manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Johnson & Starley
  6. •
  7. Heater
  8. •
  9. Johnson & Starley ECONOMAIRE 25 User guide

Johnson & Starley ECONOMAIRE 25 User guide

Fig.2
Sealing Panel
1. Thermista-stat
2. Time control
3. Air circulator fan
4. Circuit diagramlabel
5. Gas connection
6. Circulator thermostat
7. FDC &limitswitch
8. Gas cock
9. Ignition burner
10. Main burner assembly
11. Intejan circulator
12. Water return connection
13. Water flow connection
14 Air heater multifuntion control
15. Intejan multifunction control
(ECONOMAIRE25INTEJAN)
16 Flue gas test point
17. LED diagnostics indicator
18. Control module
19. Combustion air fan
20. Filter
21. Flue adapter
7
8
Fig. 1
HeaterwithSealingPanel removed
2
4
5
6
14
13
12
10
11
15
21
20
19
9
17
18
1
3
16
ECONOMAIRE 25/INTEJAN
WARM AIR HEATER
INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS
G.C. Numbers:
Air Heater: 25 42-416-15
Water Circulator: 53-416-32
1. BRIEFDESCRIPTION
1.1 The ECONOMAIRE 25/INTEJAN is a fan assisted downflow ducted warm air heater, which is fan flued and room sealed.
The heater is supplied with digital temperature control (for maximum comfort) and a water circulator is standard on the 25
INTEJAN.However,an INTEJANcirculator(retro-fit) kitisavailable fortheECONOMAIRE 25.
ECONOMAIRE25/INTEJANhasbeentestedandcertifiedbyAdvanticaTechnologiesforusewithNATURALgasG20.
Note: These instructions have been written to service both the ECONOMAIRE 25 and the ECONOMAIRE 25 INTEJAN. If your
heater does not have the intejan circulator fitted, simply ignore the relevant section/s.
Publication No. ZZ 1108/5
February 2008
These instructions are to be left with the User or adjacent to the Gas Meter
128
Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently. If
you have a problem in obtaining a spare part, please contact our Spares Department at the
address below.
JOHNSON & STARLEY LTD.
Telephone: (01604) 762881 Rhosili Road,
Brackmills,
Fax: (01604) 767408 Northampton NN4 7LZ
227
1.2 The air heater output can be adjusted between 5.6kW (20.0MJ/h, 19,000 Btu/h) and 7.3kW (26.4MJ/h, 25,000 Btu/h) “summer
air circulation” of unheated air is available by manual selection (see the user’s instructions). INTEJAN output is 3.5kW
(12.6MJ/h;11,900Btu/h).
Installation shall be in accordance with the current editions of:
Building Standards (Scotland) (Consolidation) Regulations
Building Regulations
Gas Safety (Installation and Use) Regulations (as amended)
BS 7671 Institute of Electrical Engineers (I.E.E.) Wiring Regulations
BS 6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS 5440 Pt. 1 (Flues for GasAppliances)
BS 5440 Pt. 2 (Air Supply for GasAppliances)
BS 5864 Installation of Gas Fired DuctedAir Heaters
British System Design Manual “Gas Fired Warm Air Heating”
Model and Local Authority Bye-laws
BS 5546 Installation of Domestic Hot Water Supplies.
IMPORTANT:ITISASTATUTORYREQUIREMENTTHATALLGASAPPLIANCESAREINSTALLED BYCOMPETENT
PERSONS,(i.e.CORGIREGISTEREDINSTALLERS)INACCORDANCEWITHTHEGASSAFETY(INSTALLATIONANDUSE)
REGULATIONS(CURRENTEDITION).FAILURETOCOMPLYWITHTHESEREGULATIONSMAYLEADTOPROSECUTION.
1.3 TECHNICALDATA
ECONOMAIRE 25 ECONOMAIRE 25 INTEJAN
Weight: 45 Kg 51.5 Kg
Air Heater Water Circulator
Gas G20
Gas Supply Pressure 20mbar
Gas Category I 2H
Countries of Installation GB & IE
Electrical Supply 230 ~ 50Hz fused 5A 165W
Nox Class 1
Max Water Side Operating
pressure (PMS) N/A 1bar
OpenVented System N/A Yes
Sealed System N/A No
AIR HEATER WATER CIRCULATOR
LOW RATE HIGH RATE
KW MJ/h Btu/h KW MJ/h Btu/h KW MJ/h Btu/h
INPUT 7.6 27.1 25,780 9.7 35.1 33,250 4.86 17.5 16,600
OUTPUT 5.6 20.0 19,000 7.3 26.4 25,000 3.5 12.6 11,900
Gas rate cv
1037Btu/ft30.7m3/h (24.9ft3/h) 0.91m3/h (32.1ft3/h) 0.458m3/h (16.2ft3/h)
Burner setting
pressure (hot) 10.0mbar (4.0 in wg) 17.0mbar (6.8 in wg) 15.0mbar (6.0 in wg)
Main Injector Bray Cat 33/700 Amal 187/001/400
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly and that your service engineer completes the
appropriate service interval record below.
SERVICE PROVIDER
Before completing the appropriate service interval record below, please ensure that you have carried out the service
as described in the heater manufacturer’s instructions and in compliance with the Gas Safety Regulations
SERVICE1 Date . . . . . . . . . . . . . . . . . . .
Engineer’sName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Company Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI ID Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE2 Date . . . . . . . . . . . . . . . . . . .
Engineer’sName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Company Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI ID Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE3 Date . . . . . . . . . . . . . . . . . . .
Engineer’sName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Company Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI ID Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE4 Date . . . . . . . . . . . . . . . . . . .
Engineer’sName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Company Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI ID Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE5 Date . . . . . . . . . . . . . . . . . . .
Engineer’sName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Company Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI ID Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE6 Date . . . . . . . . . . . . . . . . . . .
Engineer’sName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Company Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI ID Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE7 Date . . . . . . . . . . . . . . . . . . .
Engineer’sName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Company Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI ID Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE8 Date . . . . . . . . . . . . . . . . . . .
Engineer’sName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Company Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI ID Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE9 Date . . . . . . . . . . . . . . . . . . .
Engineer’sName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Company Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI ID Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE10 Date . . . . . . . . . . . . . . . . . . .
Engineer’sName . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Company Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI ID Serial No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When all of the above services have been completed, please contact your service engineer for an additional
service record sheet.
26
2. HEATERCOMPARTMENTANDCLEARANCES(SEEBS5864)
2.1 IMPORTANT: If the heater is to be fitted to an existing base duct (warm air plenum), always ensure that installation is
carried out such that the rear left hand corner of the heater is aligned with the rear left hand corner of the base duct, so that
any overhang or blanking off will be at the front and/or right hand side. In any event, blanking plates must be mechanically
secured and all joints sealed.
2.2 When the heater is fitted into a compartment, a minimum clearance from the compartment walls of 15mm (1/2 in) at the sides
and rear and 25mm (1 in) at the front must be left. Consideration should also be given to the space required for the removal
and replacement of the filter tray and the entry of the gas, water and electrical supplies. If gas and /or water connections are
made from a side entry, a minimum clearance of 75mm (3 in) is required at that side.
2.3 For service access, a minimum of 450mm (18ins) is required at the front of the heater. Space must also be allowed, in a
compartment installation, to permit the removal of the heater. The clearance between the appliance and the compartment
should be not less than 75mm (3 in). However, if clearances are less than 75mm, the internal surface of the compartment
must be lined with non-combustible material and the compartment must be of a fixed rigid structure.
2.4 In airing cupboard installations, the part used as the air heater compartment must comply with the relevant section of BS
5864 and must be completely separated by either a non-combustible partition or a perforated metal partition with the
perforations not exceeding 13mm (1/2in). The secondary flue must be a tight fit where it passes through the partition and
must be suitably protected (see BS 5440: Part 1).
2.5 In under-stairs installations, the compartment must comply with the relevant section of BS 5864, provided that in addition all
internal surfaces (including the base) are non-combustible or lined with non-combustible material. This requirement is
applicable only to dwellings of more than two storeys.
2.6 Where the air heater is to be installed onto a combustible surface and under-floor ducting used, a suitable base tray (BT32)
MUST be used in order to provide insulation. NB where a base plenum is used no base tray is required!
3. VENTILATION AIR
3.1 When installed in a compartment two permanent ventilation openings into the compartment are required, one at high level
and one at low level, both communicating either directly with outside air or with a ventilated room or space. The minimum
effective areas specified in Table 1 are related to the rated heat input of the air heater and assume that an INTEJAN circulator
is fitted.
4. DUCTSYSTEM
(See British Design Manual - Gas fired Warm Air Heating)
4.1 RETURNAIR
4.1.1 Room-sealed appliances may be installed without return air ducting, provided that the path between the return air
grille and the appliance return air inlet is protected in such a manner that the required air-flow will be maintained at all
times. The return air grille MUST have a free area of not less than 645cm2 (100in2). It is recommended that the return
air duct not be routed directly from the main living area, but from a convenient central area serving the remainder of
the dwelling.
4.1.2 The return air system should be constructed of fire-resistant material. The flue shall not be run through an area
serving as a return air plenum. It is extremely important that the correct size of return air grilles and ducting is used.
For heaters on maximum output the return air duct size should not be less than the equivalent of 200mm x 200mm (8" x
8"). If flexible duct is used the duct diameter should not be less than 300mm (12") dia. The return air grille should
have a free area of not less than 645cm2(100in2).
4.1.3 An adequate and unobstructed return air path is essential from areas not served by a directly ducted return and to
which warm air is delivered.All such rooms should be fitted with relief grilles which have a free area of 0.0088m2/kW
(1in2/250Btu/h) of heat supplied to the room. The only exceptions are kitchens, bathrooms and WCs.
3
Table1:
MinimumEffectiveAreas
Low level grille 131cm
2
(20.5 in
2
)
VENTILATED FROM INSIDE THE
BUILDING Low level grille 131cm
2
(20.5 in
2
)
High level grille 66cm
2
(10.5 in
2
)
VENTILATED FROM OUTSIDE THE
BUILDING High level grille 66cm
2
(10.5 in
2
)
Low
High
WARM AIR HEATER AND CIRCULATOR
COMMISSIONING CHECKLIST
WARM AIR UNIT
BENCHMARK Number
HOTWATERGENERATOR
CONTROLS to comply with the Building Regulations, each section must have a tick on one or other of the boxes
APPLIANCE SERIAL NUMBER: .. .... .... .... .... .... .... .... .... .... .... .... . ... . . ... . .. NOTIFICATION No: ... . ... . .... .... . ... . .... ...
APPLIANCE SERIAL NUMBER: .. .... .... .... .... .... .... .... .... .... .... .... . ... . . ... . .. NOTIFICATION No: ... . ... . .... . ... . .... .... . ..
REQUIREMENT
1. Time & temp control to heating
2. Time & temp control to hot water
3. Heating zone valves
4. Thermostatic Radiator Valves
5. Boiler interlock
MEASURES PROVIDED
Room stat & integral timer
Cylinder stat & Integral timer
Fitted Not Required
Fitted Not Required
Provided Not Required
FOR WARM AIR HEATERS ONLY
Has the system been balanced in accordance with the heater manufacturer’s instructions? YES NO
Was an anemometer used? YES NO
Have balancing dampers been fitted? YES NO
FOR WARM AIR HEATING: MEASURE AND RECORD
Burner operating pressure Mbar
Heat input KW
Temperature differential between return air inlet and nearest outlet oC
FOR HOT WATER GENERATORS: MEASURE AND RECORD
Burner operating pressure Mbar
Heat input KW
Water flow temperature oC
Does the heating & hot water system comply with the appropriate building regulations? YES NO
Has the appliance and associated controls been installed & commissioned in accordance with manufacturer’s instructions? YES NO
Have you demonstrated the operation of the appliance & system controls to the customer? YES NO
Have you left all the manufacturer’s literature with the customer YES NO
