manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Johnson Controls
  6. •
  7. Irrigation System
  8. •
  9. Johnson Controls tyco TY1234 User manual

Johnson Controls tyco TY1234 User manual

RAPID RESPONSE Series LFII Residential Sprinklers
3.0 K-factor Pendent
Wet Pipe Systems
Page 1 of 4 DECEMBER 2018 TFP402
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Number (SIN)
T Y12 34
General
Description
The TYCO RAPID RESPONSE Series
LFII Residential Pendent Sprinklers
(TY1234) are decorative, fast response,
frangible bulb sprinklers designed for
use in residential occupancies such as
homes, apartments, dormitories, and
hotels. When aesthetics and optimized
flow characteristics are key consider-
ations, the Series LFII (TY1234) should
be the first choice.
The 3.0 K-factor of the Series LFII Res-
idential Pendent Sprinkler has been
designed to optimize flows (that is, to
avoid over discharging) specifically
for small coverage areas up to 14 ft x
14 ft (4,3 m x 4,3 m). The required resi-
dential flow rates can then be delivered
with the use of smaller pipe sizes and
reduced water supply requirements.
The Series LFII Residential Sprinklers
are intended for use in the following
scenarios:
•
wet pipe residential sprinkler
systems for one-and two-family
dwellings and mobile homes per
NFPA 13D
•
wet pipe residential sprinkler
systems for residential occupan-
cies up to and including four stories
in height per NFPA 13R
•
wet pipe sprinkler systems for
the residential portions of any
occupancy per NFPA 13
The recessed version of the Series
LFII Residential Pendent Sprinkler is
intended for use in areas with finished
ceilings. It employs a two-piece Style
20 Recessed Escutcheon.
The Recessed Escutcheon provides
1/4 in. (6,4 mm) of recessed adjust-
ment or up to 1/2 in. (12,7 mm) of total
adjustment from the flush ceiling posi-
tion. The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the pipe drops to
the sprinklers must be cut.
The Series LFII Residential Pendent
Sprinkler has been designed with heat
sensitivity and water distribution char-
acteristics proven to help in the control
of residential fires and to improve the
chance for occupants to escape or be
evacuated.
Corrosion-resistant coatings, where
applicable, are utilized to extend the life
of copper alloy sprinklers beyond that
which would otherwise be obtained
when exposed to corrosive atmo-
spheres. Although corrosion-resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable Approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
NOTICE
The Series LFII Residential Pendent
Sprinklers (TY1234) described herein
must be installed and maintained in
compliance with this document and
with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION (NFPA), in addition to the
standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
TFP402
Page 2 of 4
Technical
Data
Approvals
UL Listed (for use with wet pipe and dry
pipe systems)
C-UL Listed (for use only with wet pipe
systems)
Certified to all requirements of
NSF/ANSI 61
Note: Sprinklers with a polyester finish
are UL Listed as corrosion-resistant
sprinklers.
See the Design Criteria section for details
on these approvals.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=3.0 GPM/psi½(43,2 LPM/bar½)
Temperature Rating
155°F (68°C) or 175°F (79°C)
Finishes
Natural Brass, Signal White Polyester
Coated, or Chrome Plated
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Sealing Assembly ..Beryllium Nickel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . .3 mm Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The TYCO RAPID RESPONSE Series
LFII Residential Pendent Sprinklers
(TY1234) are UL and C-UL Listed for
installation in accordance with the fol-
lowing criteria.
SURFACE
ESCUTCHEON
PLATE SEATING
1-9/16"
(39,7 mm)
-
2
Button
Temperature
rating is
indicated on
Deector.
Deector
Compression
Screw
Bulb
Sealing Assembly
-
6
*
-
4
5
-
3
-
*
*
6
4
5
1
3
2
Components:
Frame
1
-
1/2"
NPT
7/16" (11,1 mm)
MAKE-IN
NOMINAL
ESCUTCHEON
STYLE 20
RECESSED
WRENCH
(55,6 mm)
2-3/16"
FLATS
(73,0 mm)
2-7/8" DIA.
Insert
7
-
7
CROSS SECTION PENDENT RECESSED PENDENT
TY1234
2-7/8" DIA.
(73,0 mm)
(57,2 mm)
2-1/4" DIA.
MOUNTING
SPRINKLER
CLOSURE
SURFACE
FITTING
FACE OF
(11,1±3,2 mm)
7/16±1/8"
MOUNTING
PLATE
1-3/8" (34,9 mm)
1-1/8" (28,6 mm)
(3,2 mm)
1/8"
1/2" (12,7 mm)
1/4" (6,4 mm)
WRENCH RECESS
(END "A" USED
FOR TY1234)
RECESS
WRENCH
WITH SPRINKLER
ENGAGEMENT
IN TO ENSURE
WRENCHING AREA
PUSH WRENCH
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
PENDENT AND RECESSED PENDENT SPRINKLERS (TY1234)
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE
RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER
(TY1234)
FIGURE 3
W-T YPE 6
SPRINKLER WRENCH
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFP402
Page 3 of 4
Installation
The TYCO RAPID RESPONSE Series
LFII Residential Pendent Sprinklers
(TY1234) must be installed in accor-
dance with this section:
General Instructions
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm).
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 7 to 14
lb-ft (9,5 to 19,0 N∙m). Higher levels
of torque can distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutch-
eon Plate by under-or over-tightening
the Sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Residential Sprinkler Design Guide
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Pendent Sprinkler
Design Guide TFP490 for the manufac-
turer’s recommendations that may be
acceptable to the local authority having
jurisdiction.
System Type
Only wet pipe systems may be utilized.
Ceiling Types
Smooth flat horizontal, or beamed, or
sloped, in accordance with the 2013
Edition of NFPA 13D, 13R, or 13 as
applicable.
Hydraulic Design
(NFPA 13D and 13R)
