Model CHEC—8.0 K-factor
Concealed Horizontal Extended Coverage
Quick Response Light Hazard, Sidewall Sprinklers
Page 1 of 4 AUGUST 2018 TFP265
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Model CHEC 8.0 K-factor,
Concealed Horizontal Extended Cov-
erage Quick Response Light Hazard,
Sidewall Sprinklers are decorative,
3 mm bulb type sprinklers featuring a
unique cover plate designed to conceal
the sprinkler. It is the best choice for
architecturally sensitive areas such as
dormitories, hotel rooms, reception
areas, office buildings, banquet facili-
ties, conference rooms, and hospitals.
The soft contour of the cover plate opti-
mizes a low profile while blending in
with surrounding surfaces. The plate,
while maintaining a fast response sen-
sitivity has been specifically designed
without vent holes to increase its aes-
thetic appeal while helping to avoid
objects from being hung from the sprin-
kler, such as garment bags and clothes
hangers, that might otherwise cause an
inadvertent operation.
They are designed for installation
along a wall or the side of a beam and
beneath a smooth and level ceiling.
Horizontal sidewall sprinklers are com-
monly used in lieu of pendent or upright
sprinklers because of aesthetics or
building construction considerations
where piping across the ceiling is not
desirable.
They are intended for use in auto-
matic sprinkler systems designed in
accordance with standard installation
rules, for example NFPA 13, for light
hazard occupancies. The fast response
thermal sensitivity rating of the Model
CHEC Sprinklers provides for a quick
response extended coverage rating up
to a 16 ft x 16 ft coverage area.
Each unit includes a Cover Plate
Assembly that conceals the sprinkler
operating components. The sepa-
rable two-piece design of the Cover
Plate and Support Cup Assemblies
allows installation of the sprinklers and
pressure testing of the fire protection
system prior to the installation of the
wall or application of a finish coating.
Also, the separable “push-on and
thread-off” two-piece design of the
sprinkler provides for 1/2 in. (12,7 mm)
of horizontal adjustment.
The Model CHEC Sprinklers are
shipped with a Protective Cap. The
Protective Cap is temporarily removed
for installation, and it must be replaced
to help protect the sprinkler while the
wall is being plastered, wallpapered,
or painted. When the wall installation
is complete the Protective Cap must be
removed and the Cover Plate Assembly
installed. The Protective Cap must be
removed to ensure proper performance
of the sprinklers.
NOTICE
The TYCO Model CHEC 8.0 K-factor,
Concealed Horizontal Extended Cov-
erage Quick Response Light Hazard,
Sidewall Sprinklers described herein
must be installed and maintained in
compliance with this document and
with the applicable standards of the
National Fire Protection Association, in
addition to the standards of any author-
ities having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number
T Y43 32
Technical
Data
Approvals
UL and C-UL Listed
NYC Approved under MEA 177-03-E
Note: The listings apply only to the service
conditions indicated in the Design Criteria
section.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=8.0 GPM/psi½(115,2 LPM/bar½)
Temperature Rating
155°F (68°C) Sprinkler with
139°F (59°C) Cover Plate
Horizontal Adjustment
1/2 in. (12,7 mm)
Finishes
Refer to the Ordering Procedure section
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button Spring . . . . . . . . . . . . . . . Stainless Steel
Sealing Assembly ..Beryllium Nickel w/TEFLON
Bulb, 3 mm Diameter Glass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Support Cup . . . . . . . . . . . . . . . . . . . . . . . . Steel
Retainer. . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Cover Plate . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Cover Plate Ejection Spring . . . . Stainless Steel