Competent person’s signature . .. .. .. .. .. .. . . . .. .. ... .. .. . .. .. . .. .. .. . .. .. Customer’s Signature . .. .. . .. .. . .. .. .. . .. .. . .. .. . .. .. .. . .. .. . .. .
(To confirm demonstration of equipment & receipt of appliance instructions)
COMMISSIONING ENGINEER’S DETAILS
Name .............................................................. . .. .. .. .. .. .. ... . . Commissioning Date .. ... ... ... ... ... ... ... ... ..
Address ........ . . .. . . .. . .. . .. . . .. . .. . .. . . .. . .. . . .. . .. . .. . . .. . .. . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tel No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CORGI REGISTRATION No . . .. .. .. . .. .. .. . .. .. .. . .. .. .. . .. .. .. . .. .. .. . .. .. .. . .. . . . . . . . . CORGI ID SERIAL No . . . . . . . . . . . . . . . . . . . . . . . . . . .
FOR ALL PRODUCTS
Fig. 3
FlueAdaptorandOrifice
Flue
Adaptor
Orifice
Johnson&Starley
Johnson&Starley
14
10
18
30
26
412
13
11
6
3
24
16
7
8
23
32
9
5
47
22
31 19
39
20
25
28
35
50
44 48
42
38
49
40
46
36
41
29
43
45
17
1
21
2
34
15
33
37
Fig. 17
ExplodedDiagram
4.1.4 The return air duct should allow for ease of removal for access to the flue.
4.1.5 All duct work in the room or internal space in which the heater is installed shall be mechanically secured and sealed
with ducting tape.
4.2 WARMDELIVEREDAIR
4.2.1 All duct work, including riser ducts, should be fully insulated with 50mm (2in) fibreglass or similar. If short extended
duct runs are taken below floor level these should be similarly insulated and in addition wrapped with a sound
vapour proof barrier. They must also be protected from crushing.
4.2.2 The duct system should be carefully designed (as given in the guidelines in the British System Design Manual) to
suit the needs of specific heating requirements and building layout. The type of duct system (e.g. radial/extended
plenum/ stepped) should be installed using the least number of fittings to minimise airflow resistance. The base duct,
which equalises the air pressure to supply ducts, must be constructed to support the weight of the heater, which
must be sealed using self-adhesive foam strip, ducting tape or sealing compound. All ducting and blanking plates
must be mechanically secured and sealed.
5. INSTALLATIONREQUIREMENTS
NOTE: THISAPPLIANCEMUSTONLYBEINSTALLEDWITHTHESUPPLIEDACCESSORIESANDTERMINAL.
5.1 FLUES
The ECONOMAIRE 25/INTEJAN can be used with horizontal or vertical flue types C12 and C32. You should also consult (or be
familiarwith)British Standards BS 5440Pt.1 Flues
5.1.1 All joints must be soundly sealed.
5.1.2 Sufficient support brackets must be used in order to support the total weight of the flue system.
5.1.3 The flue must conform with Building Regulations and British Gas Materials and Insallations specification (3rd edition)
regarding clearance and shielding from combustible materials.
5.1.4 The horizontal flue length MUST NOT be less than 300mm plus 90o bend and MUST NOT exceed 12m excluding
terminal.
5.1.5 The total vertical flue length MUST NOT be less than 1m and MUST NOT exceed 12m excluding terminal.
5.1.6 Total length refers to the equivalent worked flue length and therefore includes bends and NOT the distance from the
heater to the flue terminal.
5.1.7 When calculating total flue length, reference MUST be made to the following ‘equivalent lengths’:
A) 90obend = 2m B) 45obend = 1m
5.1.8 The maximum number of 90o bends that can be used is:
A) Horizontal= 2 B) Vertical= 3
5.1.9 If a ‘short flue’ is used, the factory fitted flue orifice MUST be left in place
(seeFig.3).
5.1.10 ‘short flue’ refers to a total flue length not exceeding:
A) Horizontal (plus 90obend) = 0.8m B)Vertical(including terminal)
= 5m
5.1.11 Where the total flue length exceeds these lengths, the flue orifice MUST
be removed.
5.1.11 The heater is supplied with either a horizontal or vertical flue, dependant
upon your specification when ordering. Reference should be made to
Table 2 for extra flue/terminal components.
5.2 HORIZONTALTERMINAL LOCATION:
5.2.1 The terminal must be positioned on the outside of the building and allow
for the free passage of air across it at ALL times.
5.2.2 Avoid positions where the terminal is adjacent to projections, particularly
under a balcony or immediately adjacent to a drain pipe.
5.2.3 The terminal position must ensure that combustion products cannot enter the building in which the heater is installed
(or any adjacent building) through windows, doors or by any others means.
5.2.4 Fig. 4 shows recommended terminal positions
254
Terminal Position MinDistance
A Directly above or below a window or other opening 300mm
B Below gutters, soil pipes or drain pipes 75mm
C Below eaves 200mm
D Below balcony 200mm
E From vertical drain/soil pipes 150mm
F From internal or external corners 300mm
G Above ground or balcony level 300mm
H From a surface facing terminal 600mm
I Fromaterminal facing aterminal 1200mm
J Vertically from a terminal on the same wall 1500mm
K Horizontally from a terminal on the same wall 300mm
Fig.4
Recommended(Horizontal)TerminalPositions
Fig. 5
HorizontalFlueTerminal(ShowingMaximumProtrusion)
Outer Tube Flue Tube
Max.Protrusion (22mm)
24
5.2.5 It is recommended that the flue is fitted so that the outer part is flush with the wall. However, where this is not the
through the wall MUST NOT exceed 22mm (see Fig. 5)
5.2.5 If the heater is to be installed in a timber framed building you MUST consult British Gas publication “Guide for Gas
Installations in Timber Framed Housing DM2” or your local gas region.
5.2.6 Where the lowest part of the flue terminal is located less than 2 metres above the ground, a balcony, or above a flat
roof across which there is access, the terminal MUST be fitted with a Tower Flue Components type K3 guard (or
similar) such that the distance between the guard and the nearest part of the terminal is no less than 50mm.
5.2.7 Reference should be made to Table 2 for required terminal components and guard.
5.2.8 NOTE:TOENSURETHATRAINWATERCANNOTENTERTHEHEATERUNIT,THEFLUEMUSTBE
INSTALLEDWITHASLIGHTFALLAWAYFROMTHEHEATER.
5
LIST OF SPARES (see Fig. 17)
ECONOMAIRE 25 and ECONOMAIRE 25 INTEJAN
Item G.C. No Part No Description Qty
1 E69625 1000-0521020 Wiring harness 1
2 E80119 1000-0521860 Wiring harness (air heater) 1
3 232862 N250-0350005 Heat exchanger 1
4 E80123 1000-0521820 FDC &limit switch 1
5 E79272 T193-0145000 Filter assembly 1
6 E80138 N250-0702000 Burner & control assembly 1
E84175 N250-0751000 Complete burner arm assembly
7 398388 BOS02060 Main burner injector (Bray 33/700) 1
8 E80139 1000-0708550 Ignition burner assembly 1
9 E69631 1000-0520860 Air pressure switch 1
10 E69632 1000-0520830 Clock mechanism 1
11 E80183 1000-0704820 Ignition burner feed pipe 1
12 E80141 1000-0708510 Electric flame control device (Honeywell) 1
13 387819 BOS02394 Igniter lead 1
14 E80143 1000-0708520 Multifunction control 1
E84219 400-0016-7-32 ‘O’ rings for above 2
15 245514 1000-0515620 Thermista-stat 1
16 E80184 N250-0504005 Combustion air fan (SIFAN) 1
17 E80185 N250-0500000 Complete electrical panel 1
18 E80146 1000-0520850 Control module 1
19 245509 1000-0513820 Fuse T3.15A (anti surge) 1
20 245542 1000-0515970 Capacitor15mf 1
21 E80186 N250-0167000 Cabinet door assembly 1
22 232878 BOS02064SP Air circulation fan 1
23 245183 1000-0703150 Ignition burner injector 1
24 E69653 1000-1507310 Gasket 1
25 E69709 1000-0000390 Air Pressure Tube 2
26 E80151 1000-2501050 Grommet 1
27 ITEMNOTSHOWN
28 E69656 1000-0505540 Electronics box(cleanflow) 1
29 793896 AO237X0309 Cleanflow filtermedium (pad) 2
30 E80153 1000-0708480 Gas feed pipe 1
31 E80154 1000-0708430 Gas feed pipe 1
32 Viewportwindow(NOTAVAILABLEASASPARE) 2
33 E69648 1000-0520880 Reset panel (daughter board) 1
WaterCirculator:
34 244-876 SOO284 Main body assembly (inc baffle & spring clip) 1
35 E80155 1000-0521870 Wiring harness 1
36 E69670 1000-0520920 Overheat cut-off switch 1
37 244-876 N250-0700000 Complete burner arm assembly 1
38 E80143 1000-0708520 Multifunction control 1
E84219 400-0016-7-32 ‘O’ Rings for above 2
39 384615 BOS00562 Burnerarm 1
40 244880 BOS02397/1 Ignition burner 1
41 398003 1000-0702040 Thermostat 1
42 E80158 1000-0702090 Maininjector(Amal187/001/400) 1
43 392935 1000-0701260 Ignition burner injector 1
44 E80159 1000-0708470 Igniter lead 1
45 E80161 1000-0708450 Main burner gas feed pipe 1
46 230328 1000-2500075 Phial retaining plug 1
47 E80141 1000-0708510 Electronic flame control device (Honeywell) 1
48 E80163 1000-0708460 Ignition burner feed pipe 1
49 E80164 1000-0708440 Gas feed pipe 1
50 E80151 1000-2501050 Grommet 1
Terminal Position MinDistance
A Directly below a window or other opening 300mm
B Above roof level (to base of terminal) 300mm
C From adjacent wall to flue 300mm
D From internal corner to flue 400mm
E Fromfacing terminal 1200mm
F Between terminals 300mm
G Below eaves or balcony 200mm(BUT NOT
RECOMMENDED)
Fig. 6
Recommended(Vertical)TerminalPositions
SIDE VIEW
BASE VIEW
FRONT VIEW
TOP VIEW
995
345
335
303
300
45
206
80
254
376
440
828
915
1
0
7
5
294
230 26
253
25
403
220
80
140
553 NOM
6
0
1
7
4
0
5
8
0
KNOCKOUTS FOR
WATER CONNECTION
(BOTH SIDES)
KNOCKOUTS FOR
WATER
CONNECTION
(BOTH SIDES)
KNOCKOUTS
FOR GAS
CONNECTION
Fig. 16
Economaire25-PrincipalDimensions
623
5.3 VERTICALTERMINALLOCATION:
5.3.1 The ECONOMAIRE 25/INTEJAN is designed to be used with a vertical flue where
the installation of a horizontal flue is either not possible or not desired.
5.3.2 Installation of a vertical flue can be achieved on either a flat or pitched
roof with a pitch angle of between 25oand 50o.
5.3.3 The terminal MUST be positioned on the outside of the
building and allow for the free passage of air accross it at
ALLtimes.
5.3.4 Avoid positions where the terminal is adjacent to
projections; particularly under a balcony.
5.3.5 The terminal position must ensure that
combustion products cannot enter the
building in which the heater is installed (or
any adjacent building) through windows,
doors or by any other means.
5.3.6 Fig. 6 shows recommended terminal
positions.
5.3.7 Reference should be made to Table 2
for the required terminal components.
PART No CONTENTS COLOUR
1000-0014840 1 X 90° Standard Flue Elbow White
1000-0014850 1 X 45° Flue Elbows White
1000-0014870 1 X 500mm Extension White
1000-0014860 1 X 1000mm Extension White
1000-0014880 1 X Vertical Terminal and 1 X Support Bracket Anthracite
1000-0014980 1 X Vertical Terminal and 1X Support Bracket Terracotta
1000-0014890 1 X Lead Pitched Roof Flashing and 1X Collar Anthracite
1000-0014990 1 X Lead Pitched Roof Flashing and 1X Collar Terracotta
1000-0014900 1 X Aluminium Flat Roof Flashing Aluminium
1000-0014910 1 X Horizontal Wall Terminal White
1000-0014920 2 X Wall Plates (for above) N/A
1000-0014930 1 X Horizontal Wall Terminal and 2 X Wall Plates N/A
1000-0014940 1 X Condensation Drain White
1000-0014950 1 X Syphon Kit (for above) N/A
1000-0014960 1 X Condensation Drain and 1 X Syphon Kit N/A
1000-0014970 1 X Wall Bracket (100mm dia) N/A
1000-0015430 1 X Terminal Guard N/A
Table 2.
FlueandTerminal Components
1
2
3
4
5
6
7
8
9
1
0
L
N
L
N
A
/
H
C
O
M
W
/
H
T
h
e
r
m
i
s
t
a
-
s
t
a
t
Thermista-stat
(Supplied)
Polarity
not
important
E
x
t
e
r
n
a
l
P
r
o
g
r
a
m
m
e
r
(Notsupplied)
E
c
o
n
o
m
a
i
r
e
Heater
havevoltagefree
switchingcontacts
Must
Test
Supply
Fuse
T3.15A
230V~50Hz
R
1
2
7
K
0
ONCOMOFFONCOMOFF
NL123456
A/HTIMED
O/P
W/HTIMED
O/P
Fig. 15
SchematicDiagram(showingconnectionof anexternalcontroller)
22 7
5.4 ELECTRICAL
WARNING:THISAPPLIANCEMUSTBEEARTHED!
5.4.1 Mains.
a. The heater is supplied with mains cable (PVC sheathed, heat resisting to 85oC), 3 core: Brown; Blue; Green/
Yellow, 6A, 0.75mm2), connected to a terminal block and exiting through the heater at the right hand top. The
cable is suitable for a 230V 50Hz supply and requires connection to the fixed wiring using a double pole
switched, fused spur with a contact separation of at least 3mm in ALL poles. The fuse fitted must be rated 5A
to BS 1362. Connections must also be in accordance with the current edition of I.E.E Regulations BS 7671.
NOTE: If, for any reason, the heater is re-wired, then 3 core cable that meets the above specification MUST be used. Under
NO circumstances, should 5 core cable be used for the combined purpose of supplying power to the heater and
connecting the thermista-stat!
b. Fan delay and overheat (limit controls) are not adjustable and are factory set so that the limit switch opens at
93OC and closes at 76OC.
c. An electronic controller (thermista-stat) is supplied which acts like a room thermostat.
5.4.2 Thermista-stat and its location.
a. The thermista-stat should be located where there is free air circulation and positioned approx. 1.5m (5ft) from
the floor.
b. Avoid the following locations:
