Kemper KHS Mini System Control User manual

Installation and operating instructions
KEMPER KHS Mini System Control
KEMPER KHS Mini System Control MASTER 2.0 Figure 686 02 008
KHS Mini System Control SLAVE Figure 686 02 006

Manual KHS Mini System Control
TABLE OF CONTENTS
TABLE OF CONTENTSTABLE OF CONTENTS
TABLE OF CONTENTS
1.
GENERAL INSTRUCTIONS:
................................
................................................................
................................................................
................................................................
.................................................
..................................
.................
1
11
1
2.
AREA O APPLICATION
................................
................................................................
................................................................
................................................................
......................................................
............................................
......................
2
22
2
2.1
Operating mo es for the water exchange .................................................................................................. 2
2.2
KHS MASTER/SLAVE technology ............................................................................................................. 2
2.3
Water exchange groups ............................................................................................................................. 2
3.
SA ETY
................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................
................................
................
3
33
3
3.1
Safety Instructions ..................................................................................................................................... 3
3.2 Hazar s if the safety instructions are not complie with ............................................................................ 3
3.3
Unauthorize alteration an spare part fabrication .................................................................................... 3
3.4
Unauthorise mo es of operation .............................................................................................................. 3
4.
TECHNICAL DATA
................................
................................................................
................................................................
................................................................
...............................................................
..............................................................
...............................
4
44
4
5.
CAN BUS SYSTEM OVERVIEW
................................
................................................................
................................................................
................................................................
...........................................
......................
...........
5.1
Layout variants ..........................................................................................................................................
5.2
Terminal resistance .................................................................................................................................... 6
5.3 Connection of terminal resistor .................................................................................................................. 6
6.
ASSEMBLY
................................
................................................................
................................................................
................................................................
................................................................
................................................................
..........................................
....................
..........
7
77
7
6.1.
Wall mounting ............................................................................................................................................ 7
6.2
Electrical installation KHS Mini System Control ......................................................................................... 8
6.2.1
Terminal escription -MASTER 2.0- an -SLAVE- 8
6.2.2
Detaile illustration of the terminals for cable entry 9
6.2.2.1
Power supply connection 9
6.2.2.2
Connection of KHS-VAV Maximum flow isolating ball valve with servo- rive
(Figure 686 00)
9
6.2.2.3
Connection of KHS-VAV Maximum flow isolating ball valve with spring reset servo- rive
(Figure 686 01)
10
6.2.2.4
CAN bus connection 10
6.2.2.5
Connection of external switch
11
6.2.2.6
Connection of KHS-CONTROL-PLUS flow measurement valve (Figure 638 4G)
12
6.2.2.7
Connection of KHS Temperature sensor Pt 1000 (Figure 628 0G) 13
6.2.2.8
Connection of KHS rain with overflow monitor (Figure 688 00)
13
6.2.2.9
Connection of water sensor (Figure 620 00) 14
6.2.2.10
Connection of floating alarm relay 14
6.3
Installation of network cable ..................................................................................................................... 1
7.
COMMISSIONING
................................
................................................................
................................................................
................................................................
...............................................................
..............................................................
...............................
16
1616
16