TFP265
Page 2 of 4
Operation
When exposed to heat from a fire, the
Cover Plate, which is soldered to the
Retainer at three points, falls away
to expose the Sprinkler Assembly.
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, activating the sprinkler and
allowing water to flow.
Design
Criteria
The TYCO Model CHEC 8.0 K-factor,
Concealed Horizontal Extended Cov-
erage Quick Response Light Hazard,
Sidewall Sprinklers are UL and C-UL
Listed for use in light hazard occupan-
cies, using the design criteria in Table
A, in addition to the requirements
specified in the current NFPA 13 for
extended coverage sidewall sprinklers.
The Model CHEC Sprinklers are only
listed and approved with the Model
CHEC Cover Plates having a factory
applied finish.
Response
Rating
Coverage
Area1
Ft x Ft (m x m)
Minimum
Flow2
GPM (LPM)
Minimum
Pressure2
PSI (bar)
Deflector-To-Ceiling
Distance3
In. (mm)
Sprinkler
Temperature
Rating, °F
Lateral
Minimum
Spacing4
Ft. (m)
Quick 16 × 14 (4,9 × 4,3) 26 (98) 10.6 (0,73) 4 to 12 (100 to 300) 155 10 (3,1)
Quick 16 × 16 (4,9 × 4,9) 26 (98) 10.6 (0,73) 4 to 12 (100 to 300) 155 10 (3,1)
NOTES
1. Backwall (where sprinkler is located) by sidewall (length of throw).
2. Requirement is based on minimum ow in GPM from each sprinkler. The indicated residual pressures are based on the nominal K-factor.
3. The centerline of the sprinkler waterway is located 7/16 in. (11,1 mm) below the deector (Ref. Figure 2).
4. Minimum spacing is for lateral distance between sprinklers located along a single wall. Otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an
opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.
TOP
SPRINKLER/SUPPORT CUP
ASSEMBLY
COVER PLATE/RETAINER
ASSEMBLY
BUTTON
3/4" NPT
BULB
FRAME DEFLECTOR
COMPRESSION
SCREW
SUPPORT CUP
WITH ROLL FORMED
THREADS
SEALING
ASSEMBLY
RETAINER
WITH THREAD
DIMPLES
SOLDER
TABS (3)
COVER
PLATE
WRENCH
FLATS
COVER PLATE
EJECTION
SPRING
BUTTON
EJECTION
SPRING
PUSH INTO
SUPPORT CUP
UNTIL RETAINER
FLANGE IS FLUSH
WITH MOUNTING
SURFACE
DISPOSABLE
SPRINKLER
STRAP (SEE
INSTALLATION
SECTION)
FIGURE 1
MODEL CHEC CONCEALED HORIZONTAL EXTENDED COVERAGE
QUICK RESPONSE LIGHT HAZARD SIDEWALL SPRINKLER
TABLE A
UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA
TFP265
Page 3 of 4
Installation
The TYCO Model CHEC 8.0 K-factor,
Concealed Horizontal Extended Cov-
erage Quick Response Light Hazard,
Sidewall Sprinklers must be installed in
accordance with this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm).
A 3/4 in. NPT sprinkler joint should be
obtained with a minimum to maximum
torque of 10 to 20 lb-ft (13,4 to
26,8 N·m). Higher levels of torque may
distort the sprinkler inlet with conse-
quent leakage or impairment of the
sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Sprinkler
Assembly by under-or over-tightening
the Sprinkler/Support Cup Assembly.
Readjust the position of the sprinkler
fitting to suit.
To install the Model CHEC Sprinklers,
complete the following steps:
Step 1. The sprinkler must only be
installed with its centerline perpen-
dicular to the back wall and parallel to
the ceiling. Face the word “Top” on the
deflector towards the ceiling.
Step 2. Remove the Protective Cap.
NOTICE
Do not remove the Sprinkler Strap
(Figure 1) until the sprinkler system is
to be placed in service.
Step 3. With pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 4. Wrench tighten the sprinkler
using only the W-Type 7 Wrench (Ref.
Figure 3). With reference to Figures 1
and 2, apply the wrench recess of the
W-Type 7 Wrench to the Sprinkler Flats.
Step 5. With reference to Figure 4,
replace the Protective Cap by pushing
it inwards until it bottoms out against
the Support Cup.
Note: The Protective Cap helps prevent
damage to the Sprinkler while the wall
is being plastered, wallpapered, or