i. In a room where temperature is greatly affected by the sun or any other heat source, e.g. radiant fire,
wall light fittings or TV set.
ii. Near an outside door or windows, or on an outside wall.
iii. Where it will be affected by warm air ducts, diffusers, waste pipes or the heater itself.
iv. Where it will be subjected to vibration.
c. Connect the thermista-stat wires to terminals ‘8’ and ‘9’ on the terminal block (see Figs. 13 & 14).
5.5 GAS (SeeBS 5864and BS6891)
5.5.1 The local gas supply conditions MUST be adequate for the specified burner pressures as stated in the technical
specification (para. 1.3)
5.5.2 An independent gas supply pipe from the meter is to be preferred wherever possible. Where this is not possible, the
pipe must be capable of taking the complete input of the heater and all other gas appliances being served by the
same pipe. This supply should be suitably sized to conform to British Standards requirements of no more than 1.0
mbar (0.4in wg) pressure drop (See table of discharge in BS 6891).
5.5.3 The 1/2in union gas cock (supplied) MUST be fitted to the gas inlet of the heater for easy isolation during servicing.
The gas pipe should be fitted and installed so as to be durable, substantial and gas tight. To assist in determining
where a gas connection may not be tight, a leak detection fluid should be applied around the connection. Under no
circumstances should a flame be used to locate a gas leak. Gas entry to the air heater is through either side to a Rc1/2
(1/2in BSP. external [taper] thread).
6. AIRHEATERCOMMISSIONING
6.1 PREPARATION:
After installation of the appliance, you MUST do the following:
6.1.1 Test for gas leakage using proprietary detection fluid and seal any leaks found.
6.1.2 Carry out preliminary electrical system checks.
6.1.3 Ensure that:
a. filter, fan and fan compartments are free from obstructions.
b. all registers or grilles are open and conform to design specifications.
c. return, relief and ventilation air installations are adequate.
6.2 SYSTEMBALANCING:
6.2.1 Set the air heater electrical supply ON.
6.2.2 Set the thermista-stat to the “SUMMER AIRFLOW” position.
6.2.3 Balance the system to provide the required volume proportions at the warm air outlets.
Fig.14
Economaire25LogicDiagram
Fig. 7
ElectricalDoorAssembly
IMPORTANT
ON
ON
6
12
93
LED status indicator
Time control
Indicator panel
Terminalblock
Cover plate screws
Note: If the system includes ceiling diffusers, the air through these should be NOT LESS THAN 1.5m/s (300ft/min), except
for very small rooms, (i.e. bathrooms etc.). Outlet faces may require partial blanking in order to achieve this.
6.3 LIGHTINGIGNITION ANDMAINBURNER:
6.3.1 Turn on the gas supply to the heater.
6.3.2 Set both the “AIR HEATER” and “WATER
HEATER” switches on the time control unit to
the “OFF” position.
6.2.3 Set the thermista-stat to “9”.
6.3.4 Locate the LED status indicator which can be
observed through the inspection hole at the
bottom right hand corner of the control
module.
6.3.5 Turn on the mains power supply to the heater
6.3.6 Set the “AIR HEATER” switch on the time
control to “CONT.” and observe the LED
status indicator.
6.3.7 Whilst the control module runs through its
diagnostic cycle the decimal point (DP) in the
bottom right hand corner of the LED display
will flash continuously.
6.3.8 Theigniterwill spark foramaximum period of
60 seconds during which time the ignition and
main burners SHOULD ignite and the igniter
will stop.
6.3.9 When the control module reaches stage 5,
(indicated by “5” on the LED) power is fed to the gas valve and the green LED “ON” light on the indicator panel will
illuminate. After a period of approx. 5 seconds, the module will move on to stage 6 (indicated by “6” on the LED).
NOTE:regardlessofwhentheburner ignitesduringthe 60secondperiod, theLEDwill continuetodisplay stage6.
6.3.10 If, after the 60 second period, the main burner has ignited the LED indicator will show “0” and the green LED “ON”
light on the indicator panel will remain steady.
6.3.11 If the main burner fails to ignite, the red LED marked “LOCKOUT” will illuminate on the display panel and the LED
status indicator will display an alphanumeric character relevant the the fault detected.
6.3.12 In the event of a lockout and the ignition and main burners failing to ignite, reference should be made to table 4 in the
fault finding section of these instructions in order to establish the fault condition.
6.3.13 Allow the air heater to operate for a minimum of 15 minutes to ensure stability.
6.3.14 Reset the thermista-stat to the desired comfort level.
6.3.15 Set the time control to the desired “on” and “off” periods.
6.3.17 Set the “AIR HEATER” switch on the time control to “TIMED”.
6.4 MAINBURNERPRESSURETEST:
NOTE:AIRHEATERBURNERSAREFACTORYSETTOPROVIDEANOMINALHIGHRATEOUTPUTASDETAILEDINSUB
PARA1.2
6.4.1 Loosen the screw on the outlet pressure test point and fit a pressure test gauge (see Fig. 8)
6.4.2 Check the gauge reading against the information at paragraph 1.3.
6.4.3 If necessary, use the burner pressure adjuster to obtain required gauge reading in accordance with paragraph 1.3.
6.4.4 Remove the pressure gauge and re-tighten screw on the outlet pressure test point.
6.5 AUTOMATICCONTROLSCHECK
6.5.1 Light the ignition and main burners as detailed in 6.3 above.
6.5.2 Allow the heater to operate for 15 minutes to ensure stability.
6.5.3 After a short period, ensure that the fan increases to full speed.
6.5.4 When the temperature reaches the control setting, check that the main burner cycles ON and OFF at intervals of
approx. 75 to 120 seconds. 821
Fig. 8
MultifunctionControl
(With Ignition Controller removed).
1. Inlet Pressure Test Point.
2. Outlet Pressure Test Point.
3. Burner Pressure Adjuster.
1
3
2
FanPerformanceCurve
150
0.07
mbar
0.50
0.375
R
e
s
i
s
t
a
n
c
e
E
x
t
e
r
n
a
l
t
o
H
e
a
t
e
r
0.25 0.10
0.125
Air Volume
0.05
0.20
0.15
in.wg.
200
0.09 250
0.12
300 ft /min
0.14m /sec
3
3
Fig.13
Economaire25FlowDiagram
1r
b
b
g/y
br
br
r
r
r
r
br
N
L
br
bbk
bbr
w
w
gy gy
gy
pk
w
w
v
yy
b
bk
br
b
bk
br
b
b
b
r
r
bk
w
bk
or
or
r
bk
bk
bk
bk
bk
bk
br
v
gy
pk
pk
g/y
g/y
pk
br
y
y
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
CONTROL MODULE
AIR
CIRCULATION
FAN
CLEANFLOW
FILTER
(OPTIONAL)
COMBUSTION
AIR FAN
AIR PROVING
SWITCH
FAN POWER
CAPACITOR
RESISTOR
TERMINAL
BLOCK
CLOCK
AIR
HEATER
SWITCH
WATER
HEATER
SWITCH
WATER HEATER
GAS CONTROL
(OPTIONAL)
WATER HEATER
THERMOSTAT
THERMISTA-STAT AIR HEATER
GAS CONTROL
COVER
COVER
WATER HEATER
OVERHEAT
LIMIT SWITCH
LIMIT SWITCH
FDC ASSEMBLY
AIR HEATER
IGNITION
ELECTRODE
WATER
HEATER
IGNITION
ELECTRODE
WIRE COLOUR CODE
black ------bk
blue -------b
brown -----br
grey -------gy
violet ------v
white ------w
red ---------r
pink --------pk
yellow------y
orange-----or
black/white-----bk/w
green/yellow ---g/y
WIRE COLOUR CODE
black ------bk
blue -------b
brown -----br
grey -------gy
violet ------v
white ------w
red ---------r
pink --------pk
yellow------y
orange-----or
black/white-----bk/w
green/yellow ---g/y
6.6 SAFETYCHECK:
In order to check the correct operation of the control module, run the heater for
a short period and introduce a fault condition by carrying out the following
sequence:
6.6.1 Check for gas soundness within the appliance.
6.6.3 Turn on both the gas and electrical supplies to the heater.
6.6.4 Set the “AIR HEATER” switch on the time control unit to “CONT”.
6.6.5 Light the ignition and main burners as described in section 6.3
6.6.6 Allow the heater to run for a period of 5 minutes to stabalise.
6.6.7 Turn off gas supply to heater at the heater Gas Cock. DO NOT TURN
OFFATGASMETER!
6.6.8 Having detected the fault condition, the module should cause the red
LED on the indicator panel to flash and the module will go through the
ignition sequence. Having detected the fault condition a second time,
the control module should cause the heater to go into lockout,
indicated by a constant red LED and the LED status indicator will show
“6”
6.6.9 Reinstate gas supply and wait for a minimum period of 10 seconds.
6.6.10 Depress the “RESET” button on the Indicator Panel.
6.6.11 The heater will go through its ignition procedure and the ignition and
mainburnersSHOULD ignite.
6.6.12 Set the “AIR HEATER” switch on the time control unit to “TIMED”
9
20
7. INTEJANCIRCULATOR
7.1 WATERCIRCULATIONSYSTEM.Detailedrecommendations forthewater circulationsystem aregivenin BS6798,BS5449
(for small bore and microbore central heating systems), and BS5446. The maximum water side operating pressure (PMS) is
1bar.
7.1.1 To ensure good circulation in gravity circuits, flow pipes should be designed to run vertically from the water heater
before running laterally. Any lateral run should be less than 2 x the previous vertical run. Pipework should be installed
with a rise towards the vent point. In systems with poor circulation, a pump kit is also available.
7.1.2 Drain cocks must be located in accessible positions that permit the draining of the whole system, including the
appliance and hot water storage vessel. A drain cock should be fitted at the lowest point of the water heating circuit
and, in the case of an indirect system, another must be fitted at the lowest point of the cold feed. Drain cocks should
be at least 1/2in nominal size and be in accordance with BS2879.
7.1.3 Economy valves can only be used in a DIRECT installation.
Feed
Tank
Direct storage
cylinder
Hot water
Circulator
Drain cock
Fig. 9
TypicalINTEJANdirectsystemapplication.
Fig.9a
Positionof temperaturestops
Snap rivet
Temp. stop 2 for direct
system. Remove for
indirect system
application.
Spindle
Fixingscrew
Temp. stop 1
Isigniter
operating?
L
E
D
d
i
s
p
l
a
y
N
N
Doesignition
burnerlight?
Y
Isgas
supplyon?
Cleanignition
burner
Replace
i
g
n
i
t
i
o
n
lead
Restoregas
supply
Y
Y
Isignition
burner
blocked?
N
9
C
i
r
c
u
l
a
t
o
r
o
p
e
r
a
t
i
n
g
n
o
r
m
a
l
l
y
.
0
8
Y
23
Iscirculator
switchset
toon?
Does
fluefan
start?
Y
Doesair
pressure
switch
operate?
Y
Isthere
230Vtothe
heater?
IsLED
Displaying
H?
Hasfuse
blown?
Isthere230V
acrosspins11&
12atstartup?
Isthere230V
acrosspins14&
Natstart up?
Are
electrical
connections
good?
NN
NNN
Y
D
o
e
s
m
a
i
n
B
u
r
n
e
r
L
i
g
h
t
?
Y
C
h
a
n
g
e
i
g
n
i
t
i
o
n
c
o
n
t
r
o
l
l
e
r
a
n
d
m
u
l
t
i
f
u
n
c
t
i
o
n
c
o
n
t
r
o
l
Replace
ignition
controller
D
o
e
s
b
u
r
n
e
r
p
r
e
s
s
u
r
e
i
n
c
r
e
a
s
e
?
H
a
s
i
g
n
i
t
e
r
s
t
o
p
p
e
d
s
p
a
r
k
i
n
g
?
A
r
e
ignite
r
l
e
a
d
termin
a
l
e
n
d
s
crack
e
d
o
r
bro
k
e
n
?
N
N
Y
Y
N
N
Y
Y
Are
electrical
connections
sound?
Areair
pressure
pipes
sound?
Y
Y
NN
Replacefuse
Replacecontrol
module
Re-sealpipesor
replaceif
necessary
Replace
fluefan
Press“RESET”
Replacecontrol
module
Replacecontrol
module
Isthere
230Vacross
pins
8& 9?
IsLED
Displaying
7?
Isigniter
leadcondition
good?
Isigniter
condition
good?
Y
Y
Y
C
h
a
n
g
e
i
g
n
i
t
i
o
n
c
o
n
t
r
o
l
l
e
r
N
N
N
Y
Replace
multifunction
control
Replace
igniterlead
Replaceigniter
N
N
Istheflue
thecorrect
length?
Hasorifice
beenused
correctly?
Y
Y
Changep
r
e
s
s
u
r
e
switch
Re-configure
flue
Referto
paragraph. 5
Y
Y
Y
Y
N
Set
thermostat
Water Circulator
Diagnostics Flowchart
NOTE: The circulator thermostat is factory set to provide a temperature range of 50oC to 82oC. The temperature is increased
by rotating the theromostat knob clockwise and temperature stop 2 MUST be left in position (see fig. 9a) if the
circulator is used in a direct application, ensuring a maximum temperature of 60oC. For indirect applications, remove
temperature stop 2.
In order to ensure that soundness of the heater is maintained, you MUST ensure that flow and return pipes into the
sealed compartment are sealed with the supplied grommets!
7.2 WATERCONNECTIONS:
Note: Both flow and return connections are Rp3/4(3/4in BSP female) connections.
IMPORTANT:Usecompressionfittingsattheapplianceflowand returnconnections andatthe airheater casingexit,tofacilitate
easyaccessto the circulatorbody.
7.2.1 Remove the fixing screws holding the sealing panel in place.
7.2.2 Carefully remove the sealing panel, such that access can be gained to the circulator compartment.
7.2.3 Side Exit: Knockouts/holes are provided in both sides of the heater cabinet for external pipe routing. Horizontal pipe
runs are to be kept to an absolute minimum.
7.2.4 TopExit:
A) Remove the plastic plugs from the air heater top panel and the fan chamber floor.
B) Pass the flow and return pipes (flow pipe to the rear) from below and then locate the pipes with the circulator body
connections. Fully tighten the connections to the main body before completing the connections to the top ends of
the Flow and Return pipes, ensuring that the pipework does not restrict access to the circulator thermostat phial
pocket or the air heater heat exchanger access panel.
NOTE: In order to maintain an air tight seal, the supplied grommets MUST be used where the flow and return pipes pass