The minimum required sprinkler
flow rate for systems designed to
NFPA 13D or NFPA 13R are given in
Table A as a function of temperature
rating and the maximum allowable cov-
erage areas. The sprinkler flow rate is
the minimum required discharge from
each of the total number of design
sprinklers as specified in NFPA 13D or
NFPA 13R.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
•
The ow rates given in Table A for
NFPA 13D and 13R as a function of
TFP402 temperature rating and the
maximum allowable coverage area.
•
A minimum discharge of 0.1
gpm/ft2over the “design area”
comprised of the four most hydrau-
lically demanding sprinklers for
actual coverage areas protected by
the four sprinklers.
Obstruction to Water Distribution
Sprinklers are to be located in accor-
dance with the obstruction rules of
NFPA 13D, 13R, and 13 as applica-
ble for residential sprinklers as well as
with the obstruction criteria described
within the TYCO technical data sheet
TFP490.
Operational Sensitivity
Sprinklers are to be installed with
a deflector-to-ceiling distance of
1-1/4 in. to 4 in.
Sprinkler Spacing
The minimum spacing between sprin-
klers is 8 ft (2,4 m). The maximum
spacing between sprinklers cannot
exceed the length of the coverage
area being hydraulically calculated
(for example a maximum of 12 ft for a
12 ft x 12 ft coverage area, or 16 ft for a
16 ft x 16 ft coverage area.) See Table
A.
Max.
Coverage
Area (a)
ft x ft
(m x m)
WET PIPE SYSTEM
Minimum Flow and Residual Pressure (b, c)
Ordinary Temp. Rating
155°F (68°C) Intermediate Temp. Rating
175°F (79°C) Deflector to
Ceiling Installation
Type
Minimum
Spacing
ft
(m)
Flow
GPM
(L/min)
Pressure
PSI
(bar)
Flow
GPM
(L/min)
Pressure
PSI
(bar)
12 x 12
(3,7 x 3,7)
8
(30,3)
7.1
(0,49)
8
(30,3)
7.1
(0,49) Smooth
Ceilings
1-1/4 in. to 4 in.
Beamed
Ceilings per
NFPA 13D
or 13R
1-1/4 in. to
1-3/4 in. below
bottom of
beam.
Recessed
using Style 20
Escutcheon or
non-recessed
per NFPA 13D,
13R, or 13
8
(2,4)
14 x 14
(4,3 x 4,3)
11
(41,6)
13.4
(0,92)
11
(41,6)
13,4
(0,92)
15 x 15
(4,6 x 4,6)
12
(45,4)
16
(1,10)
12
(45,4)
16
(1,10)
16 x 16
(4,9 x 4,9)
13
(49,2)
18.8
(1,29)
13
(49,2)
18.8
(1,29)
18 x 18
(5,5 x 5,5)
17
(64,3)
32,1
(2,21)
18
(68,1)
36.0
(2,48)
Notes:
a. For coverage area dimensions less than or between those indicated, use the minimum required ow for the next highest coverage area for which
hydraulic design criteria are stated.
b. Requirement is based on minimum ow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal
K-factor. See Hydraulic Design under the Design Criteria section.
c. For NFPA 13 residential applications, the greater of 0.1 gpm/ft2over the design area or the ow in accordance with the criteria in this table must be
used.
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY1234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
TFP402
Page 4 of 4
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
LOCTITE is a registered trademark of Henkel Corporation;
TEFLON is a registered trademark of DuPont
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assembly
Specify: Series LFII (TY1234), K=3.0,
Residential Pendent Sprinkler, (specify)
temperature rating, (specify) finish, and
P/N (specify):
155°F (68°C)
Natural Brass .................51- 010-1-155
Signal White (RAL 9003)
Polyester1....................51-010-4-155
Chrome Plated ................51- 0 10 - 9 -15 5
175°F (79°C)
Natural Brass .................51- 010 -1-175
Signal White (RAL 9003)
Polyester1....................51- 010-4-175
Chrome Plated ................51-010 - 9 -175
1. UL Listed as corrosion-resistant.
Recessed Escutcheon
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, and P/N
(specify*)
*Refer to Technical Data Sheet TFP770.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench
for use with Series LFII Pendent Sprin-
klers, P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench for
use with Series LFII Recessed Pendent
Sprinklers, P/N 56-850-4-001
Series LFII Residential Pendent
Sprinklers
The Series LFII Residential Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. Install pendent sprinklers in the
pendent position with the deflector par-
allel to the ceiling.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Wrench-tighten the sprinkler
into the sprinkler fitting using only the
W-Type 6 Sprinkler Wrench (Figure
3). With reference to Figure 1, apply
the W-Type 6 Sprinkler Wrench to the
wrench flats.
Series LFII Residential Recessed
Pendent Sprinklers
The Series LFII Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. Install recessed pendent sprin-
klers in the pendent position with the
deflector parallel to the ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step C. Wrench-tighten the sprinkler
into the sprinkler fitting using only the
W-Type 7 Recessed Sprinkler Wrench
(Figure 4). With reference to Figure 1,
apply the W-Type 7 Recessed Sprinkler
Wrench to the sprinkler wrench flats.
Step D. After installing the ceiling
applying the finish coat, slide on the
Style 20 Closure over the Series LFII
Sprinkler and push the Closure over the
Mounting Plate until the flange comes
in contact with the ceiling.
Care and
Maintenance
The TYCO RAPID RESPONSE Series
LFII Residential Pendent Sprinklers
(TY1234) must be maintained and ser-
viced in accordance with this section:
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this decision.
Absence of the outer piece of an
escutcheon,which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather-duster. Otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. See the Installation
section for additional information.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, for example, NFPA 25,
in addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.