Manual KHS Mini System Control
8.
CON IGURATION
................................
................................................................
................................................................
................................................................
..............................................................
............................................................
..............................
17
1717
17
8.1
Manual configuration ................................................................................................................................ 18
8.1.1
Basic menu operation an functions 18
8.1.2
General plan 19
8.1.3
Detaile overview 20
8.1.4
Main menu 21
8.1.4.1
System settings ..................................................................................................................................... 22
8.1.4.2
CAN BUS setup .................................................................................................................................... 25
8.1.4.3
Device settings ...................................................................................................................................... 26
8.1.4.4
Operating mo es .................................................................................................................................. 31
8.1.4.5
Journal .................................................................................................................................................... 37
8.1.4.6
Switching programs .............................................................................................................................. 38
8.1.4.7
Valve manual mo e ............................................................................................................................. 39
8.1.4.8
Network setup ....................................................................................................................................... 40
8.1.4.9
Error han ling ........................................................................................................................................ 42
8.1.5
Using the USB interface ...................................................................................................................... 43
8.2
Configuration of the WEB browser ........................................................................................................... 44
8.2.1
Basic menu operation an functions ................................................................................................. 45
8.2.2
SYSTEM SETTINGS ........................................................................................................................... 46
8.2.3
DEVICE SETTINGS ............................................................................................................................. 48
8.2.4
OPERATING MODES.......................................................................................................................... 63
8.2.5
OVERVIEW ........................................................................................................................................... 70
8.2.6
CURRENT VALUES ............................................................................................................................ 71
8.2.7
DATA TRANSFER ............................................................................................................................... 72
8.2.8
EMAIL ADMINISTRATION .................................................................................................................. 77
9.
DESCRIPTION O MAL UNCTIONS AND MAL UNCTION REPAIR
.................
..................................
.................
79
7979
79
10.
DIMENSIONS, ATTACHMENT DIMENSIONS
................................
................................................................
.....................................................
..........................................
.....................
81
8181
81
11.
ACCESSORIES
................................
................................................................
................................................................
................................................................
................................................................
................................................................
..................................
....
..
82
8282
82
12.
WIRING INSTRUCTIONS OR COMPONENTS WITH ELECTRICAL
CONNECTION
................................
................................................................
................................................................
................................................................
................................................................
................................................................
....................................
........
....
82
8282
82
13.
APPENDIX
................................
................................................................
................................................................
................................................................
................................................................
................................................................
..........................................
....................
..........
83
8383
83
13.1
Valve technologies ................................................................................................................................... 83
13.1.1
A/B valve technology............................................................................................................................ 83
13.1.2
C-valve technology ............................................................................................................................... 84
13.2
Overview for the system commissioning of the KHS Mini System Control ............................................... 84

Manual KHS Mini System Control 1
1. General instructions:
Assemble an commission the KEMPER KTS Mini System Control only after rea ing these assembly
an operating instructions. It informs you in etail about the assembly, commissioning, operating
principles an operation of the Kemper KHS Mini System Control. If you cannot fin the information
an instructions you nee in these operating instructions, ask the manufacturer, Gebr. Kemper (please
refer to last page for the a ress). Keep the mounting an operating instructions with the evice or file
it with the other technical ocumentation in the system ocumentation.
Symbols used
The symbols use in the text are explaine below.
List of symbols
Note:
Useful information
Warning notice:
Danger electric shock
Attention:
Imminent anger
Maintenance:
Maintenance/Repair

Manual KHS Mini System Control 2
2. Area of application
The KEMPER KHS Mini System Control can be use for monitoring an water exchange in rinking
water systems. The water exchanges can be generate an ocumente as flushing logs with the
MASTER 2.0 control. The e icate water exchanges prevent stagnation in the rinking water with the
aim of maintaining the rinking water hygiene in the rinking water systems. Base on the KHS Mini
System Control MASTER, the MASTER 2.0 is a web-base further evelopment that no longer
requires configuration an rea out software. The system works entirely in epen ent of the operating
system. On top of that, some new functions have been a e that make the evice also interesting for
large buil ings.
NOTICE:
If two or more valves are simultaneously opene in a rinking water system,
un er certain circumstances pressure fluctuations or a large pressure rop can
occur in the system. For that reason, make sure beforehan that the require flow
pressure is continuously guarantee at all tapping points. It is recommen e to
not make simultaneous water exchanges.
2.1
Operating modes
for the water exchange
Time controlle water exchange
Temperature controlle water exchange
Volume controlle water exchange
2.2
KHS MASTER/SLAVE technology
The MASTER/SLAVE technology can be use to trigger flushing measures for maintaining the
rinking water hygiene for the rinking water system. The correspon ing operating mo es can be
in ivi ually configure for each in ivi ual water-exchange group. Positioning the in ivi ual MASTER
or SLAVE controls irectly on the water exchange groups ensures short wiring istances for
interconnection.
2.3
Water exchange groups
Shown in Ill. 2.1 as an example is a KHS Mini
System Control -SLAVE- (2) in connection with a
water exchange group which comprises a KHS-
VAV Maximum flow isolating ball valves (4),
Temperature sensor (1), Volume flow sensor (3)
an a KHS Drain (5). The components of the water
exchange group are only liste as examples here.
The operating mo e epen s on the components
an the valve technology (for valve technology
please refer to Chapter 13.1). In the example
illustrate , the -SLAVE-(2) controls the specifie
water exchange groups. It is connecte with the
MASTER 2.0- through a CAN bus cable.
( )
Note:
Maintenance cut-offs are re-
commended in front of the
Volume flow sensor (3).
Ill. 2.1 Illustration of a water exchange
group
(1)
(2)
(3)
(4)

