KEBCO COMBIVERT G6 User manual

Instructions for Use
COMBIVERT G6
Controlboard MODBUS
Translation of the original manual
Document 20332669 EN 00

Impressum
KEB Automation KG
Suedstraße 38, D-32683 Barntrup
Germany
Tel: +49 5263 401-0 • Fax: +49 5263 401-116
E-Mail: [email protected] • URL: https://www.keb.de
ma_dr_g6-modbus-20332669_en
Version 00 • Edition 01/02/2023

Table of Contents
ma_dr_g6-modbus-20332669_en iii
Table of Contents
1 Introduction ................................................................................................................................................... 4
1.1 Markings................................................................................................................................................ 4
1.1.1 Warnings................................................................................................................................. 4
1.1.2 Information notes .................................................................................................................... 4
1.1.3 Symbols and markers ............................................................................................................. 5
1.2 Laws and guidelines.............................................................................................................................. 5
1.3 Warranty and liability............................................................................................................................. 5
1.4 Support.................................................................................................................................................. 5
1.5 Copyright............................................................................................................................................... 5
1.6 Validity of this manual ........................................................................................................................... 6
1.7 Target group.......................................................................................................................................... 6
2 General Safety Instructions.......................................................................................................................... 7
2.1 Installation ............................................................................................................................................. 7
2.2 Start-up and operation .......................................................................................................................... 8
2.3 Maintenance.......................................................................................................................................... 8
3 Product description ...................................................................................................................................... 9
3.1 Functional description ........................................................................................................................... 9
3.2 Validity................................................................................................................................................... 9
3.3 Hardware description ............................................................................................................................ 9
4 MODBUS functions ....................................................................................................................................... 10
4.1 Supported functions .............................................................................................................................. 10
4.2 Parameter addressing........................................................................................................................... 10
4.3 Watchdog function ................................................................................................................................ 10
5 Parameter description .................................................................................................................................. 11
5.1 OS group: Operator system .................................................................................................................. 11
5.2 Fb group: Fieldbus parameters ............................................................................................................. 11
5.2.1 Fb00 Protocol selector............................................................................................................ 11
5.2.2 Fb01 DIN66019II input select. ................................................................................................ 11
5.2.3 Fb02 Current protocol............................................................................................................. 11
5.2.4 Fb03 MODBUS node ID ......................................................................................................... 11
5.2.5 Fb04 MODBUS baud rate....................................................................................................... 11
5.2.6 Fb10 MODBUS config ............................................................................................................ 11
5.2.7 Fb11 Reading map size.......................................................................................................... 12
5.2.8 Fb12 Writing map size ............................................................................................................ 12
5.2.9 Fb13 Read map index ............................................................................................................ 12
5.2.10 Fb14 Read map ...................................................................................................................... 12
5.2.11 Fb15 Write map index............................................................................................................. 12
5.2.12 Fb16 Write map ...................................................................................................................... 12
5.2.13 Fb20 diag response delay time............................................................................................... 13
6 Revision History ............................................................................................................................................ 14
Glossary ......................................................................................................................................................... 15

1 | Introduction KEB Automation KG
4 ma_dr_g6-modbus-20332669_en
1 Introduction
The described devices, accessories, hardware and/or software are products of
KEB Automation KG. The enclosed documents correspond to conditions valid at
printing. Misprint, mistakes and technical changes reserved.
1.1 Markings
1.1.1 Warnings
Certain operations can cause hazards during the installation, operation or there-
after. There are safety informations in the documentation in front of these opera-
tions.
Warnings contain signal words for the severity of the hazard, the type and/or
source of the hazard, the consequence of non-compliance and the measures to
avoid or reduce the hazard.
DANGER Type and/or source of the hazard.
Leads to death or serious bodily injury if not observed.
a) Measures to avoid the hazard.
b) Can be supplemented by an additional danger sign or pictogram.
WARNING Type and/or source of the hazard.
May cause death or serious injury if not observed.
a) Measures to avoid the hazard.
b) Can be supplemented by an additional danger sign or pictogram.
CAUTION Type and/or source of the hazard.
May cause bodily injury if not observed.
a) Measures to avoid the hazard.
b) Can be supplemented by an additional danger sign or pictogram.
NOTICE Type and/or source of the hazard.
Can cause damage to property if not observed.
a) Measures to avoid the hazard.
b) Can be supplemented by an additional danger sign or pictogram.
1.1.2 Information notes
Indicates to the user a special condition, prerequisite, scope or simplifica-
tion.
This is a reference to further documentation with barcode
for smartphones and link for online users.
https://www.keb.co.uk/nc/search

