GB 10
Memory capacity is not sufficient to
read in parameters.
(In mode FU-OP)
Unitisnotsuitedfor data transmission
withthe memory operator.
Parameters have not been saved
completely in the operator memory
(RAM).
During download into memory and
errors message occurred (Err.1....5).
Thus, not all parameters could be
saved.
The connected inverter’s address
does not correspond to the inverter
address saved in the memory.
- Clear error message by pressing
the ‘ENTER’-key →inverter’s
address will not be changed
- By pressing the ‘START’-key →the
error is cleared and the addresses
in the memory operator are down-
loaded.
Downloadto theinverterwasstopped
(With Mode OP_FU) The inverter was not in state „noP“
during writing parameter Fr.01 →
open control release and start
„download“ again.
Saved (e.g. type 45) and connected
(e.g. type 46) inverter do not
correspond.
All type numbers can be displayed
(In mode OP_FU)
- Clear message by pressing the
‘ENTER’ -key →download is
stopped.
- Clear message by pressing the
‘START’-key →download
continues.This functionis usede.g.
to change inverter-software-
versions, to transfer old download
lists onto the new software.
(Beispiel)
4. Error Messages
Display Description Cause / Remedy
Frequencyinverter orservocontroller
was not recognized by the operator Connectionpinbroken/missing; Baud
rate notcorrectadjusted; Operatoror
controller defective
Upload unpossible - Data of the
inverter cannot be load in the
operator
Mode FU_OP (UPLOAD) is locked.
(see3.1)
Selectedoperation canceled byuser. “STOP” -key was pressed while
display was flashing
Duringanactiveoperation(e.g.download)
the connected inverter or servo is no
longer recognized by the operator.
Connection pin broken or missing,
transmission interrupted, frequency
inverter/servo controller is switched
off.