E-Link Gateway Installation Instructions10
Table 9: BAS Output Protocol Quick Start Selections
APP Group
Switch B Output Protocol Quick Starts
SwitchSettings 8421Port1 Port3 Port4
0 1
1. When making edits to User Report 4 (Port Configuration), Group Application Switch B must be set to zero. This setting
ensures that the edits are stored. Otherwise, the edits are overwritten to the default values assigned to the particular Group
Switch B setting the next time E-Link is reset, or power is cycled. Edits made in any other User Reports do not require
alterations to either bank of Group Application switches. For standard set-up, not requiring modifications via User Report 4,
use application switch B, settings 1 to 14.
0000MS/TP,AUTO,N,8,1 Modbus,19,200,N,8,1 Terminal
1 2, 5
2. The Terminal setting on Port 4 is restricted for factory use only.
To comply with the LONMARK® specification, all data transmitted on the LONWORKS network must be expressed in SI units
(metric units). The LONWORKS ProtoCessor performs no unit conversions; it assumes that the data supplied is already
correctly expressed.
0001MS/TP,AUTO,N,8,1 Modbus,19,200,N,8,1 Terminal
2 2, 5 0010MS/TP,AUTO,N,8,1 Modbus,19,200,N,8,2 Terminal
3 2, 5 0011MS/TP,AUTO,N,8,1 N2,9,600,N,8,1 Terminal
4 2, 5 0100N2,9,600,N,8,1 MS/TP,38,400,N,8,1 Terminal
5 2, 5 0101Modbus, 19,200, N, 8, 1 MS/TP, 38,400, N, 8, 1 Terminal
6 2, 5 0110Modbus, 19,200, N, 8, 2 MS/TP, 38,400, N, 8, 1 Terminal
7 2, 5 0111Modbus, 9,600, E, 8, 1 MS/TP, 38,400, N, 8, 1 Terminal
8 2, 5 1000Modbus, 9,600, N, 8, 1 MS/TP, 38,400, N, 8, 1 Terminal
93, 5, 6
3. Use Quick Start 9 and 11 if the equipment is supplying the data in SI units (the E-Link is not required to perform any
conversions, so it operates in pass-through mode).
1001N2,9,600,N,8,1 Modbus,19,200,N,8,1 L
ONWORKS – Pass through
10 4, 5, 6
4. Use Quick Start 10 and 12 if the equipment is supplying the data in Imperial units and the E-Link is required to convert these
units into SI.
5. Setting Switch T = ON, on the MAC address, forces TERMINAL mode of Port 3, at 57,600 baud, N, 8, 1. This setting is only
required to debug the E-Link Gateway’s operation, or access the User Reports.
6. Select Quick Starts 9 and 10 when connecting the E-Link Gateway to an ECO2 unit.
1010N2,9,600,N,8,1 Modbus,19,200,N,8,1 L
ONWORKS – Conversion
11 3, 5 1011Modbus, 19,200, N, 8, 2 N2, 9,600, N, 8, 1 LONWORKS – Pass through
12 4, 5 1100Modbus, 19,200, N, 8, 2 N2, 9,600, N, 8, 1 LONWORKS – Conversion
13 2, 5 1101Modbus, 9,600, E, 8, 1 Modbus, 19,200, N, 8, 2 Terminal
14 2, 5 1110MS/TP,38,400,N,8,1 N2,9,600,N,8,1 Terminal
15 7
7. Quick Starts 15 on APP Group B, and 63 on APP Group A, are reserved for field adjustments.
1111Reserved Reserved Terminal