Manual KHS Mini System Control 3
3. Safety
The escriptions an instructions in these
operating instructions concern the KHS Mini
System Control -MASTER 2.0- an KHS
Mini System Control -SLAVE-. The
prerequisite for han ling the controller is the
eployment of professionally traine
personnel as per DIN EN 50110-1.
3.1
Safety Instructions
Before commissioning, make sure the connections have been ma e properly an professionally an
that the system is properly protecte . Comply with the pertinent regulations (EN, VDE, etc.) an the
regulations of the local energy utility.
3.2 Hazards if the safety instructions are not complied with
Non-compliance with the safety instructions can result in both hazar s to people an hazar s to the
environment an the system. Non-compliance with the safety instructions lea s to the loss of rights to
any compensation claims. In some cases, non-compliance can, for example, result in the following
hazar s:
Failure of important functions in the evice
Hazar s to people through electrical an mechanical effects
3.3 Unauthorized alteration and spare part fabrication
Alternations an mo ifications to the evice are only permissible after agreement with the
manufacturer. Original spare parts an manufacturer authorise accessories serve the purpose of
safety. The use of any other parts may annul the liability for any resultant consequences.
Attention:
Use only original/approve spare parts otherwise no warranty claims will be
recognize .
3.4 Unauthorised modes of operation
The reliability of the supplie unit is only ensure when use as inten e . Never excee the limits
state in this ocumentation un er any circumstances.
Note:
If the operating instructions are not followe , the manufacturer of this controller
oes not assume any responsibility. These operating instructions contain basic
instructions that must be complie with uring set-up, commissioning an
maintenance. Therefore, the plumber/mechanic an the responsible
specialists/operators must rea these operating instructions before assembly an
commissioning. Comply not only with the general safety instructions liste in this
main point; also follow the specific safety instructions liste un er the other main
points.
Warning notice:
During assembly and
maintenance, make sure that
the control is not switched on.
Only skilled professional
personnel are permitted to
operate electrical systems.
Danger of fatal electric shock.

Manual KHS Mini System Control 4
4. Technical Data
Technical Data
Power supply 230 V AC 50/60Hz
Display Graphic display with background ligh
ting
Operation with 4 buttons: Up | Down | Enter | Esc
Relay flush valve switching capacity 230 V, 2 A
loating alarm relay, max. 230 V, 2 A
16 memory locations for the operating modes:
•
Time controlled water exchange
•
Temperature controlled water exchange
•
Volume controlled water exchange
•
Routine-time, routine-duration and routine-volume
•
Data logging
•
Release
or connecting:
•
1 ea. KHS-VAV-plus or KHS-VAV
•
1 ea. KHS-Temperature sensor Pt 1000
•
1 ea. KHS-Control Plus volume flow measurement valve
•
1 ea. KHS overflow monitor
•
1 detector circuit with up to 25 water sensors
Acoustic alarm signal in case of faults
Alarm acknowledgement on device
System is expandable: 1
-
MASTER
-
with max. 62
-
SLAVEs
-
via CAN bus
Leak safeguard through water sensor
Bus system connection per direction: CAN installation cable, max. 1000m total length
WEB
-
based PC
-
link for configuration and for reading out the flush log
Can save 50,000
journal
entries
Datalogging up to 12 million entries
External switch | Switchover
:
• Program 1 (e.g. school-holidays program)
• Program 2 (e.g. school program)
• Maintenance mode (system is blocked)
Menu driven operation in German, English or Dutch
Internal consumption 10 VA
Manual operation of the valves on the MASTER or via WEB browse
r
Ambient temperature range from 0 °C to 50 °C
Protection class IP 54
Surface mounted housing for wall installation
USB interface for updating the firmware, reading out the
journal
and data logging and
for downloading and uploading the configuration file
Network link through network cable (accessory)
Email in case of malfunctions possible