Introduction | 1
ma_dr_g6-modbus-20332669_en 5
Notes on conformity for use in the North American or Canadian mar-
ket.
1.1.3 Symbols and markers
üCondition
a) Action step
ðResult or intermediate result
=> Cross-reference to a chapter, page or picture
Hyperlink
<Steuercode>
Lexicon entry
1.2 Laws and guidelines
KEB Automation KG confirms with the CE mark and the EU declaration of conform-
ity, that our device complies with the essential safety requirements.
The EU declaration of conformity can be downloaded on demand via our website.
1.3 Warranty and liability
The warranty and liability on design, material or workmanship for the acquired
device is given in the general conditions of sale.
Here you will find our general sales conditions.
https://www.keb.co.uk/terms-and-conditions
Further agreements or specifications require a written confirmation.
1.4 Support
Through multiple applications not every imaginable case has been taken into ac-
count. If you require further information or if problems occur which are not treated
detailed in the documentation, you can request the necessary information via the
local KEB Automation KG agency.
The use of our units in the target products is beyond of our control and
therefore exclusively the responsibility of the customer.
The information contained in the technical documentation, as well as any user-spe-
cific advice in spoken and written and through tests, are made to best of our know-
ledge and information about the intended use. However, they are considered for in-
formation only without responsibility and changes are expressly reserved, in partic-
ular due to technical changes. This also applies to any violation of industrial prop-
erty rights of a third-party.
Selection of our units in view of their suitability for the intended use must be done
generally by the user.
Tests can only be carried out within the scope of the intended end use of the
product (Application) by the Customer. They must be repeated, even if only
parts of hardware, software or the unit adjustment are modified.
1.5 Copyright
The customer may use the instructions for use as well as further documents or
parts from it for internal purposes. Copyrights are with KEB Automation KG and re-
main valid in its entirety.

1 | Introduction KEB Automation KG
6 ma_dr_g6-modbus-20332669_en
Other wordmarks and/or logos are trademarks (™) or registered trademarks (®) of
their respective owners.
1.6 Validity of this manual
This part of the instruction manual describes the implemented control card. It
• is only valid in conjunction with the instructions for use of the power part.
• contains only supplementary safety instructions.
• if certain functions or properties are version-dependent, this is indicated at the
appropriate place. The version number of the COMBIVERT can be found in
brackets after the material number.
1.7 Target group
The instructions for use is determined exclusively for electrical personnel. Electrical
personnel for the purpose of this instruction manual must have the following quali-
fications:
• Knowledge and understanding of the safety instructions.
• Skills for installation and assembly.
• Start-up and operation of the product.
• Understanding of the function in the used machine.
• Detection of hazards and risks of the electrical drive technology.
• Knowledge of IEC 60364.
• Knowledge of national safety regulations (e. g. DGUV Regulation 3.

