Johnson Controls tyco TY-B Series User manual

Series TY-B — 57, 80, and 115 K-factor
Upright and Pendent Sprinklers
Special Response, Standard Coverage
Page 1 of 4 AUGUST 2018 TFP672
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The Series TY-B, 57, 80, and 115 K-fac-
tor, Upright and Pendent Sprinklers
described in this data sheet are special
response - standard coverage, decora-
tive 4 mm glass bulb type spray sprin-
klers designed for use in accordance
with the installation rules recognized by
the applicable Approval agency (e.g.,
VdS).
NOTICE
The Series TY-B Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards recognized by the Approval
agency, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers (SINs)
TY2149 . . . . . . . . . . . . . . Upright 57K
TY2249 . . . . . . . . . . . . . Pendent 57K
TY3141 . . . . . . . . . . . . . . Upright 80K
TY3241 . . . . . . . . . . . . . Pendent 80K
TY4141 . . . . . . . . . . . . . Upright 115K
TY4241 . . . . . . . . . . . . .Pendent 115K
Technical
Data
Approvals
VdS Approved (CEA 4001)
Maximum Working Pressure
12,1 ba r
Discharge Coefficient
K = 57 lpm/bar½
K = 80 lpm/bar½
K = 115 lpm/bar½
Temperature Ratings
57°C, 68°C, 79°C, 93°C, and 141°C
Finishes
Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Button . . . . . . . . . . . . . . . . . . . . . . Brass/Copper
Sealing Assembly ..Beryllium Nickel w/TEFLON
Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Compression Screw . . . . . . . . . . . . . . . . .Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
TFP672
Page 2 of 4
*
*
*
PENDENTUPRIGHT
CROSS
SECTION
55 mm
WRENCH
FLATS
38 mm
10 mm
NOMINAL
MAKE-IN
53 mm
3
1
2
5
4
6
ISO
7 - R3/8
Temperature rating is
indicated on Deector
or adjacent to orice
seat on Frame.
Components:
-
1
3
2
-
-
Frame
Sealing
Assembly
Button
Deector
Compression
Screw
-
4 Bulb
-
6
5-
*
* **
*
**
SECTION
CROSS
PENDENTUPRIGHT
56 mm
38 mm
11 mm
NOMINAL
MAKE-IN 1/2"
NPT
56 mm
WRENCH
FLATS
3
1
2
5
4
6
1
2
Bulb
Button
Frame
-
-4-
3 Sealing
Assembly
-
Compression
Screw
5-
Deector6 -
Components:Pipe thread connections per
ISO 7-1 can be provided on
special request.
Temperature rating is
indicated on Deector
or adjacent to orice
seat on Frame.
FIGURE 1
SPECIAL RESPONSE SERIES TY-B UPRIGHT (TY2149) AND PENDENT (TY2249) SPRINKLERS
57 K-FACTOR, ISO 7-1 R 3/8
FIGURE 2
SPECIAL RESPONSE SERIES TY-B UPRIGHT (TY3141) AND PENDENT (TY3241) SPRINKLERS
80 K-FACTOR, 1/2 INCH NPT
TFP672
Page 3 of 4
Installation
The Series TY-B Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1,6 mm for
the 57°C to 2,4 mm for the 141°C tem-
perature ratings.
A leak tight ISO 7-1 R 3/8 sprinkler
joint should be obtained with a torque
of 8 to 16 N∙m. A leak tight 1/2 in. NPT
sprinkler joint should be obtained with
a torque of 9 to 19 N∙m. A leak tight
3/4 in. NPT sprinkler joint should be
obtained with a torque of 13 to 27 N∙m.
Higher levels of torque may distort the
sprinkler inlet and cause leakage or
impairment of the sprinkler.
Do not attempt to make up for insuf-
ficient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-B Pendent and Upright
Sprinklers must be installed in accor-
dance with the following instructions:
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 4) or
W-Type 7 Sprinkler Wrench (Ref. Figure
5). With reference to Figures 1, 2, and
3, the W-Type 6 or W-Type 7 Sprinkler
Wrench is to be applied to the wrench
flats.
Care and
Maintenance
The Series TY-B Sprinklers must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
* **
**
*
*
UPRIGHT PENDENT
CROSS
SECTION
59 mm
40 mm
3/4"
NPT
13 mm
NOMINAL
MAKE-IN
57 mm
WRENCH
FLATS
Pipe thread connections per
ISO 7-1 can be provided on
special request.
5
6
4
3
2
1
Bulb
Compression
Screw
Deector
Sealing
Assembly
Components:
1-Frame
Button
3
2
-
-
-
4
-
6
5-
Temperature rating is
indicated on Deector
or adjacent to orice
seat on Frame.
WRENCH RECESS
(END "A" USED FOR
ISO 7 - R3/8 &
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
RECESS
WRENCH
WITH SPRINKLER
ENGAGEMENT
IN TO ENSURE
WRENCHING AREA
PUSH WRENCH
FIGURE 4
W-T YPE 6
SPRINKLER WRENCH
FIGURE 3
SPECIAL RESPONSE SERIES TY-B UPRIGHT (TY4141) AND PENDENT (TY4241) SPRINKLERS
115 K-FACTOR, 3/4 INCH NPT
FIGURE 5
W-T YPE 7
SPRINKLER WRENCH
TFP672
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
* Eastern Hemisphere sales only
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Ref to the Installa-
tion section for more information.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assembly
Specify: (Specify) SIN, (specify) K-fac-
tor, Series TY-B (specify Pendent or
Upright) Sprinkler Special Response,
(specify) temperature rating, with
(specify) finish, P/N (specify from Table
A)
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
P/N 57 - XXX - X - XXX
SIN
480 57K UPRIGHT (ISO 7-1 R 3/8) TY2149
481 57K PENDENT (ISO 7-1 R 3/8 TY2249
470 80K UPRIGHT (1/2 in. NPT) TY3141
471 80K PENDENT (1/2 in. NPT) TY3241
490 115K UPRIGHT (3/4 in. NPT) TY4141
491 115K PENDNET (3/4 in. NPT) T Y4241
SPRINKLER
FINISH
1NATURAL BRASS
3PURE WHITE (RAL9010)*
POLYESTER
4SIGNAL WHITE (RAL9003)
POLYESTER
9CHROME PLATED
TEMPERATURE
RATING
135 57°C
155 68°C
175 79°C
200 93°C
286 141°C
TABLE A
SERIES TY-B SPECIAL RESPONSE PENDENT AND UPRIGHT SPRINKLERS
PART NUMBER SELECTION