painted.
COVER PLATE
RETAINER
ASSEMBLY
SPRINKLER
SUPPORT CUP
ASSEMBLY
MANUFACTURER
PRESET GAP
5/32" (4,0 mm)
2-3/8" to 2-5/8" DIA.
(60,3 to 66,7 mm)
1/2" (12,7 mm)
THREADED
ADJUSTMENT
FACE OF
SPRINKLER
FITTING
7/8" to 1-3/8"
(22,2 to 34,9 mm)
RETAINER
FLANGE
MOUNTING
SURFACE
1-11/16"
(42,9 mm)
1-3/4"
(44,5 mm)
3-5/16" DIA.
(84,1 mm)
CENTERLINE
OF SPRINKLER
WATERWAY
7/16"
(11,1 mm)
TOP OF
DEFLECTOR
9/16"
(14,3 mm)
WRENCH
FLATS
FIGURE 2
MODEL CHEC CONCEALED HORIZONTAL EXTENDED COVERAGE
QUICK RESPONSE LIGHT HAZARD SIDEWALL SPRINKLER
INSTALLATION DIMENSIONS
TFP265
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Factory painted Cover Plates must not
be repainted. They should be replaced,
if necessary, by factory painted
units. Non-factory applied paint may
adversely delay or prevent sprinkler
operation in the event of a fire.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied or over heated sprinklers must be
replaced.
Care must be exercised to avoid
damage to the sprinklers -before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section).
If a sprinkler must be removed, do not
reinstall it or a replacement without
reinstalling the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it
immediately.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assembly
Specify: Model CHEC, 8.0 K-factor,
Concealed Horizontal Extended Cov-
erage Quick Response Light Hazard,
Sidewall Sprinkler, 155°F (68°C),
P/N 51-396-1-155
Separately Ordered Cover Plate
Specify: 139°F (59°C) Model CHEC
Cover Plate Assembly with Specify
Finish, P/N (specify):
Pure White (RAL 9010)* . . . . . . . . .56-396-3-135
Signal White (RAL 9003) . . . . . . . .56-396-4-135
Chrome......................56-396-9-135
Custom......................56-396-X-135
* Eastern Hemisphere sales only.
Sprinkler Wrench
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
NOTICE
As long as the Sprinkler Strap (Figure 1)
or the Protective Cap (Figure 4) remains
in place, the system is considered to be
“Out of Service”.
Step 6. After the wall has been com-
pleted with the nominal 2-1/2 in. (63,5
mm) diameter mounting hole and in
preparation for installing the Cover
Plate Assembly, remove and discard
the Protective Cap and the Sprin-
kler Strap. If the Sprinkler has been
damaged in any way including acciden-
tal over spray from finishing the wall,
replace the entire Sprinkler/Support
Cup Assembly.
NOTICE
Refer to Technical Data Sheet TFP700
regarding instructions for the removal
of the Sprinkler Strap.
Step 7. Push the Cover Plate/Retainer
Assembly into the Support Cup, and as
necessary, make the final adjustment
of the Cover Plate with respect to the
wall by turning the Cover Plate/Retainer
Assembly clockwise until its flange just
comes in contact with the wall.
If it becomes necessary to remove
the Cover Plate, it can be removed
by unscrewing in a counter-clockwise
direction.
If the Cover Plate/Retainer Assembly
cannot be engaged with the Support
Cup or the Cover Plate/Retainer
Assembly cannot be engaged suffi-
ciently to contact the wall, the Sprin-
kler Fitting must be repositioned.
Care and
Maintenance
The TYCO Model CHEC 8.0 K-factor,
Concealed Horizontal Extended Cov-
erage Quick Response Light Hazard,
Sidewall Sprinklers must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national codes.
When properly installed, there is a
nominal 5/32 in. (4,0 mm) air gap
between the lip of the Cover Plate and
the wall, as shown in Figure 2. This
air gap is necessary for proper oper-
ation of the sprinkler. If the wall is to
be repainted after the installation of
the Sprinkler, care must be exercised
to ensure that the new paint does not
seal off any of the air gap.
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
CAP
PROTECTIVE
FIGURE 3
W-TYPE 7 SPRINKLER
WRENCH
FIGURE 4
DISPOSABLE PROTECTIVE
CAP