through the upper sealing plate and diaphragm.
IMPORTANT:Ensurethatthefittingsonthecirculatorbodyarewellsupportedwhenmakingflowandreturnconnections.
7.2.5 Using good quality duct tape, seal around the Flow and Return pipes where they pass through the air heater top
panel and fan chamber floor.
10 19
Feed
tank Cold water
storage
Hot water
Circulator
Indirect storage
cylinder
Drain
cock
Drain
cock
Fig. 10
TypicalINTEJANindirectsystemapplication.
Isigniter
operating?
Isthere
230Vacross
pins5 &6?
I
s
t
h
e
r
e
2
3
0
V
a
c
r
o
s
s
p
i
n
s
1
&
2
?
R
e
p
l
a
c
e
m
o
d
u
l
e
IsLED
Displaying
4?
LEDdisplay
Isigniter
leadcondition
good?
Isigniter
condition
good?
Y
N
Y
Y
Changeignition
controller
Doesignition
burnerlight?
Y
Isgas
supplyon?
Cleanignition
burner
Replaceignition
lead
Restoregas
supply
Replace
control
module
Y
Y
Isignition
burner
blocked?
N
N
6
H
e
a
t
e
r
o
p
e
r
a
t
i
n
g
n
o
r
m
a
l
l
y
.
I
s
a
i
r
c
i
r
c
u
l
a
t
o
r
f
a
n
o
p
e
r
a
t
i
n
g
?
Y
A
r
e
f
a
n
c
o
n
n
e
c
t
i
o
n
s
g
o
o
d
?
N
Y
I
s
p
o
w
e
r
r
e
a
c
h
i
n
g
t
h
e
f
a
n
?
R
e
p
l
a
c
e
f
a
n
0
5
Y
23
Isheater
switchset
toon?
Does
combustion
airfan
start?
Y
Doesair
pressure
switch
operate?
Y
Isthere
230Vto the
heater?
IsLED
Displaying
F?
Hasfuse
blown?
Isthere230V
acrosspins11&
12atstartup?
Isthere230V
acrosspins14&
Natstartup?
Are
electrical
connections
good?
NN
N
N
NN
Y
Does
m
a
i
n
Burner
L
i
g
h
t
?
Y
Y
Change
i
g
n
i
t
e
r
controll
e
r
a
n
d
multifun
c
t
i
o
n
control
Replace
ignition
controller
Does
b
u
r
n
e
r
pres
s
u
r
e
incre
a
s
e
?
Hasi
g
n
i
t
e
r
stop
p
e
d
spark
i
n
g
?
Are
igniterlead
terminalends
crackedor
broken?
N
N
N
N
Y
Y
N
N
N
N
Y
Y
Y
Are
electrical
connections
sound?
Areair
pressure
pipes
sound?
Y
Y
NN
Replacefuse
Replacecontrol
module
Re-sealpipesor
replaceif
necessary
Replace
combustion
airfan
Press“RESET”
Replacecontrol
module
Replace
multifunction
control
Replace
igniterlead
Replaceigniter
N
N
Istheflue
thecorrect
length?
Hasorifice
beenused
correctly?
Y
Y
Changepressure
switch
Re-configure
flue
Referto
paragraph. 5
Y
Y
Y
Y
N
Set
thermista-stat
to position“9”
Air Heater
Diagnostics Flowchart
11
18
8. INTEJANCIRCULATORCOMMISSIONING
8.1 PREPARATION:
8.1.1 Ensure that the gas and electrical supplies are OFF.
8.1.2 Fill the water circulation system, clear any air locks and check for water soundness, sealing any leaks detected.
8.1.3 Refit the sealing panel and secure using the fixing screws.
NOTE: Whilst the sealing panel needs to be fixed in such a manner so as to ensure an air tight seal, care MUST be taken not
to over tighten the fixing screws.
8.2 LIGHTING IGNITIONANDMAINBURNERS:
8.2.1 Turn on the gas supply to
the heater.
8.2.2 Set both the “AIR HEATER”
and “WATER HEATER”
switches on the time control
unit to the “OFF” position.
8.2.3 Set the thermostat so that it
reaches the maximum stop.
8.2.4 Locate the LED status
indicator which can be
observed through the
inspection hole at the
bottom right hand corner of
the control module.
8.2.5 Turn on the mains power
supply to the heater
8.2.6 Set the “WATER HEATER”
switch on the time control to
“CONT.” and observe the
LED status indicator.
8.2.7 Whilst the control module
runs through its diagnostic
cycle the decimal point (DP)
in the bottom right hand
corner of the LED display
will flash continuously.
8.2.8 The igniter will spark for a
maximumperiodof60
seconds during which time
the ignition burner and main burner SHOULD ignite and the igniter will stop.
8.2.9 When the control module reaches stage 8, (indicated by “8” on the LED) power is fed to the gas valve and the green
LED “ON” light on the indicator panel will illuminate.After a period of approx. 5 seconds, the module will move on to
stage 9 (indicated by “9” on the LED). NOTE: regardless of when the burner ignites during the 60 second period,
theLED willcontinueto displaystage9.
8.2.10 If, after the 60 second period, the main burner has ignited the LED indicator will show “0” and the green LED “ON”
light on the indicator panel will remain steady.
8.2.11 If the main burner fails to ignite, the red LED marked “LOCKOUT” will illuminate on the display panel and the LED
status indicator will display an alphanumeric character relevant the the fault detected.
8.2.12 In the event of a lockout and the ignition and main burners failing to ignite, reference should be made to table 4 in the
fault finding section of these instructions in order to establish the fault condition.
8.2.13 Test for gas leakage at the supply, multifunction control, ignition burner and main burner using proprietary detection
fluid, sealing any leaks found.
8.2.14 Allow the circulator to operate for a minimum of 15 minutes to ensure stability.
8.2.15 Reset the thermostat to the desired water temperature.
Burner on
Demand satisfied
Burner on
Demand satisfied
Burner extinguishes
No further demand
Burner extinguishes
Fan slows/stops
Is time
period up?
START
END
Timed or continuous operation
No
No
No
No No
No
No
No
Yes Yes
No
Module powers up
LOCKOUT
LOCKOUT
RESET
RESET
Demand
for water
heat
Demand
for water
heat
Demand
for air
heat
Demand
for air
heat
Is no-flow
provided?
Fan starts
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Pressure switch operates
Is flow
provided?
Thermostat
Thermista-stat
Thermostat Thermista-stat
Water circulator
Air heater
No
Fig. 12
ControlFlowchart
8.2.16 Set the time control to the desired “on” and “off” periods.
8.2.17 Set the “WATER HEATER” switch on the time control to “TIMED”.
8.3 WATERBURNERPRESSURETEST:
NOTE:THEWATERCIRCULATORBURNERSAREPRE-SETANDSHOULDNOTREQUIREADJUSTING.
8.3.1 Loosen the screw on the outlet pressure test point and fit a pressure test gauge (see Fig. 8)
8.3.2 Check the gauge reading against the information at paragraph 1.3.
8.3.3 If necessary, use the burner pressure adjuster to obtain the required gauge reading as shown at paragraph 1.3
8.3.4 Remove the pressure gauge and re-tighten the screw on the outlet pressure test point.
8.4 SAFETYCHECKS:
8.4.1 Check for gas soundness within the appliance.
8.4.2 Check for water soudness around circulator and ALL joints.
8.4.3 Turn on both the gas and electrical supplies to the heater.
8.4.4 Set the “WATER HEATER” switch on the time control unit to “CONT”.
8.4.5 Light the ignition and main burners as described in section 8.2
8.4.6 Allow the circulator to operate for a period of 5 minutes to stabilise.
8.4.7 Turn off gas supply to heater at the heater gas cock. DO NOT TURN OFF AT GAS METER!
8.4.8 The circulator SHOULD automatically go into “LOCKOUT” indicated by the red LED on the indicator panel and the
LED status indicator will show “H”
8.4.9 Reinstate the gas supply and wait for a minimum period of 10 seconds.
8.4.10 Depress the “RESET” button on the indicator panel.
8.4.11 The heater will go through its ignition procedure and the ignition and main burners SHOULD ignite.
8.4.12 Set the “WATER HEATER” switch on the time control unit to “TIMED”
9. INSTRUCTIONSFORUSERS
9.1 If the building is unoccupied, ensure that the user instructions are left taped to the air heater for the the user’s reference and
that the installation instructions are left at or near the air heater for use on future service calls.
9.2 If the building is occupied, hand the user instructions over and ensure that the user understands:
9.2.1 How to light both the air heater and water circulator.
9.2.2 How to re-set the air heater or water circulator if “LOCKOUT” occurs.
9.2.3 How to operate the time control, thermista-stat and the SUMMER AIRFLOW switch.
9.2.4 That the time control must be reset following a power failure.
9.2.5 How to use the circulator thermostat to set the water temperature.
9.2.6 How to turn off the heater and switch off the electrical supply to the heater.
9.2.7 How to remove, clean and refit the air filter and at what intervals, (i.e. fortnightly, or weekly for new houses).
9.2.8 How to control the heating system by opening and closing warm air outlets.
9.2.9 How to obtain summer air circulation.
9.2.10 Thattheairgrillesonthe heaterorheater compartment;grillesand ventilatorsinthe walls,windowsor doorsof
thebuildingMUSTNOTBEOBSTRUCTED.
9.2.11 That the heater must be serviced at least once a year by a competent person to ensure efficient and safe operation.
9.2.12 That the red instructions for safe use have been pointed out and understood.
9.2.13 Thatexperthelpmustbeobtainedifpersistent “LOCKOUT”occurs.
10. MAINTENANCE
NOTE:It isrecommendedthatthisappliance beservicedatintervalsof nolessthan12months.
IMPORTANT:Ensurethatthegasandelectricity suppliesareisolatedbeforecommencinganymaintenance orreplacementof
components. Because the appliance is room sealed, it is also imperative that if at any stage of repairs the gasket on the sealing
plateis damagedit MUSTbe replaced!Aftercompletionofanymaintenance,always testforgassoundnessandcarryout a
completefunctionaltestoftheapplianceinaccordancewiththeCommissioningInstructionsatparagraphs 6.1to6.6inclusive.
12 17
NOTE: When reassembling ensure that gaskets are soundly sealed and replaced where necessary (See cautionary note at
paragraph10)Prior touse, youMUST fullycommissionthe heaterinaccordancewith theseinstructions.
10.12. FLUEFAN,REMOVALANDCLEANING
10.12.1 Remove the air circulation fan as detailed at 10.6
10.12.2 Disconnect the power supply to the pressure switch.
10.12.3 Carefully remove the feed pipes to the pressure switch TAKING CARE TO NOTE THEIR POSITION.
10.12.4 Unscrew the 2 x fixing screws holding the pressure switch in place and remove the switch.
10.12.5 Carefully open the plastic insulators on the fan fly-lead and break the electrical connections such that the spade
connectors can be fed through the grommet on the sealing plate..
10.12.6 Remove the 11 x fixing screws holding the flue fan sealing plate in place and remove the plate.
NOTE:WHENREMOVINGTHESEALINGPLATE,CAREFULLYFEEDTHEPRESSUREPIPESTHROUGHTHEGROMMETS
INTHEPLATE,TAKINGCARENOTTOPULLTHEPIPESOFFTHEFANPRESSURETAPPINGS!
10.12.6 Release the 4 x fixing screws holding the flue fan in place
10.12.7 Carefully withdraw the fan and its gasket from the collecter box, taking care not to damage the fan blades.
10.12.8 Remove all dust from both the impeller and motor, taking care not to disturb the balance of the fan.
10.12.9 Refitting/replacement is in reverse order.
11. DEFECTDIAGNOSIS
The following table shows the LED status indicator display and the corresponding fault condition, along with the lockout type. It
should be noted that under certain conditions the red LED relating to the air heater may flash. This is part of the control sequence
and the module should reset automatically. It is ONLY necessary to press the “RESET” button if the red LED is on continuously.
10.1 ROUTINEMAINTENANCE:
10.1.1 Operate the appliance and check for the correct function of the burner and controls.
10.1.2 Turn OFF the gas and electrical supplies to the appliance.
10.1.3 Remove the air heater front panel.
10.1.4 Remove and check the return air filter/cleaner for cleanliness, remove and clean the air circulation fan as detailed in
para10.6.
10.1.5 Remove the burner and controls assembly as detailed in para 10.2, inspect and clean the main burner and injector as
necessary. Examine the main burner for cracks, including hairline cracks, exchanging the burner as necessary.
10.1.6 Inspect and clear the ignition burner orifice.
10.1.7 Clean the heat exchanger flueways by thoroughly brushing from above and below.
10.1.8 By viewing through the fan aperture, and using a torch or similar, examine the heat exchanger externally for signs of
cracks or holes, particularly around welded joints.
10.1.9 Using a torch or similar, introduce a light source into the heat exchanger burner aperture and upper access port, and
again examine the heat exchanger for signs of cracks or holes, particularly around welded joints, whilst again viewing
through the fan aperture.
10.1.10 Refit the air circulation fan, burner and controls assembly, and air filter/air cleaner.
10.1.11 Allow the air heater to operate for approximately 15 minutes to ensure stability and, with the main burner lit, ensure
that the operation of the air circulation fan does not affect the main burner flame profile.
10.1.12 Locate the flue gas test point (see fig.1) and attach a flue gas analyser to the test point in accordance with the
manufacturer’s instructions. NOTE: the CO/CO2ratio should be no greater than 0.008
10.1.13 Fully commission the appliance in accordance with paragraphs 6 and 8.
NOTE:The flue gas test MUST NOT be used as an alternative to servicing the heater!
10.2 MULTIFUNCTIONCONTROLANDAIRHEATER/WATERCIRCULATORBURNERASSEMBLYREMOVAL:
NOTE: Both the air heater and water circulator burner assemblies, as well as their respective ignition burner assemblies,
MUST be removed as a complete unit together with their respective multifunction control.
PROCEDURE:
10.2.1 Ensure that the gas and electrical supplies are switched OFF.
10.2.2 Remove the front door from the heater.
10.2.3 Remove the fixing screws that hold the sealing panel in place and carefully remove the panel.
10.2.4 Disconnect the electronic module from the relevant multifunction control by removing the securing bolt and sliding it
away from the heater unit, taking care not to cause damage.
10.2.5 Break the flared connection on the relevant multifunction control from the gas supply feed.
10.2.6 Remove the relevant burner assembly fixing screws.
10.2.7 Whilst supporting the assembly, carefully remove the fixing screws securing the multifunction control.
10.2.8 Carefully remove the complete assembly, by sliding the sealing grommet out of the bulkhead, taking care not to cause
damage to the grommet!
10.2.9 Refitting the burner assembly is a reverse procedure of the above instructions.
10.3 BURNERASSEMBLYCLEANING:
10.3.1 Remove the burner assembly as detailed above.
10.3.2 Disconnect the ignition burner gas feed pipe from the ignition burner
10.3.3 Release the single screw, nut and washer securing the ignition burner to the main burner and remove the ignition
burner.
10.3.4 Release the 2 screws, nuts and washers securing the main burner to the mounting bracket and remove the main
burner.
10.3.5 Clean the burner thoroughly both inside and out with a soft brush. DO NOT ENLARGE, DISTORT OR DAMAGE
BURNERHOLES.
10.3.6 Reassemble in reverse order.
13
NOTE: When the air heater and watercirculator are used together, the status indications for the water circulator will
overridethosefortheair heater; therefore LED displays “8” and“9”willoverride“5”and “6”. For this reason, it
isstronglyrecommendedthattheairheaterandwatercirculatorbecommissionedindependently ofeachother.
16
Table.4
Controlmodulefaultindications
LED Cycle Fault Condition Lockout Type
0 Running None – all is well None
1 Air Proving Air switch closed Absolute
2 Air Proving Gas valve relay on (either) Absolute
3 Air Proving Air switch closure failed Absolute
4 Prove Heater Valve Gas valve current, relay should be open Air Heater
5 Prove Heater Valve None (wait for ignition burner) Air Heater
6 Prove Heater Relay Flame failure Air Heater
7 Prove Circulator Relay Gas valve current, relay should be open Circulator
8 Prove Circulator Relay None (wait for ignition burner) Circulator
9 Prove Circulator Relay Flame failure Circulator
A Running Excessive cabinet temperature Absolute
C Running Air flow sensor out of range Air Heater
E Running Problem with air circulator fan Air Heater
F Running Air heater limit stat Air Heater
H Running Circulator limit stat Circulator
L Running Open air flow sensor Air Heater
Fig. 11
Controlmodule, showingconnectorblocks.
NOTE:
Todisconnectthemodule,LIFTtheconnector
blocksoffthecircuit board.DO NOTremove
thewiresfromtheconnectorblock!
Connector
blocks
10.4. IGNITIONBURNERANDELECTRODEREMOVALANDREPLACEMENT:
10.4.1 Remove the burner as detailed in 10.2 above.
10.4.2 Disconnect the igniter lead from electrode.
10.4.3 Break the gas feed at the burner end of the gas feed pipe.
10.4.4 Release the single screw, nut and washer securing the ignition burner to the main burner assembly and carefully
remove the ignition burner assembly.
10.4.5 Release the electrode securing nut from the ignition burner assembly and withdraw the electrode.
10.4.6 Release the ignition burner feed pipe securing nut from the ignition burner assembly and withdraw the feed pipe and
injector from the ignition burner assembly. Disconnect the ignition burner injector from the ignition burner feed pipe
hook.
10.4.7 Release the 2 x 5mm screws securing the ignition burner bracket to the ignition burner mounting bracket and remove
the ignition burner bracket.
10.4.8 Refitting or replacement is in reverse order.
10.5 NOTE:If,atanytime,thegassupplyfeedpipeisremovedfromthemultifunctioncontrol,the ‘O’ringMUSTbereplaced.
10.6 AIRCIRCULATINGFAN,REMOVALANDCLEANING:
10.6.1 Ensure that the electrical supply is isolated.
10.6..2 Remove the front door from the heater and remove the fixing screws on the electrical door assembly.
10.6.3 Open the door assembly outwards on its hinges (see fig. 7) such that access is gained to the rear of the assembly.
10.6.4 Disconnect the fan flying leads from the fan assembly.
10.6.5 Release the fan assembly securing screw and withdraw the fan assembly from the heater cabinet, avoiding damage to
the fan blades.
10.6.6 Remove all dust from both the impeller and motor, taking care to not disturb the balance of the fan.
10.6.7 Refitting or replacement is in reverse order.
10.7 CONTROLMODULEREMOVAL:
10.7.1 Ensure that the electrical supply is isolated.
10.7.2 Remove the front door from the heater.
10.7.3 Loosen the top and bottom screws holding the electrical cover plate in place on the electrical door assembly. (see fig.
7) DONOTCOMPLETELYREMOVETHESCREWS ATTHIS STAGE.
10.7.4 Remove the cover plate by sliding it upwards, such that it exposes the control module.
10.7.5 Carefully disconnect the module by lifting the connecting blocks off the circuit board (see fig. 11)
NOTE:Thereis noneedto loosenanyof theconnectionscrews ontheconnectorblocks!
10.7.6 Completely remove the top and bottom cover plate screws and pull the control module free of the electrical door
assembly.
10.7.7 Fit the new control module in place and partially fit the cover plate fixing screws. DO NOT TIGHTEN SCREWS AT
THISSTAGE!
10.7.8 Re-connect the module by carefully pushing the connector blocks onto the circuit board.
10.7.9 Re-fit the electrical cover plate and tighten the cover plate screws.
10.7.10 Re-establish electrical supply.
10.7.11 Commission air heater and water circulator as decribed in the relevant sections above.
10.8 TIMECONTROL,SWITCHANDLEDINDICATOR(DAUGHTERBOARD)REMOVAL:
Preparation:
10.8.1 Ensure that the electrical supply is isolated.
10.8.2 Remove the appliance front door and release the 3 x securing screws on the electrical door assembly.
10.8.3 Open the door assembly outwards on its hinges (see fig. 7) such that access is gained to the rear of the assembly.
TimeControl removal:
10.8.3 Disconnect spade terminal connectors “C1”, “C2”, “C3” and “C5” from the time control.
10.8.4 Release the 3 x fixing screws securing the clock mounting plate to the electrical door and withdraw the total assembly
from the door.
10.8.5 Remove the 3 X M3 bolts that secure the time clock mechanism and remove from the mounting plate.
10.8.6 Refitting or replacement is in reverse order.
LEDIndicator(DaughterBoard)
10.8.7 Disconnect the daughter board by unplugging the flylead from the control module board.
10.8.8 Release the 3 x fixing screws securing the clock mounting plate to the electrical door and withdraw the total assembly
from the door.
10.8.9 Remove the 2 X M3 nuts holding the board onto the bolts and remove.
10.8.10 Replacement is in reverse order, ensuring to refit the spacers.
Switch/sremoval:
10.8.11 Disconnect the spade terminal connectors “S1”, “S2” and
“S3” or “S4”, “S5” and “S6” from the switch terminals.
10.8.12 Release the switch/s by pressing out from the back of the
electrical door assembly.
10.8.13 Fit new switch/s and lock into position by pressing home until
the locking tabs locate on the top and bottom of the switch.
10.8.14 Re-connect the spade connectors.
10.8.15 Re-fitting of the electrical door assembly is in reverse order.
10.8.16 Close the electrical door assembly and secure using the 3 x
fixingscrews.
10.8.17 Set the time control to correct time.
10.8.18 Set the time control to the required “ON” and “OFF” periods.
10.9 FANDELAYCONTROL/LIMITSWITCHREMOVAL:
10.9.1 Ensure that the electrical supply is isolated.
10.9.2 Remove the appliance front door.
10.9.3 Remove the 2 x fixing screws holding the FDC/limit switch
assembly in place and withdraw from the appliance.
10.9.4 Disconnect the wires from the terminal block and relaese the
clamping bush, in order to remove the wiring harness.
10.9.5 Refitting or replacement is in reverse order.
10.10 WATERCIRCULATORTHERMOSTATREMOVAL:
10.10.1 Remove the appliance front door.
10.10.2 Disconnect the two spade terminals from the back of the thermostat.
10.10.3 Carefully loosen the control knob from the shaft of the thermostat using a large flat head screwdriver and remove.
10.10.4 Loosen and remove the 2 x screws securing the thermostat and remove the thermostat from its mounting bracket.
10.10.5 Refitting or replacement is in reverse order.
10.11 HEATEXCHANGER ACCESS:
10.11.1 Ensure that the gas and elctrical supplies are isolated.
10.11.2 Remove the appliance front door.
10.11.3 Remove the 15 x screws holding the sealing panel in place and carefully remove the panel.
10.11.4 Remove the burner assembly as detailed at 10.2
10.11.5 Remove the multifunctional control for the water circulator (IF FITTED)
10.11.6 Release the 4 x screws securing the combustion chamber heat shield and withdraw the heat shield.
10.11.7 Release the 4 x screws securing the top access cover plate and withdraw the cover plate and gasket.
10.11.8 Release the 4 x screws securing the heat exchanger top sealing plate and withdraw the sealing plate and gasket.
10.11.9 Reassembly is in reverse order. 1514
Fig. 11
Controlmodule, showingconnectorblocks.
NOTE:
Todisconnectthemodule,LIFTtheconnector
blocksoffthecircuit board.DO NOTremove
thewiresfromtheconnectorblock!
Connector
blocks
10.4. IGNITIONBURNERANDELECTRODEREMOVALANDREPLACEMENT:
10.4.1 Remove the burner as detailed in 10.2 above.
10.4.2 Disconnect the igniter lead from electrode.
10.4.3 Break the gas feed at the burner end of the gas feed pipe.
10.4.4 Release the single screw, nut and washer securing the ignition burner to the main burner assembly and carefully
remove the ignition burner assembly.
10.4.5 Release the electrode securing nut from the ignition burner assembly and withdraw the electrode.
10.4.6 Release the ignition burner feed pipe securing nut from the ignition burner assembly and withdraw the feed pipe and
injector from the ignition burner assembly. Disconnect the ignition burner injector from the ignition burner feed pipe
hook.
10.4.7 Release the 2 x 5mm screws securing the ignition burner bracket to the ignition burner mounting bracket and remove
the ignition burner bracket.
10.4.8 Refitting or replacement is in reverse order.
10.5 NOTE:If,atanytime,thegassupplyfeedpipeisremovedfromthemultifunctioncontrol,the ‘O’ringMUSTbereplaced.
10.6 AIRCIRCULATINGFAN,REMOVALANDCLEANING:
10.6.1 Ensure that the electrical supply is isolated.
10.6..2 Remove the front door from the heater and remove the fixing screws on the electrical door assembly.
10.6.3 Open the door assembly outwards on its hinges (see fig. 7) such that access is gained to the rear of the assembly.
10.6.4 Disconnect the fan flying leads from the fan assembly.
10.6.5 Release the fan assembly securing screw and withdraw the fan assembly from the heater cabinet, avoiding damage to
the fan blades.
10.6.6 Remove all dust from both the impeller and motor, taking care to not disturb the balance of the fan.
10.6.7 Refitting or replacement is in reverse order.
10.7 CONTROLMODULEREMOVAL:
10.7.1 Ensure that the electrical supply is isolated.
10.7.2 Remove the front door from the heater.
10.7.3 Loosen the top and bottom screws holding the electrical cover plate in place on the electrical door assembly. (see fig.
7) DONOTCOMPLETELYREMOVETHESCREWS ATTHIS STAGE.
10.7.4 Remove the cover plate by sliding it upwards, such that it exposes the control module.
10.7.5 Carefully disconnect the module by lifting the connecting blocks off the circuit board (see fig. 11)
NOTE:Thereis noneedto loosenanyof theconnectionscrews ontheconnectorblocks!
10.7.6 Completely remove the top and bottom cover plate screws and pull the control module free of the electrical door
assembly.
10.7.7 Fit the new control module in place and partially fit the cover plate fixing screws. DO NOT TIGHTEN SCREWS AT
THISSTAGE!
10.7.8 Re-connect the module by carefully pushing the connector blocks onto the circuit board.
10.7.9 Re-fit the electrical cover plate and tighten the cover plate screws.
10.7.10 Re-establish electrical supply.
10.7.11 Commission air heater and water circulator as decribed in the relevant sections above.
10.8 TIMECONTROL,SWITCHANDLEDINDICATOR(DAUGHTERBOARD)REMOVAL:
Preparation:
10.8.1 Ensure that the electrical supply is isolated.
10.8.2 Remove the appliance front door and release the 3 x securing screws on the electrical door assembly.
10.8.3 Open the door assembly outwards on its hinges (see fig. 7) such that access is gained to the rear of the assembly.
TimeControl removal:
10.8.3 Disconnect spade terminal connectors “C1”, “C2”, “C3” and “C5” from the time control.
10.8.4 Release the 3 x fixing screws securing the clock mounting plate to the electrical door and withdraw the total assembly