General Safety Instructions | 2
ma_dr_g6-modbus-20332669_en 7
2 General Safety Instructions
The products are developed and built according to the state of the art and recog-
nized safety rules. Nevertheless, their use may create dangers to life and limb of
the user or third parties or damage to the machine and other material property.
The following safety instructions have been created by the manufacturer for the
area of electric drive technology. They can be supplemented by local, country- or
application-specific safety instructions. This list is not exhaustive. Non-observance
of the safety instructions by the customer, user or other third party leads to the loss
of all resulting claims against the manufacturer.
NOTICE Hazards and risks through ignorance!
a) Read the instructions for use.
b) Observe the safety and warning instructions.
c) Ask if something is unclear.
2.1 Installation
DANGER Electrical voltage at terminals and in the device!
Danger to life due to electric shock !
üFor any work on the device
a) Switch off the supply voltage.
b) Secure it against switching on.
c) Wait until all drives has been stopped in order that no regenerative energy can
be generated.
d) Await capacitor discharge time (min. 5 minutes). Measure DC voltage at the
terminals.
e) Never bridge upstream protective devices. Also not for test purposes.
NOTICE Use of unsuitable voltage sources!
Electric Shock!
a) Use for the connection only suitable voltage sources with safe isolation (SELV/
PELV) in accordance with VDE 0100 with nominal voltage of DC 24 V ±10 %.
b) Pay attention on a sufficient overvoltage category of the voltage supply.
c) With existing or newly wired circuits the person installing the units or machines
must ensure that the PELV requirements are met.
For a trouble-free and safe operation, please pay attention to the following instruc-
tions:
• The electrical installation shall be carried out in accordance with the relevant re-
quirements.
• Cable cross-sections and fuses must be dimensioned by the user according to
the specified minimum/maximum values for the application.
• For drive converters that are not isolated from the supply circuit (in accordance
with EN 61800-5-1) all control lines must be included in other protective meas-
ures (e.g. double insulation or shielded, earthed and insulated).
• When using components without isolated inputs/outputs, it is necessary that
equipotential bonding exists between the components to be connected (e.g. by
the equipotential line). Disregard can cause destruction of the components by
equalizing currents.

2 | General Safety Instructions KEB Automation KG
8 ma_dr_g6-modbus-20332669_en
2.2 Start-up and operation
The start-up (i.e. the starting of normal operation) is prohibited until the machinery
has been proved to conform to the provisions Directive 2006/42/EG and Directive
2014/30/EU; EN 60204-1 must be observed.
WARNING Wrong parameterization
Unintentional behaviour of the drive
üDuring initial start-up or replacement of the drive controller
a) Secure motors against automatic restart.
b) Check whether the appropriate parameter list for the application has been im-
ported.
WARNING Software protection functions as sole protection.
Protection function in case of software problems without function.
üSecuring a unit solely with software-supported functions is not sufficient.
a) Install external protective measures (e.g. limit switch) that are independent of
the drive controller.
2.3 Maintenance
DANGER Unauthorized exchange, repair and modifications
Unpredictable malfunctions
a) The function of the drive controller is dependent on its parameterization. Never
replace without knowledge of the application.
b) Modification or repair is permitted only by KEB Automation KG authorized per-
sonnel.
c) Only use original manufacturer parts.
d) Infringement will annul the liability for resulting consequences.

Product description | 3
ma_dr_g6-modbus-20332669_en 9
3 Product description
3.1 Functional description
This manual describes the software extension of the control board COMBIVERT G6 with
MODBUS.
It is based on the standard control board analog/digital. It is designed to be used on any
G6 with or without STO functions.
This manual describes the fieldbus parameter group and the behaviour of the MODBUS
driver.
All DIN666019II behaviours and services comply with the G6 standard analog/digital. For
more information, see the documentation on DIN66019II.
3.2 Validity
The described software is only valid for devices with material number in accordance with
the following key:
xxG6CDx-YSxx
The assignment of the firmware depends on the hardware of the power unit:
Power unit hardware Power unit code Config-ID Control board firmware
MODBUS
Config-ID 160212
U/F 7137 5424 / 5425 1.2.0.x / 1.3.0.x
U/F 7084 5888 / 5889 1.2.1.x / 1.3.1.x
3.3 Hardware description
The D-Sub DE-9 socket (X4A) is intended for the connection to DIN66019II or MODBUS.
The socket supports the RS232 or alternatively the RS485 transmission standard. All
other connections correspond to the standard control board analog/digital.
The following figure shows the assignment of the interface X4A:
5 4 3 2 1
9 8 7 6
1
2
3
4
5
67
8
9
Fig.1: D-Sub DE-9 socket
1 reserved 2 TxD (RS232)
3 RxD (RS232) 4 RxD-A (RS485)
5 RxD-B (RS485) 6 reserved
7 DGND (reference potential) 8 TxD-A (RS485)
9 TxD-B (RS485)
The protocol of the interface can be switched between MODBUS and DIN 66019II by
parameter or via an input.

