CGA Fitting
1/4" (8 mm)
Female Quick-Connect
Nitrogen Regulator
850 psi
(58.6 bar)
Relief Valve
Figure 3.3 Nitrogen Regulator/Hose Assembly

Page: 12
REFILL MANUAL FOR 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID
Revision E
Document # DOC181
Issued: May 31, 2011
Revised: June 23, 2020
Section 3 Fill Components
3.4 Valve Closing Adapter
P/N 17292 (See Figure 3.4)
e valve closing adapter is threaded onto the valve actuation connection of
the cylinder valve and receives pressure from the nitrogen supply at the end of
the filling procedure to close the cylinder valve. A 1/4 inch (8 mm) male quick-
connect fitting (P/N 99499) is installed in the 1/4 inch (8 mm) FNPT inlet
port of the valve closing adapter and is utilized to facilitate connection to the
valve closing line of the nitrogen regulator-hose assembly.
3.5 Agent Supply Tank
Novec 1230 fluid is supplied in drums of 661 lb (300 kg) capacity or IBC containers of 2425 lb (1100 kg)
capacity.
3.5.1 IBC Container
Because Novec 1230 fluid is a liquid at typical ambient temperatures and pressure, pumping agent from
an IBC container in a closed system can create a vacuum detrimental to the structural integrity of the
IBC container. To counter this effect, a dry nitrogen supply is regulated into a port at the top of the IBC
container at approximately 5 psig (0.35 bar). Refer to 3M™ Novec™ 1230 Fire Protection Fluid Storage
and Handling document 60-5002-0131-8 for additional information.
3.5.1.1 IBC Coupler Kit
P/N 99501 (See Figure 3.5.1.1)
e IBC coupler kit is utilized to connect a dry nitrogen supply to the
top port of the IBC container during the agent fill procedure. e top
port of IBC container ships fitted with a check valve that upsets when
the coupler kit is installed to it. e coupler fill head is a quick connect
fitting that is attached to the top port valve and turned clockwise 1/4
turn to lock into place. e coupler supply connection is a 1 in (25 mm)
MNPT connection fitted to a nitrogen coupler hose line that attaches to
the outlet of the low pressure nitrogen regulator. e coupler kit controls
the flow of nitrogen into the IBC container through a manually actuated
piston valve. It is fitted with a pressure relief valve set at 10 psi (0.70
bar). Refer to 3M™ Novec™ 1230 Fire Protection Fluid Storage and
Handling document 60-5002-0131-8 for additional information.
3.5.1.2 Low Pressure Nitrogen Regulator
P/N 99951 (See Figure 3.5.1.2)
A low pressure nitrogen regulator is installed in the nitrogen vapor line between the nitrogen supply and
IBC coupler. It regulates the nitrogen pressure entering the IBC container down to approximately 5 psig
(0.35 bar).e inlet port is a CGA 580 fitting. Refer to 3M™ Novec™ 1230 Fire Protection Fluid Storage
and Handling document 60-5002-0131-8 for additional information.
1/4" (8 mm)
Male Quick-Connect
Fitting (P/N 99499)
Figure 3.4 Valve Closing Adapter
Figure 3.5.1.1 IBC Coupler Kit
Table of contents
Other Janus Safety Equipment manuals