from the door.
10.8.5 Remove the 3 X M3 bolts that secure the time clock mechanism and remove from the mounting plate.
10.8.6 Refitting or replacement is in reverse order.
LEDIndicator(DaughterBoard)
10.8.7 Disconnect the daughter board by unplugging the flylead from the control module board.
10.8.8 Release the 3 x fixing screws securing the clock mounting plate to the electrical door and withdraw the total assembly
from the door.
10.8.9 Remove the 2 X M3 nuts holding the board onto the bolts and remove.
10.8.10 Replacement is in reverse order, ensuring to refit the spacers.
Switch/sremoval:
10.8.11 Disconnect the spade terminal connectors “S1”, “S2” and
“S3” or “S4”, “S5” and “S6” from the switch terminals.
10.8.12 Release the switch/s by pressing out from the back of the
electrical door assembly.
10.8.13 Fit new switch/s and lock into position by pressing home until
the locking tabs locate on the top and bottom of the switch.
10.8.14 Re-connect the spade connectors.
10.8.15 Re-fitting of the electrical door assembly is in reverse order.
10.8.16 Close the electrical door assembly and secure using the 3 x
fixingscrews.
10.8.17 Set the time control to correct time.
10.8.18 Set the time control to the required “ON” and “OFF” periods.
10.9 FANDELAYCONTROL/LIMITSWITCHREMOVAL:
10.9.1 Ensure that the electrical supply is isolated.
10.9.2 Remove the appliance front door.
10.9.3 Remove the 2 x fixing screws holding the FDC/limit switch
assembly in place and withdraw from the appliance.
10.9.4 Disconnect the wires from the terminal block and relaese the
clamping bush, in order to remove the wiring harness.
10.9.5 Refitting or replacement is in reverse order.
10.10 WATERCIRCULATORTHERMOSTATREMOVAL:
10.10.1 Remove the appliance front door.
10.10.2 Disconnect the two spade terminals from the back of the thermostat.
10.10.3 Carefully loosen the control knob from the shaft of the thermostat using a large flat head screwdriver and remove.
10.10.4 Loosen and remove the 2 x screws securing the thermostat and remove the thermostat from its mounting bracket.
10.10.5 Refitting or replacement is in reverse order.
10.11 HEATEXCHANGER ACCESS:
10.11.1 Ensure that the gas and elctrical supplies are isolated.
10.11.2 Remove the appliance front door.
10.11.3 Remove the 15 x screws holding the sealing panel in place and carefully remove the panel.
10.11.4 Remove the burner assembly as detailed at 10.2
10.11.5 Remove the multifunctional control for the water circulator (IF FITTED)
10.11.6 Release the 4 x screws securing the combustion chamber heat shield and withdraw the heat shield.
10.11.7 Release the 4 x screws securing the top access cover plate and withdraw the cover plate and gasket.
10.11.8 Release the 4 x screws securing the heat exchanger top sealing plate and withdraw the sealing plate and gasket.
10.11.9 Reassembly is in reverse order. 1514
NOTE: When reassembling ensure that gaskets are soundly sealed and replaced where necessary (See cautionary note at
paragraph10)Prior touse, youMUST fullycommissionthe heaterinaccordancewith theseinstructions.
10.12. FLUEFAN,REMOVALANDCLEANING
10.12.1 Remove the air circulation fan as detailed at 10.6
10.12.2 Disconnect the power supply to the pressure switch.
10.12.3 Carefully remove the feed pipes to the pressure switch TAKING CARE TO NOTE THEIR POSITION.
10.12.4 Unscrew the 2 x fixing screws holding the pressure switch in place and remove the switch.
10.12.5 Carefully open the plastic insulators on the fan fly-lead and break the electrical connections such that the spade
connectors can be fed through the grommet on the sealing plate..
10.12.6 Remove the 11 x fixing screws holding the flue fan sealing plate in place and remove the plate.
NOTE:WHENREMOVINGTHESEALINGPLATE,CAREFULLYFEEDTHEPRESSUREPIPESTHROUGHTHEGROMMETS
INTHEPLATE,TAKINGCARENOTTOPULLTHEPIPESOFFTHEFANPRESSURETAPPINGS!
10.12.6 Release the 4 x fixing screws holding the flue fan in place
10.12.7 Carefully withdraw the fan and its gasket from the collecter box, taking care not to damage the fan blades.
10.12.8 Remove all dust from both the impeller and motor, taking care not to disturb the balance of the fan.
10.12.9 Refitting/replacement is in reverse order.
11. DEFECTDIAGNOSIS
The following table shows the LED status indicator display and the corresponding fault condition, along with the lockout type. It
should be noted that under certain conditions the red LED relating to the air heater may flash. This is part of the control sequence
and the module should reset automatically. It is ONLY necessary to press the “RESET” button if the red LED is on continuously.
10.1 ROUTINEMAINTENANCE:
10.1.1 Operate the appliance and check for the correct function of the burner and controls.
10.1.2 Turn OFF the gas and electrical supplies to the appliance.
10.1.3 Remove the air heater front panel.
10.1.4 Remove and check the return air filter/cleaner for cleanliness, remove and clean the air circulation fan as detailed in
para10.6.
10.1.5 Remove the burner and controls assembly as detailed in para 10.2, inspect and clean the main burner and injector as
necessary. Examine the main burner for cracks, including hairline cracks, exchanging the burner as necessary.
10.1.6 Inspect and clear the ignition burner orifice.
10.1.7 Clean the heat exchanger flueways by thoroughly brushing from above and below.
10.1.8 By viewing through the fan aperture, and using a torch or similar, examine the heat exchanger externally for signs of
cracks or holes, particularly around welded joints.
10.1.9 Using a torch or similar, introduce a light source into the heat exchanger burner aperture and upper access port, and
again examine the heat exchanger for signs of cracks or holes, particularly around welded joints, whilst again viewing
through the fan aperture.
10.1.10 Refit the air circulation fan, burner and controls assembly, and air filter/air cleaner.
10.1.11 Allow the air heater to operate for approximately 15 minutes to ensure stability and, with the main burner lit, ensure
that the operation of the air circulation fan does not affect the main burner flame profile.
10.1.12 Locate the flue gas test point (see fig.1) and attach a flue gas analyser to the test point in accordance with the
manufacturer’s instructions. NOTE: the CO/CO2ratio should be no greater than 0.008
10.1.13 Fully commission the appliance in accordance with paragraphs 6 and 8.
NOTE:The flue gas test MUST NOT be used as an alternative to servicing the heater!
10.2 MULTIFUNCTIONCONTROLANDAIRHEATER/WATERCIRCULATORBURNERASSEMBLYREMOVAL:
NOTE: Both the air heater and water circulator burner assemblies, as well as their respective ignition burner assemblies,
MUST be removed as a complete unit together with their respective multifunction control.
PROCEDURE:
10.2.1 Ensure that the gas and electrical supplies are switched OFF.
10.2.2 Remove the front door from the heater.
10.2.3 Remove the fixing screws that hold the sealing panel in place and carefully remove the panel.
10.2.4 Disconnect the electronic module from the relevant multifunction control by removing the securing bolt and sliding it
away from the heater unit, taking care not to cause damage.
10.2.5 Break the flared connection on the relevant multifunction control from the gas supply feed.
10.2.6 Remove the relevant burner assembly fixing screws.
10.2.7 Whilst supporting the assembly, carefully remove the fixing screws securing the multifunction control.
10.2.8 Carefully remove the complete assembly, by sliding the sealing grommet out of the bulkhead, taking care not to cause
damage to the grommet!
10.2.9 Refitting the burner assembly is a reverse procedure of the above instructions.
10.3 BURNERASSEMBLYCLEANING:
10.3.1 Remove the burner assembly as detailed above.
10.3.2 Disconnect the ignition burner gas feed pipe from the ignition burner
10.3.3 Release the single screw, nut and washer securing the ignition burner to the main burner and remove the ignition
burner.
10.3.4 Release the 2 screws, nuts and washers securing the main burner to the mounting bracket and remove the main
burner.
10.3.5 Clean the burner thoroughly both inside and out with a soft brush. DO NOT ENLARGE, DISTORT OR DAMAGE
BURNERHOLES.
10.3.6 Reassemble in reverse order.
13
NOTE: When the air heater and watercirculator are used together, the status indications for the water circulator will
overridethosefortheair heater; therefore LED displays “8” and“9”willoverride“5”and “6”. For this reason, it
isstronglyrecommendedthattheairheaterandwatercirculatorbecommissionedindependently ofeachother.
16
Table.4
Controlmodulefaultindications
LED Cycle Fault Condition Lockout Type
0 Running None – all is well None
1 Air Proving Air switch closed Absolute
2 Air Proving Gas valve relay on (either) Absolute
3 Air Proving Air switch closure failed Absolute
4 Prove Heater Valve Gas valve current, relay should be open Air Heater
5 Prove Heater Valve None (wait for ignition burner) Air Heater
6 Prove Heater Relay Flame failure Air Heater
7 Prove Circulator Relay Gas valve current, relay should be open Circulator
8 Prove Circulator Relay None (wait for ignition burner) Circulator
9 Prove Circulator Relay Flame failure Circulator
A Running Excessive cabinet temperature Absolute
C Running Air flow sensor out of range Air Heater
E Running Problem with air circulator fan Air Heater
F Running Air heater limit stat Air Heater
H Running Circulator limit stat Circulator
L Running Open air flow sensor Air Heater
Burner on
Demand satisfied
Burner on
Demand satisfied
Burner extinguishes
No further demand
Burner extinguishes
Fan slows/stops
Is time
period up?
START
END
Timed or continuous operation
No
No
No
No No
No
No
No
Yes Yes
No
Module powers up
LOCKOUT
LOCKOUT
RESET
RESET
Demand
for water
heat
Demand
for water
heat
Demand
for air
heat
Demand
for air
heat
Is no-flow
provided?
Fan starts
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Pressure switch operates
Is flow
provided?
Thermostat
Thermista-stat
Thermostat Thermista-stat
Water circulator
Air heater
No
Fig. 12
ControlFlowchart
8.2.16 Set the time control to the desired “on” and “off” periods.
8.2.17 Set the “WATER HEATER” switch on the time control to “TIMED”.
8.3 WATERBURNERPRESSURETEST:
NOTE:THEWATERCIRCULATORBURNERSAREPRE-SETANDSHOULDNOTREQUIREADJUSTING.
8.3.1 Loosen the screw on the outlet pressure test point and fit a pressure test gauge (see Fig. 8)
8.3.2 Check the gauge reading against the information at paragraph 1.3.
8.3.3 If necessary, use the burner pressure adjuster to obtain the required gauge reading as shown at paragraph 1.3
8.3.4 Remove the pressure gauge and re-tighten the screw on the outlet pressure test point.
8.4 SAFETYCHECKS:
8.4.1 Check for gas soundness within the appliance.
8.4.2 Check for water soudness around circulator and ALL joints.
8.4.3 Turn on both the gas and electrical supplies to the heater.
8.4.4 Set the “WATER HEATER” switch on the time control unit to “CONT”.
8.4.5 Light the ignition and main burners as described in section 8.2
8.4.6 Allow the circulator to operate for a period of 5 minutes to stabilise.
8.4.7 Turn off gas supply to heater at the heater gas cock. DO NOT TURN OFF AT GAS METER!
8.4.8 The circulator SHOULD automatically go into “LOCKOUT” indicated by the red LED on the indicator panel and the
LED status indicator will show “H”
8.4.9 Reinstate the gas supply and wait for a minimum period of 10 seconds.
8.4.10 Depress the “RESET” button on the indicator panel.
8.4.11 The heater will go through its ignition procedure and the ignition and main burners SHOULD ignite.
8.4.12 Set the “WATER HEATER” switch on the time control unit to “TIMED”
9. INSTRUCTIONSFORUSERS
9.1 If the building is unoccupied, ensure that the user instructions are left taped to the air heater for the the user’s reference and
that the installation instructions are left at or near the air heater for use on future service calls.
9.2 If the building is occupied, hand the user instructions over and ensure that the user understands:
9.2.1 How to light both the air heater and water circulator.
9.2.2 How to re-set the air heater or water circulator if “LOCKOUT” occurs.
9.2.3 How to operate the time control, thermista-stat and the SUMMER AIRFLOW switch.
9.2.4 That the time control must be reset following a power failure.
9.2.5 How to use the circulator thermostat to set the water temperature.
9.2.6 How to turn off the heater and switch off the electrical supply to the heater.
9.2.7 How to remove, clean and refit the air filter and at what intervals, (i.e. fortnightly, or weekly for new houses).
9.2.8 How to control the heating system by opening and closing warm air outlets.
9.2.9 How to obtain summer air circulation.
9.2.10 Thattheairgrillesonthe heaterorheater compartment;grillesand ventilatorsinthe walls,windowsor doorsof
thebuildingMUSTNOTBEOBSTRUCTED.