Manual KHS Mini System Control
CAN bus
A
CAN bus
B
CAN bus
A
5. CAN bus system overview
The basic version of the -MASTER/SLAVE- technology inclu es as the smallest solution the
-MASTER 2.0- System Control for water exchanging measures in the sector of rinking water an
for signal evaluation.
Furthermore, the -MASTER 2.0- System Control, using two integrate CAN bus connections, can
trigger up to 62 -SLAVE- controls an one irectly-connecte KHS water exchange group. Up to a
maximum of 31 -SLAVE- controls per CAN-BUS connection of the -MASTER 2.0- can be controlle
per CAN bus connection.
That means up to 63 KHS water exchange groups can be connecte an operate through
the -MASTER/SLAVE- technology. The accumulate total length of one CAN bus connection
can amount to a maximum of 1000 m (total length is thus 2000m).
5.1
Layout variants
Note:
The controllers must be connecte in series, as can be seen in Example 1.
During this, the -MASTER 2.0- System Control can be connecte within the
series (Variant 2) or as a final subscriber (Variant 1). Branches or start
connections, as can be seen in Example 2, are not possible. Furthermore, shorter
cable istances are recommen e .
Example 1: Layout variant, KHS-Mini System Control -MASTER 2.0-
Variant 1
Variant 2
Ill. 5.1 Illustration of a layout variant, KHS Mini System Control -MASTER- system control

Manual KHS Mini System Control 6
CAN bus
A
CAN bus
A
CAN bus
B
CAN bus
A
Example 2: Incorrect layout
Ill. 5.2 View of an impermissible layout variant, KHS Mini System Control -Master 2.0-
5.2
Terminal resistance
Variant 1
Note:
The 120 Ω terminal resistance
must be installe only in the last
control component (-SLAVE-) of
a CAN bus cable line. The -
MASTER control oes not
require a terminal resistance.
Variant 2
Ill. 5.3 Illustration of a CAN bus line with terminal resistor
5.3 Connection of terminal resistor
Attention:
All KHS Mini controls -SLAVE-
are supplie with a 120 Ω
terminal resistor.
For non-terminal -SLAVE-
controls, the resistor must be
remove !
120
120 120
120
Ω
Note:
Note:Note:
Note:
Incorrect layout
Ill. .4 Illustration of the terminal resistor
connection

Manual KHS Mini System Control 7
6.
Assembly
Warning notice:
Allow only certifie electricians to assemble an install electrical equipment.
Danger of fatal electric shock.
Very strong magnetic fiel s can impair the functioning. Interferences can be prevente by following the
installation rules below:
Do not mount the controller an the sensors near in uctive loa s (motors, transformers,
contactors, etc.).
Fee through a separate mains voltage circuit (if necessary, with an a.c. mains filter).
In uctive loa s must be equippe with safeguar s to re uce overvoltages (varistors, RC-
filter).
Attention:
When using the controller together with other evices in one system, check to
see if that causes interference signals to be emitte .
6.1. Wall mounting
The KHS Mini System Control is inten e for wall installation. The housing has 4 each ø 4mm
mounting holes in a clearance of w = 188mm an h = 88mm. A itional imensions are liste in
Chapter 10. To mount, open the cover an screw the evice tightly to the wall. After mounting the
housing, make the require electrical connections.
Ill. 6.1 Illustration of the mounting holes for wall installation

Manual KHS Mini System Control 8
6.2
Electrical installation KHS Mini System Control
The following chapter explains the electrical installation. The electrical connections are ma e through
screwless-type terminals.
6.2.1
Terminal description -MASTER 2.0- and -SLAVE-
Ill. 6.2 Cut-out view of the -MASTER 2.0- an -SLAVE- controller boar with terminals
Illustration: Control boar with terminals
1. Flushing valve switching output 230
________________________
2. Flushing valve voltage output 230 V (only on 68654)
___________
3. Flushing valve N _______________________________________
4. Power supply - LI 230V__________________________________
5. Power supply – N ______________________________________
6. External input 230 V (Function only with -MASTER-)
___________
7. Groun e con uctor PE _________________________________
8. CAN-Bus HIGH 1
______________________________________
9. CAN-Bus LOW 1_______________________________________
10. CAN-Bus GND 1
______________________________________
11. CAN-Bus HIGH 2 _____________________________________
12. CAN-Bus LOW 2______________________________________
13. CAN-Bus GND 2
______________________________________
14 Flow measurement valve - Voltage output 5V ________________
15 Flow measurement valve - Flow input ______________________
16 Flow measurement valve - no function _____________________
17. Flow measurement valve GND
___________________________
18. Pt 1000 Input 1 _______________________________________
19. Pt 1000 Input 2 _______________________________________
20. Pt 1000 Input 3 _______________________________________
21. Pt 1000 Input 4 _______________________________________
22. Drain floating switch (stran s interchangeable)
______________
23. Drain floating switch (stran s interchangeable)
[Terminals 22 an 23 can also be use to connect
the water sensor]
24. Alarm relay voltage input external ________________________
25. External monitor voltage error ___________________________
26. External monitor voltage operation ________________________