This manual suits for next models

1

Other Johnson Controls Irrigation System manuals

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls tyco WS User manual

Johnson Controls

Johnson Controls tyco WS User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco AQUAMIST ULF AM29 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM29 User manual

Johnson Controls tyco ESFR-25 User manual

Johnson Controls

Johnson Controls tyco ESFR-25 User manual

Johnson Controls tyco RAVEN User manual

Johnson Controls

Johnson Controls tyco RAVEN User manual

Johnson Controls tyco CC3 User manual

Johnson Controls

Johnson Controls tyco CC3 User manual

Johnson Controls tyco DSB-2 User manual

Johnson Controls

Johnson Controls tyco DSB-2 User manual

Johnson Controls tyco AQUAMIST ULF AM15 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM15 User manual

Johnson Controls tyco ESFR-17 User manual

Johnson Controls

Johnson Controls tyco ESFR-17 User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco ESFR-34 User manual

Johnson Controls

Johnson Controls tyco ESFR-34 User manual

Johnson Controls Tyco TY720 User manual

Johnson Controls

Johnson Controls Tyco TY720 User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco ULTRA K17 User manual

Johnson Controls

Johnson Controls tyco ULTRA K17 User manual

Johnson Controls tyco EC-8 Series User manual

Johnson Controls

Johnson Controls tyco EC-8 Series User manual

Johnson Controls MS1 Manual

Johnson Controls

Johnson Controls MS1 Manual

Johnson Controls tyco DS-1 Series User manual

Johnson Controls

Johnson Controls tyco DS-1 Series User manual

Johnson Controls tyco AQUAMIST IFP User manual

Johnson Controls

Johnson Controls tyco AQUAMIST IFP User manual

Johnson Controls tyco AQUAMIST ULF AM33 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM33 User manual

Johnson Controls tyco DS-1 Series User manual

Johnson Controls

Johnson Controls tyco DS-1 Series User manual

Johnson Controls Tyco TY3201 User manual

Johnson Controls

Johnson Controls Tyco TY3201 User manual

Johnson Controls SABROE NS-HPAC User manual

Johnson Controls

Johnson Controls SABROE NS-HPAC User manual

Popular Irrigation System manuals by other brands

Viking VK502 Technical data

Viking

Viking VK502 Technical data

Eden 94152EDAMZ quick start guide

Eden

Eden 94152EDAMZ quick start guide

Metabo Dry-running Sensor Hydrostop operating instructions

Metabo

Metabo Dry-running Sensor Hydrostop operating instructions

Senju Sprinkler CN-RES quick start guide

Senju Sprinkler

Senju Sprinkler CN-RES quick start guide

Gardena smart Sensor 19040 manual

Gardena

Gardena smart Sensor 19040 manual

Kärcher HKF 50 E manual

Kärcher

Kärcher HKF 50 E manual

Viking VK2022 Technical data

Viking

Viking VK2022 Technical data

Tyco TY-FRB Series manual

Tyco

Tyco TY-FRB Series manual

IrriGreen 2 Quick install guide

IrriGreen

IrriGreen 2 Quick install guide

Tyco AM11 manual

Tyco

Tyco AM11 manual

Holman co1606 user guide

Holman

Holman co1606 user guide

Rivulis D515-12-430 manual

Rivulis

Rivulis D515-12-430 manual

Viking MIRAGE VK465 Technical data

Viking

Viking MIRAGE VK465 Technical data

Reliable F156 Series Bulletin

Reliable

Reliable F156 Series Bulletin

Viking FREEDOM VK460 Technical data

Viking

Viking FREEDOM VK460 Technical data

Viking VK4611 Technical data

Viking

Viking VK4611 Technical data

Viking VK192 Technical data

Viking

Viking VK192 Technical data

Fiskars 1023656 Original instructions

Fiskars

Fiskars 1023656 Original instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.