4 | MODBUS functions KEB Automation KG
10 ma_dr_g6-modbus-20332669_en
4 MODBUS functions
4.1 Supported functions
The KEB G6 MODBUS interface supports the following functions defined in the Modbus
standard:
• 3: 'Reading Holding Registers'
• 4: 'Reading Input Registers' (for KEB, identical to function 3)
• 6: 'Preset Single Register'.
• 16: 'Preset Multiple Registers'.
These functions only support 16-bit access to parameters.
Therefore, two additional functions for accessing 32-bit parameters were created:
• 100: 'Read Registers 32':
Reading multiple 32 bit registers (indirect set addressing through Fr09)
• 101: 'Write Registers 32':
Writing multiple 32 bit registers (indirect set addressing through Fr09). For those func-
tion the datagram building is similar to 3 / 16 functions.
4.2 Parameter addressing
The addresses of the parameters (register) are divided into different groups. Each of
those groups has its own accessing method:
•0000(hex)…1FFF(hex):
This group is defined to access to mapping parameters. Parameters are set up to be
redirected to the mapping list.
•2000(hex)…5EFF(hex):
In this address area the parameters of the inverter control board are mapped by a fixed
algorithm. Please keep in mind that in this address area access is done with indirect
set addressing (with Fr09). This means when writing/reading one parameter in different
sets you have to set the set indicator (Fr09) previously before access.
•5F00(hex)…5FFF(hex):
This block consists of the operator parameters.
4.3 Watchdog function
The MODBUS driver supports fieldbus monitoring. With regard to the settings Pn05 and
Pn06, the watchdog is controlled via the MODBUS communication.
This function only starts after the first valid datagram exchange.

Parameter description | 5
ma_dr_g6-modbus-20332669_en 11
5 Parameter description
5.1 OS group: Operator system
The settings in this group correspond to the G6 standard version. Please refer to the G6
standard documentation for a further description.
5.2 Fb group: Fieldbus parameters
These parameters set the fieldbus interface.
This group is available on the display and via a PC connection.
5.2.1 Fb00 Protocol selector
Selector to set the requested protocol:
• 0: DIN66019II
• 1: Modbus
• 2: DIN66019II is selected by input activation. Input is selectable on parameter Fb01.
Lower limit Upper limit Standard value Unit
0 2 0 -
5.2.2 Fb01 DIN66019II input select.
Input selection to activate/deactivate DIN66019II instead of MODBUS.
If the function is set to "0 = off", the DIN66019II cannot be selected by input.
Lower limit Upper limit Standard value Unit
0: off 7: RST 1: I1 -
5.2.3 Fb02 Current protocol
Specifies the current protocol for the D-Sub DE-9 port.
0: DIN66019II
1: MODBUS
Lower limit Upper limit Standard value Unit
0 1 0 -
5.2.4 Fb03 MODBUS node ID
Slave address for MODBUS protocol only.
Lower limit Upper limit Standard value Unit
0 239 1 -
5.2.5 Fb04 MODBUS baud rate
D-Sub DE9 transmission speed. Value is reset to default if parameter os15 (Store diag.
baudrate) is not set to 'On'.
Lower limit Upper limit Standard value Unit
0: 1.2 8: 100.0 5: 38.4 kBaud
5.2.6 Fb10 MODBUS config
Configures the MODBUS interface protocol.