This manual suits for next models

1

Other Johnson Controls Irrigation System manuals

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls CDS-2000 User manual

Johnson Controls

Johnson Controls CDS-2000 User manual

Johnson Controls tyco ULTRA K17 User manual

Johnson Controls

Johnson Controls tyco ULTRA K17 User manual

Johnson Controls tyco TY3596 User manual

Johnson Controls

Johnson Controls tyco TY3596 User manual

Johnson Controls MS1 Manual

Johnson Controls

Johnson Controls MS1 Manual

Johnson Controls tyco AQUAMIST ULF AM33 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM33 User manual

Johnson Controls tyco ILLUSION User manual

Johnson Controls

Johnson Controls tyco ILLUSION User manual

Johnson Controls tyco RFII User manual

Johnson Controls

Johnson Controls tyco RFII User manual

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls JWS-3 User manual

Johnson Controls

Johnson Controls JWS-3 User manual

Johnson Controls Tyco AQUAMIST AM31 User manual

Johnson Controls

Johnson Controls Tyco AQUAMIST AM31 User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco CC3 User manual

Johnson Controls

Johnson Controls tyco CC3 User manual

Johnson Controls tyco ESFR-17 User manual

Johnson Controls

Johnson Controls tyco ESFR-17 User manual

Johnson Controls tyco AQUAMIST ULF AM15 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM15 User manual

Johnson Controls tyco EC-25 User manual

Johnson Controls

Johnson Controls tyco EC-25 User manual

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls tyco TY3334 User manual

Johnson Controls

Johnson Controls tyco TY3334 User manual

Johnson Controls tyco AQUAMIST ULF AM29 User manual

Johnson Controls

Johnson Controls tyco AQUAMIST ULF AM29 User manual

Johnson Controls tyco WS User manual

Johnson Controls

Johnson Controls tyco WS User manual

Johnson Controls tyco TY2335 User manual

Johnson Controls

Johnson Controls tyco TY2335 User manual

Johnson Controls tyco TY720 User manual

Johnson Controls

Johnson Controls tyco TY720 User manual

Johnson Controls tyco TFP700 User manual

Johnson Controls

Johnson Controls tyco TFP700 User manual

Johnson Controls C-9500 User manual

Johnson Controls

Johnson Controls C-9500 User manual

Popular Irrigation System manuals by other brands

Viking VK503 Technical data

Viking

Viking VK503 Technical data

Autopot 24Pot XL Set-up guidelines

Autopot

Autopot 24Pot XL Set-up guidelines

Reliable F1 LO manual

Reliable

Reliable F1 LO manual

Globe GL Series quick start guide

Globe

Globe GL Series quick start guide

Viking VK570 Technical data

Viking

Viking VK570 Technical data

Tyco TY-QRF-EU quick start guide

Tyco

Tyco TY-QRF-EU quick start guide

Cadman 3250XL Operator and parts manual

Cadman

Cadman 3250XL Operator and parts manual

Tyco Fire Product Gem F898 instruction manual

Tyco Fire Product

Tyco Fire Product Gem F898 instruction manual

birdcontrol AUSTRALIA Garden Sentinel Assembly instructions

birdcontrol AUSTRALIA

birdcontrol AUSTRALIA Garden Sentinel Assembly instructions

Autopot 12Pot XL Set-up guidelines

Autopot

Autopot 12Pot XL Set-up guidelines

Viking VK510 Technical data

Viking

Viking VK510 Technical data

Viking Microfast M-5 Technical data

Viking

Viking Microfast M-5 Technical data

FIRST TUNNELS DOM installation guide

FIRST TUNNELS

FIRST TUNNELS DOM installation guide

Tyco Fire Product Star Luminous S176 instruction manual

Tyco Fire Product

Tyco Fire Product Star Luminous S176 instruction manual

AVILO G222437 manual

AVILO

AVILO G222437 manual

Viking SupplyNet DS21-24 quick start guide

Viking

Viking SupplyNet DS21-24 quick start guide

Tyco Fire Product CENTRAL LF instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL LF instruction manual

Irrigatia SOL-C60 instructions

Irrigatia

Irrigatia SOL-C60 instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.