Manual KHS Mini System Control 9
6.2.2
Detailed illustration of the terminals for cable entry
Note:
The following illustrations apply to the KHS Mini System Control -MASTER 2.0-
an the KHS Mini System Control -SLAVE-. Please note the prece ing warning
notices:
6.2.2.1
Power supply connection
Power supply: 230 V +/- 15% AC 50/60Hz
Connection: Terminals, L, N, PE
Line fuse max. 16A
BN = brown = L
BU = blue = N
GR = green = PE
Ill. 6.3: Schematic representation of the power supply connection
6.2.2.2
Connection of KHS-VAV Maximum flow isolating ball valve with servo-drive
( igure 686 00)
BN = brown = 1
BK = black = 2
BU = blue = 3
Ill. 6.4: Schematic representation of the connection of the KHS-VAV Maximum flow isolating ball valve
BN
BNBN
BN
BK
BKBK
BK

Manual KHS Mini System Control 10
6.2.2.3
Connection of KHS-VAV Maximum flow isolating ball valve with spring reset servo-drive ( igure
686 01)
BN = brown = 1
BU = blue = 3
Ill. 6.5: Schematic representation of the connection of the KHS-VAV Maximum flow isolating ball
valve with spring reset servo- rive
6.2.2.4
CAN bus connection
Attention:
Follow the notices an instructions in Chapter
5. The twiste pair of the CAN bus cable
shoul be separate an the shiel ing
remove only as far as necessary to assign
the maximum terminals (recommen ation:
max. 4cm).
The shiel ing must be properly bun le with a
heat shrink tube or insulating tape to prevent
contact of the in ivi ual wires of the shiel ing
to the other potentials.
Ill. 6.6: Schematic iagram of the twiste pair

Manual KHS Mini System Control 11
Ill. 6.7: Exemplary illustration of a CAN bus installation from a -MASTER 2.0- an three -SLAVE-
controls
6.2.2.5
Connection of external switch
Attention:
The external connection can only be use
with the KHS Mini System Control -MASTER
2.0-.
Power supply: 230V +/- 15% AC 50/60Hz
Line fuse max. 16A
BK = black = L
Ill. 6.8: Schematic iagram of connection of external switch
Note:
Through the trigger on Terminal 6 you have a facility to switch the KHS Mini
System Control program with external switching processes through a 230V
input. The program switching of the external connection is iscusse in Chapter
8.
230V
L (external voltage)
Switch
CAN bus H an L = 1
Twiste -Pair
H: Stran 1
L: Stran 2
Put on GND cable
shiel ing
The terminal groups 8/9/10 an 11/12/13
are of equal value. For instance the wire
en a can also be connecte to
Terminals 11/12/13 an the wire en b
to Terminals 8/9/10.

Manual KHS Mini System Control 12
6.2.2.6
Connection of KHS-CONTROL-PLUS flow measurement valve ( igure 638 4G)
Connection of KHS-CONTROL-PLUS volume flow measurement valve
BR = +5V DC = 14
BU = Flow = 15
BK = GND = 17
Ill. 6.9: Schematic iagram of connection of KHS-CONTROL-PLUS flow measurement valve
Connection of KHS-CONTROL-PLUS temperature sensor
Attention:
The KHS-CONTROL-PLUS has an internal
Pt 1000, enabling an a itional temperature
measurement. If no temperature
measurement is nee e , insulate an
protect the stran s from contact with the
boar .
GY = grey (green/yellow) = 19
W = white = 20
Ill. 6.10: Schematic iagram of connection of KHS-CONTROL-PLUS volume flow sensor
Note
Attention:
To perform the temperature measurement
through the KHS-CONTROL-PLUS, the
jumper on the boar must be change from
4-wire to 2-wire, see Photo 6.11.
Important comment:
During this measurement, the temperature
measurement is falsifie through the line
resistance. For 10m line-length with
0.34mm² cross-section, the measurement
falsification can amount to approx. + 0.5°C.
Ill. 6.11: Schematic iagram of connection of KHS-CONTROL-PLUS temperature sensor
14 1 17