Other manuals for tyco TY-B Series

5

This manual suits for next models

6

Other Johnson Controls Irrigation System manuals

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TFP700 User manual

Johnson Controls

Johnson Controls tyco TFP700 User manual

Johnson Controls tyco TY2334 User manual

Johnson Controls

Johnson Controls tyco TY2334 User manual

Johnson Controls tyco ESFR-25 User manual

Johnson Controls

Johnson Controls tyco ESFR-25 User manual

Johnson Controls JWS-3 User manual

Johnson Controls

Johnson Controls JWS-3 User manual

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls

Johnson Controls tyco TY-FRL Series User manual

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls tyco TY2235 User manual

Johnson Controls

Johnson Controls tyco TY2235 User manual

Johnson Controls tyco TY2335 User manual

Johnson Controls

Johnson Controls tyco TY2335 User manual

Johnson Controls tyco ILLUSION User manual

Johnson Controls

Johnson Controls tyco ILLUSION User manual

Johnson Controls tyco DS-1 Series User manual

Johnson Controls

Johnson Controls tyco DS-1 Series User manual

Johnson Controls Tyco EC-11 Series User manual

Johnson Controls

Johnson Controls Tyco EC-11 Series User manual

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls

Johnson Controls tyco RAPID RESPONSE LFII Series User manual

Johnson Controls tyco RFII Series User manual

Johnson Controls

Johnson Controls tyco RFII Series User manual

Johnson Controls tyco EC-25 User manual

Johnson Controls

Johnson Controls tyco EC-25 User manual

Johnson Controls tyco TFP PH5 User manual

Johnson Controls

Johnson Controls tyco TFP PH5 User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls Tyco EC-8 Series User manual

Johnson Controls

Johnson Controls Tyco EC-8 Series User manual

Johnson Controls tyco TY-B Series User manual

Johnson Controls

Johnson Controls tyco TY-B Series User manual

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls

Johnson Controls tyco TY-FRB Series User manual

Johnson Controls Tyco TY720 User manual

Johnson Controls

Johnson Controls Tyco TY720 User manual

Johnson Controls tyco RFII-MRI Series User manual

Johnson Controls

Johnson Controls tyco RFII-MRI Series User manual

Johnson Controls tyco CWS User manual

Johnson Controls

Johnson Controls tyco CWS User manual

Johnson Controls tyco ESFR-25 User manual

Johnson Controls

Johnson Controls tyco ESFR-25 User manual

Popular Irrigation System manuals by other brands

Globe GL-RES Series manual

Globe

Globe GL-RES Series manual

Tyco G5 Sprinkler Guard manual

Tyco

Tyco G5 Sprinkler Guard manual

K-Rain KRC 9 user manual

K-Rain

K-Rain KRC 9 user manual

Viking FREEDOM VK466 Technical data

Viking

Viking FREEDOM VK466 Technical data

claber POP-UP 90 user manual

claber

claber POP-UP 90 user manual

Viking VK3521 Technical data

Viking

Viking VK3521 Technical data

Tyco TY-L Series manual

Tyco

Tyco TY-L Series manual

Toro TR70XT SERIES Instruction guide

Toro

Toro TR70XT SERIES Instruction guide

Reliable GFR manual

Reliable

Reliable GFR manual

Tyco ESFR-17 quick start guide

Tyco

Tyco ESFR-17 quick start guide

Netafim nmc-pro user guide

Netafim

Netafim nmc-pro user guide

Kärcher WU 90/72 manual

Kärcher

Kärcher WU 90/72 manual

Tyco Fire Product EC-17 instruction manual

Tyco Fire Product

Tyco Fire Product EC-17 instruction manual

Rain Bird 11000 Series Operation & maintenance manual

Rain Bird

Rain Bird 11000 Series Operation & maintenance manual

Tyco F08 FIP Operator's manual

Tyco

Tyco F08 FIP Operator's manual

Toro 53765 - Outdoor Ecxtra Sprinkler Timer user guide

Toro

Toro 53765 - Outdoor Ecxtra Sprinkler Timer user guide

Tyco Fire Product CENTRAL ELO Optima instruction manual

Tyco Fire Product

Tyco Fire Product CENTRAL ELO Optima instruction manual

Tyco TY-B Series quick start guide

Tyco

Tyco TY-B Series quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.