9.2.11 That the heater must be serviced at least once a year by a competent person to ensure efficient and safe operation.
9.2.12 That the red instructions for safe use have been pointed out and understood.
9.2.13 Thatexperthelpmustbeobtainedifpersistent “LOCKOUT”occurs.
10. MAINTENANCE
NOTE:It isrecommendedthatthisappliance beservicedatintervalsof nolessthan12months.
IMPORTANT:Ensurethatthegasandelectricity suppliesareisolatedbeforecommencinganymaintenance orreplacementof
components. Because the appliance is room sealed, it is also imperative that if at any stage of repairs the gasket on the sealing
plateis damagedit MUSTbe replaced!Aftercompletionofanymaintenance,always testforgassoundnessandcarryout a
completefunctionaltestoftheapplianceinaccordancewiththeCommissioningInstructionsatparagraphs 6.1to6.6inclusive.
12 17
Feed
tank Cold water
storage
Hot water
Circulator
Indirect storage
cylinder
Drain
cock
Drain
cock
Fig. 10
TypicalINTEJANindirectsystemapplication.
Isigniter
operating?
Isthere
230Vacross
pins5 &6?
I
s
t
h
e
r
e
2
3
0
V
a
c
r
o
s
s
p
i
n
s
1
&
2
?
R
e
p
l
a
c
e
m
o
d
u
l
e
IsLED
Displaying
4?
LEDdisplay
Isigniter
leadcondition
good?
Isigniter
condition
good?
Y
N
Y
Y
Changeignition
controller
Doesignition
burnerlight?
Y
Isgas
supplyon?
Cleanignition
burner
Replaceignition
lead
Restoregas
supply
Replace
control
module
Y
Y
Isignition
burner
blocked?
N
N
6
H
e
a
t
e
r
o
p
e
r
a
t
i
n
g
n
o
r
m
a
l
l
y
.
I
s
a
i
r
c
i
r
c
u
l
a
t
o
r
f
a
n
o
p
e
r
a
t
i
n
g
?
Y
A
r
e
f
a
n
c
o
n
n
e
c
t
i
o
n
s
g
o
o
d
?
N
Y
I
s
p
o
w
e
r
r
e
a
c
h
i
n
g
t
h
e
f
a
n
?
R
e
p
l
a
c
e
f
a
n
0
5
Y
23
Isheater
switchset
toon?
Does
combustion
airfan
start?
Y
Doesair
pressure
switch
operate?
Y
Isthere
230Vto the
heater?
IsLED
Displaying
F?
Hasfuse
blown?
Isthere230V
acrosspins11&
12atstartup?
Isthere230V
acrosspins14&
Natstartup?
Are
electrical
connections
good?
NN
N
N
NN
Y
Does
m
a
i
n
Burner
L
i
g
h
t
?
Y
Y
Change
i
g
n
i
t
e
r
controll
e
r
a
n
d
multifun
c
t
i
o
n
control
Replace
ignition
controller
Does
b
u
r
n
e
r
pres
s
u
r
e
incre
a
s
e
?
Hasi
g
n
i
t
e
r
stop
p
e
d
spark
i
n
g
?
Are
igniterlead
terminalends
crackedor
broken?
N
N
N
N
Y
Y
N
N
N
N
Y
Y
Y
Are
electrical
connections
sound?
Areair
pressure
pipes
sound?
Y
Y
NN
Replacefuse
Replacecontrol
module
Re-sealpipesor
replaceif
necessary
Replace
combustion
airfan
Press“RESET”
Replacecontrol
module
Replace
multifunction
control
Replace
igniterlead
Replaceigniter
N
N
Istheflue
thecorrect
length?
Hasorifice
beenused
correctly?
Y
Y
Changepressure
switch
Re-configure
flue
Referto
paragraph. 5
Y
Y
Y
Y
N
Set
thermista-stat
to position“9”
Air Heater
Diagnostics Flowchart
11
18
8. INTEJANCIRCULATORCOMMISSIONING
8.1 PREPARATION:
8.1.1 Ensure that the gas and electrical supplies are OFF.
8.1.2 Fill the water circulation system, clear any air locks and check for water soundness, sealing any leaks detected.
8.1.3 Refit the sealing panel and secure using the fixing screws.
NOTE: Whilst the sealing panel needs to be fixed in such a manner so as to ensure an air tight seal, care MUST be taken not
to over tighten the fixing screws.
8.2 LIGHTING IGNITIONANDMAINBURNERS:
8.2.1 Turn on the gas supply to
the heater.
8.2.2 Set both the “AIR HEATER”
and “WATER HEATER”
switches on the time control
unit to the “OFF” position.
8.2.3 Set the thermostat so that it
reaches the maximum stop.
8.2.4 Locate the LED status
indicator which can be
observed through the
inspection hole at the
bottom right hand corner of
the control module.
8.2.5 Turn on the mains power
supply to the heater
8.2.6 Set the “WATER HEATER”
switch on the time control to
“CONT.” and observe the
LED status indicator.
8.2.7 Whilst the control module
runs through its diagnostic
cycle the decimal point (DP)
in the bottom right hand
corner of the LED display
will flash continuously.
8.2.8 The igniter will spark for a
maximumperiodof60
seconds during which time
the ignition burner and main burner SHOULD ignite and the igniter will stop.
8.2.9 When the control module reaches stage 8, (indicated by “8” on the LED) power is fed to the gas valve and the green
LED “ON” light on the indicator panel will illuminate.After a period of approx. 5 seconds, the module will move on to
stage 9 (indicated by “9” on the LED). NOTE: regardless of when the burner ignites during the 60 second period,
theLED willcontinueto displaystage9.
8.2.10 If, after the 60 second period, the main burner has ignited the LED indicator will show “0” and the green LED “ON”
light on the indicator panel will remain steady.
8.2.11 If the main burner fails to ignite, the red LED marked “LOCKOUT” will illuminate on the display panel and the LED
status indicator will display an alphanumeric character relevant the the fault detected.
8.2.12 In the event of a lockout and the ignition and main burners failing to ignite, reference should be made to table 4 in the
fault finding section of these instructions in order to establish the fault condition.
8.2.13 Test for gas leakage at the supply, multifunction control, ignition burner and main burner using proprietary detection
fluid, sealing any leaks found.
8.2.14 Allow the circulator to operate for a minimum of 15 minutes to ensure stability.
8.2.15 Reset the thermostat to the desired water temperature.
Feed
Tank
Direct storage
cylinder
Hot water
Circulator
Drain cock
Fig. 9
TypicalINTEJANdirectsystemapplication.
Fig.9a
Positionof temperaturestops
Snap rivet
Temp. stop 2 for direct
system. Remove for
indirect system
application.
Spindle
Fixingscrew
Temp. stop 1
Isigniter
operating?
L
E
D
d
i
s
p
l
a
y
N
N
Doesignition
burnerlight?
Y
Isgas
supplyon?
Cleanignition
burner
Replace
i
g
n
i
t
i
o
n
lead
Restoregas
supply
Y
Y
Isignition
burner
blocked?
N
9
C
i
r
c
u
l
a
t
o
r
o
p
e
r
a
t
i
n
g
n
o
r
m
a
l
l
y
.
0
8
Y
23
Iscirculator
switchset
toon?
Does
fluefan
start?
Y
Doesair
pressure
switch
operate?
Y
Isthere
230Vtothe
heater?
IsLED
Displaying
H?
Hasfuse
blown?
Isthere230V
acrosspins11&
12atstartup?
Isthere230V
acrosspins14&
Natstart up?
Are
electrical
connections
good?
NN
NNN
Y
D
o
e
s
m
a
i
n
B
u
r
n
e
r
L
i
g
h
t
?
Y
C
h
a
n
g
e
i
g
n
i
t
i
o
n
c
o
n
t
r
o
l
l
e
r
a
n
d
m
u
l
t
i
f
u
n
c
t
i
o
n
c
o
n
t
r
o
l
Replace
ignition
controller
D
o
e
s
b
u
r
n
e
r
p
r
e
s
s
u
r
e
i
n
c
r
e
a
s
e
?
H
a
s
i
g
n
i
t
e
r
s
t
o
p
p
e
d
s
p
a
r
k
i
n
g
?
A
r
e
ignite
r
l
e
a
d
termin
a
l
e
n
d
s
crack
e
d
o
r
bro
k
e
n
?
N
N
Y
Y
N
N
Y
Y
Are
electrical
connections
sound?
Areair
pressure
pipes
sound?
Y
Y
NN
Replacefuse
Replacecontrol
module
Re-sealpipesor
replaceif
necessary
Replace
fluefan
Press“RESET”
Replacecontrol
module
Replacecontrol
module
Isthere
230Vacross
pins
8& 9?
IsLED
Displaying
7?
Isigniter
leadcondition
good?
Isigniter
condition
good?
Y
Y
Y
C
h
a
n
g
e
i
g
n
i
t
i
o
n
c
o
n
t
r
o
l
l
e
r
N
N
N
Y
Replace
multifunction
control
Replace
igniterlead
Replaceigniter
N
N
Istheflue
thecorrect
length?
Hasorifice
beenused
correctly?
Y
Y
Changep
r
e
s
s
u
r
e
switch
Re-configure
flue
Referto
paragraph. 5
Y
Y
Y
Y
N
Set
thermostat
Water Circulator
Diagnostics Flowchart
NOTE: The circulator thermostat is factory set to provide a temperature range of 50oC to 82oC. The temperature is increased
by rotating the theromostat knob clockwise and temperature stop 2 MUST be left in position (see fig. 9a) if the
circulator is used in a direct application, ensuring a maximum temperature of 60oC. For indirect applications, remove
temperature stop 2.
In order to ensure that soundness of the heater is maintained, you MUST ensure that flow and return pipes into the
sealed compartment are sealed with the supplied grommets!
7.2 WATERCONNECTIONS:
Note: Both flow and return connections are Rp3/4(3/4in BSP female) connections.
IMPORTANT:Usecompressionfittingsattheapplianceflowand returnconnections andatthe airheater casingexit,tofacilitate
easyaccessto the circulatorbody.
7.2.1 Remove the fixing screws holding the sealing panel in place.
7.2.2 Carefully remove the sealing panel, such that access can be gained to the circulator compartment.
7.2.3 Side Exit: Knockouts/holes are provided in both sides of the heater cabinet for external pipe routing. Horizontal pipe
runs are to be kept to an absolute minimum.
7.2.4 TopExit:
A) Remove the plastic plugs from the air heater top panel and the fan chamber floor.
B) Pass the flow and return pipes (flow pipe to the rear) from below and then locate the pipes with the circulator body
connections. Fully tighten the connections to the main body before completing the connections to the top ends of
the Flow and Return pipes, ensuring that the pipework does not restrict access to the circulator thermostat phial
pocket or the air heater heat exchanger access panel.
NOTE: In order to maintain an air tight seal, the supplied grommets MUST be used where the flow and return pipes pass
through the upper sealing plate and diaphragm.
IMPORTANT:Ensurethatthefittingsonthecirculatorbodyarewellsupportedwhenmakingflowandreturnconnections.
7.2.5 Using good quality duct tape, seal around the Flow and Return pipes where they pass through the air heater top
panel and fan chamber floor.
10 19
Fig. 8
MultifunctionControl
(With Ignition Controller removed).
1. Inlet Pressure Test Point.
2. Outlet Pressure Test Point.
3. Burner Pressure Adjuster.
1
3
2
FanPerformanceCurve
150
0.07
mbar
0.50
0.375
R
e
s
i
s
t
a
n
c
e
E
x
t
e
r
n
a
l
t
o
H
e
a
t
e
r
0.25 0.10
0.125
Air Volume
0.05
0.20
0.15
in.wg.
200
0.09 250
0.12
300 ft /min
0.14m /sec
3
3
Fig.13
Economaire25FlowDiagram
1r
b
b
g/y
br
br
r
r
r
r
br
N
L
br
bbk
bbr
w
w
gy gy
gy
pk
w
w
v
yy
b
bk
br
b
bk
br
b
b
b
r
r
bk
w
bk
or
or
r
bk
bk
bk
bk
bk
bk
br
v
gy
pk
pk
g/y
g/y
pk
br
y
y
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
CONTROL MODULE
AIR
CIRCULATION
FAN
CLEANFLOW
FILTER
(OPTIONAL)
COMBUSTION
AIR FAN
AIR PROVING
SWITCH
FAN POWER
CAPACITOR
RESISTOR
TERMINAL
BLOCK
CLOCK
AIR
HEATER
SWITCH
WATER
HEATER
SWITCH
WATER HEATER
GAS CONTROL
(OPTIONAL)
WATER HEATER
THERMOSTAT
THERMISTA-STAT AIR HEATER
GAS CONTROL
COVER
COVER
WATER HEATER
OVERHEAT
LIMIT SWITCH
LIMIT SWITCH
FDC ASSEMBLY
AIR HEATER
IGNITION
ELECTRODE
WATER
HEATER
IGNITION
ELECTRODE
WIRE COLOUR CODE
black ------bk
blue -------b
brown -----br
grey -------gy
violet ------v
white ------w
red ---------r
pink --------pk
yellow------y
orange-----or
black/white-----bk/w
green/yellow ---g/y
WIRE COLOUR CODE
black ------bk
blue -------b
brown -----br
grey -------gy
violet ------v
white ------w
red ---------r
pink --------pk
yellow------y
orange-----or
black/white-----bk/w
green/yellow ---g/y
6.6 SAFETYCHECK:
In order to check the correct operation of the control module, run the heater for
a short period and introduce a fault condition by carrying out the following
sequence:
6.6.1 Check for gas soundness within the appliance.
6.6.3 Turn on both the gas and electrical supplies to the heater.
6.6.4 Set the “AIR HEATER” switch on the time control unit to “CONT”.
6.6.5 Light the ignition and main burners as described in section 6.3
6.6.6 Allow the heater to run for a period of 5 minutes to stabalise.
6.6.7 Turn off gas supply to heater at the heater Gas Cock. DO NOT TURN
OFFATGASMETER!
6.6.8 Having detected the fault condition, the module should cause the red
LED on the indicator panel to flash and the module will go through the
ignition sequence. Having detected the fault condition a second time,
the control module should cause the heater to go into lockout,
indicated by a constant red LED and the LED status indicator will show
“6”
6.6.9 Reinstate gas supply and wait for a minimum period of 10 seconds.
6.6.10 Depress the “RESET” button on the Indicator Panel.
6.6.11 The heater will go through its ignition procedure and the ignition and
mainburnersSHOULD ignite.
6.6.12 Set the “AIR HEATER” switch on the time control unit to “TIMED”
9
20
7. INTEJANCIRCULATOR
7.1 WATERCIRCULATIONSYSTEM.Detailedrecommendations forthewater circulationsystem aregivenin BS6798,BS5449
(for small bore and microbore central heating systems), and BS5446. The maximum water side operating pressure (PMS) is
1bar.
7.1.1 To ensure good circulation in gravity circuits, flow pipes should be designed to run vertically from the water heater
before running laterally. Any lateral run should be less than 2 x the previous vertical run. Pipework should be installed
with a rise towards the vent point. In systems with poor circulation, a pump kit is also available.
7.1.2 Drain cocks must be located in accessible positions that permit the draining of the whole system, including the
appliance and hot water storage vessel. A drain cock should be fitted at the lowest point of the water heating circuit
and, in the case of an indirect system, another must be fitted at the lowest point of the cold feed. Drain cocks should
be at least 1/2in nominal size and be in accordance with BS2879.
7.1.3 Economy valves can only be used in a DIRECT installation.