5 | Parameter description KEB Automation KG
12 ma_dr_g6-modbus-20332669_en
B7 B6 B5 B4 B3 B2 B1 B0
RTU/ AS-
CII
Parity - - - - -
Bit 7 1 MODBUS RTU
0 MODBUS ASCII (not supported yet)
Bit 5/6 00 8 data bits / no parity bit / 2 stop bits
01 8 data bits / odd parity bit / 1 stop bit
10 8 data bits / even parity bit / 1 stop bit
Lower limit Upper limit Standard value Unit
0 255 192 -
5.2.7 Fb11 Reading map size
Defines the mapping buffer size for parameter reading.
Lower limit Upper limit Standard value Unit
1 100 2 -
5.2.8 Fb12 Writing map size
Defines the mapping buffer size for parameter writing.
Lower limit Upper limit Standard value Unit
1 100 2 -
5.2.9 Fb13 Read map index
Set the pointer to read mapping buffer to be displayed on Fb14.
Lower limit Upper limit Standard value Unit
0 99 0 -
5.2.10 Fb14 Read map
Value stored into the read mapping buffer at the Fb13 position.
Lower limit Upper limit Standard value Unit
0 FFFFFFFFh 0 -
5.2.11 Fb15 Write map index
Set the pointer to write mapping buffer to be displayed on Fb16.
Lower limit Upper limit Standard value Unit
0 99 0 -
5.2.12 Fb16 Write map
Value stored into the write mapping buffer at the Fb15 position.
Lower limit Upper limit Standard value Unit
0 FFFFFFFFh 0 -

Parameter description | 5
ma_dr_g6-modbus-20332669_en 13
5.2.13 Fb20 diag response delay time
Specifies the permissible delay time for a diagnostic response in ms.
Lower limit Upper limit Standard value Unit
0 126 0 ms

6 | Revision History KEB Automation KG
14 ma_dr_g6-modbus-20332669_en
6 Revision History
Edition Version Note
2012-09-03 - First creation
2012-09-19 - New functions of version 1.1.0.0 added.
2013-01-31 - New parameters of version 1.2.x.0 added.
2023-01-31 00 Revision to version 1.3.x.0; Parameter Fb05 removed; Fb20 ad-
ded.

Glossary
ma_dr_g6-modbus-20332669_en 15
Glossary
Application
The application is the intended use of the KEB
product.
COMBIVERT
Proper name for a KEB Drive Controller
Customer
The customer has purchased a product from KEB
and integrates the KEB product into his product
(customer product) or resells the KEB product (re-
seller).
Directive 2006/42/EC
Machinery Directive
Directive 2014/30/EU
Electromagnetic Compatibility (EMC) Directive
EN 60204-1
Safety of machinery - Electrical equipment of ma-
chines - Part 1: General requirements (VDE
0113-1, IEC 44/709/CDV).
EN 61800-5-1
Adjustable speed electrical power drive systems.
Part 5-1: Safety requirements - Electrical, thermal
and energy requirements (VDE 0160-105-1, IEC
61800-5-1)
MODBUS
The MODBUS protocol is an open communication
protocol based on a client/server architecture. It is
part of the IEC 61158 standard. MODBUS is a
trademark of SCHNEIDER ELECTRIC USA, INC.
PELV
Safe protective extra-low voltage (earthed).
RS232
RS-232 is a standard of a physical interface for
asynchronous, serial data transmission.
RS485
RS-485 is an industry standard according to
EIA-485 for a physical interface for asynchronous,
serial data transmission.
SELV
Safe protective extra-low voltage (unearthed;
<60V).

KEB Automation KG
16 ma_dr_g6-modbus-20332669_en
Notes

MORE KEB PARTNERS WORLDWIDE:
www.keb.de/contact/contact-worldwide

Automation with Drive www.keb.de
KEB Automation KG • Suedstraße 38 • D-32683 Barntrup • Tel: +49 5263 401-0 • E-Mail: [email protected]
Other manuals for COMBIVERT G6
12
Table of contents
Other KEBCO Industrial Equipment manuals

KEBCO
KEBCO COMBISTOP 28 User manual

KEBCO
KEBCO COMBIVERT F5 User manual

KEBCO
KEBCO COMBIVERT F6 User manual

KEBCO
KEBCO COMBILINE E6 Series User manual

KEBCO
KEBCO COMBINORM User manual

KEBCO
KEBCO COMBISTOP User manual

KEBCO
KEBCO COMBICOM User manual

KEBCO
KEBCO COMBINORM B User manual

KEBCO
KEBCO COMBILINE User manual

KEBCO
KEBCO Combivert R6 User manual