Other manuals for ECONOMAIRE 25

1

This manual suits for next models

3

Other Johnson & Starley Heater manuals

Johnson & Starley HI-SPEC J25RS Series User guide

Johnson & Starley

Johnson & Starley HI-SPEC J25RS Series User guide

Johnson & Starley SCE 75-75 G Guide

Johnson & Starley

Johnson & Starley SCE 75-75 G Guide

Johnson & Starley AQUAIR S-25 User guide

Johnson & Starley

Johnson & Starley AQUAIR S-25 User guide

Johnson & Starley WARMCAIR C26D User guide

Johnson & Starley

Johnson & Starley WARMCAIR C26D User guide

Johnson & Starley HI-SPEC J90 User guide

Johnson & Starley

Johnson & Starley HI-SPEC J90 User guide

Johnson & Starley JB25P MK 5 User guide

Johnson & Starley

Johnson & Starley JB25P MK 5 User guide

Johnson & Starley JU156 User guide

Johnson & Starley

Johnson & Starley JU156 User guide

Johnson & Starley Economaire 31 User guide

Johnson & Starley

Johnson & Starley Economaire 31 User guide

Johnson & Starley ECONOMAIRE 90 User guide

Johnson & Starley

Johnson & Starley ECONOMAIRE 90 User guide

Johnson & Starley HI-SPEC J25 User guide

Johnson & Starley

Johnson & Starley HI-SPEC J25 User guide

Johnson & Starley HI-SPEC J65 User guide

Johnson & Starley

Johnson & Starley HI-SPEC J65 User guide

Johnson & Starley ECONOMAIRE 25 User manual

Johnson & Starley

Johnson & Starley ECONOMAIRE 25 User manual

Johnson & Starley JANSTAR Mk 2 User guide

Johnson & Starley

Johnson & Starley JANSTAR Mk 2 User guide

Johnson & Starley ECONOMAIRE 32/INTEJAN User guide

Johnson & Starley

Johnson & Starley ECONOMAIRE 32/INTEJAN User guide

Johnson & Starley HI-SPEC J50P User guide

Johnson & Starley

Johnson & Starley HI-SPEC J50P User guide

Johnson & Starley ECONOMAIRE 32 User guide

Johnson & Starley

Johnson & Starley ECONOMAIRE 32 User guide

Johnson & Starley WARMCAIR C10DW User manual

Johnson & Starley

Johnson & Starley WARMCAIR C10DW User manual

Johnson & Starley WARMCAIR C10D User manual

Johnson & Starley

Johnson & Starley WARMCAIR C10D User manual

Johnson & Starley HI-SPEC J25SCA User manual

Johnson & Starley

Johnson & Starley HI-SPEC J25SCA User manual

Johnson & Starley HI-SPEC J50 User guide

Johnson & Starley

Johnson & Starley HI-SPEC J50 User guide

Johnson & Starley JANSTAR User guide

Johnson & Starley

Johnson & Starley JANSTAR User guide

Johnson & Starley HI-SPEC J40 User guide

Johnson & Starley

Johnson & Starley HI-SPEC J40 User guide

Johnson & Starley HI-SPEC J40 User guide

Johnson & Starley

Johnson & Starley HI-SPEC J40 User guide

Johnson & Starley HI-SPEC J32P User guide

Johnson & Starley

Johnson & Starley HI-SPEC J32P User guide

Popular Heater manuals by other brands

Zibro SRE 188 E operating manual

Zibro

Zibro SRE 188 E operating manual

TylöHelo Pro Series Installation and operating instructions

TylöHelo

TylöHelo Pro Series Installation and operating instructions

CORONA XL-DK operating instructions

CORONA

CORONA XL-DK operating instructions

FUAVE Kopenhagen 2000 user manual

FUAVE

FUAVE Kopenhagen 2000 user manual

Tylo SENSE COMBI Pure user guide

Tylo

Tylo SENSE COMBI Pure user guide

Orion ORCH-010 instruction manual

Orion

Orion ORCH-010 instruction manual

DeLonghi HCX Series Instructions for use

DeLonghi

DeLonghi HCX Series Instructions for use

Rowenta CLASSIC manual

Rowenta

Rowenta CLASSIC manual

Rinnai Energysaver RHFE-1004FTR How to use

Rinnai

Rinnai Energysaver RHFE-1004FTR How to use

Orbegozo CR 5017 instruction manual

Orbegozo

Orbegozo CR 5017 instruction manual

Toyotomi zibro LC-400 operating manual

Toyotomi

Toyotomi zibro LC-400 operating manual

Tylo COMPACT 2/4 Installation and operating instructions

Tylo

Tylo COMPACT 2/4 Installation and operating instructions

Clarke IRD20 Operation & maintenance instructions

Clarke

Clarke IRD20 Operation & maintenance instructions

Frico Infrapalm IHPA Assembly and operating instructions

Frico

Frico Infrapalm IHPA Assembly and operating instructions

Goldair Platinum GPPH610 operating instructions

Goldair

Goldair Platinum GPPH610 operating instructions

Twin-Star International Duraflame 9HM7000 manual

Twin-Star International

Twin-Star International Duraflame 9HM7000 manual

Sandstrom S20TFH19E instruction manual

Sandstrom

Sandstrom S20TFH19E instruction manual

Myson Kickspace 500 manual 

Myson

Myson Kickspace 500 manual 

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.