Manual KHS Mini System Control 13
Connection of KHS-CONTROL-PLUS cable-plug connector
Ill. 6.12: Schematic iagram of the preparation of the sensor top to make cable-plug connection of
the KHS-CONTROL-PLUS
6.2.2.7
Connection of KHS Temperature sensor Pt 1000 ( igure 628 0G)
RD = re = 18
RD = re = 19
W = white = 20
W = white = 21
Ill. 6.13: Schematic iagram of connection of KHS Temperature Measurement Valve Pt1000
6.2.2.8
Connection of KHS drain with overflow monitor ( igure 688 00)
Note:
In the as elivere state, a bri ge stran is
plugge between Terminals 22 an 23. It
must be remove before connecting the
KHS rain.
W = white = 22
BN = brown = 23
Ill. 6.14: Schematic iagram of connection of the KHS rain with overflow monitor
1. Cut off top of cap 2. Route cable through 3. Screw cable to sensor 4. Put on the cap

Manual KHS Mini System Control 14
6.2.2.9
Connection of water sensor ( igure 620 00)
Note:
It is possible to link up to 25 water sensors in
parallel in the etection circuit.
Max. cable length water sensor: < 50m
with stan ar cable
Max. cable length water sensor: > 50m to
500m as shiel e cable, 2x 0.75 mm²,
(e.g. UL-LIYCY)
W = white = 22
BN = brown = 23
Ill. 6.15: Exemplary iagram of the water sensor connection
6.2.2.10
Connection of floating alarm relay
Monitoring example: Errors an mains voltage
failures are reporte with external voltage to the
warning lamp, the warning horn or to the BMS.
Ill. 6.16: Exemplary iagram of the alarm relay
III. 6.16: Exemplary iagram of the alarm relay
Warning light
Alarm horn
e.g input BMS or
alarm relay
External voltage max.
230V, 2A or 24V input

Manual KHS Mini System Control 1
6.3
Installation of network cable
Note:
The supplie network cable has a total length of 2.5m!
Step 1. Open the housing Step 2. Route the cable through bottom
left into the housing
Step 3. Secure cable Step 4. Connect cable to the boar

Manual KHS Mini System Control 16
7. Commissioning
After finishing the wall installation an the electrical installation in accor ance with Chapter 5, apply
the mains voltage of 230V.
Warning notice:
Allow only certifie electricians to assemble an install electrical equipment.
Danger of fatal electric shock.
ATTENTION!
Note:
To simplify the control system an to guarantee flawless installation, fill in the
overview of the system commissioning of the KHS Mini System Control (see
supply pressure, Chapter 13.2) before making the settings. It is man atory to fill
in the supply pressure to be able to take a vantage of the optional factory
support.

Manual KHS Mini System Control 17
8. Configuration
The KHS Mini System Control -MASTER 2.0- can be configure through the internal menu riven
operation or through a web server. Furthermore, the save configurations can be uploa e through a
USB interface to the KHS Mini System Control -MASTER 2.0-.
The sample project shown below shows the basic controller types of the KHS Mini System Control -
MASTER 2.0-. The in ivi ual configuration facilities of the KHS Mini System Control -MASTER 2.0- is
eluci ate using exemplary configurations of the sample project in the following chapters (8.1 an
8.2).
After all units, as escribe in Chapter 6, have been mounte an electrically connecte an a
network connection has been successfully establishe , the actual configuration of the in ivi ual KHS
Mini System Controls starts.
The sample project has one KHS Mini System Control -MASTER 2.0- an six KHS Mini System
Controls -SLAVE-. The system controls shown in Illustration 8.1 are inten e to secure the col -water
line against stagnation an leaks in a fictitious buil ing.
Ill. 8.1 Sample project
Consumers
Sensor cable
230V cable
CAN bus cable
SLAVE 1.6
SLAVE 1.4
SLAVE 1.3
SLAVE 1.
SLAVE 1.2
SLAVE 1.1
MASTER
Valve A3; 1st
UF;
temperature
controlled
Valve
cellar
Volume flow sensor 1;
GF
Temperature sensor 1;
GF
Temperature sensor
3; 1st UF
Volume flow sensor 2;
Cellar
Water sensor 1
-
4; Cellar
Drain + overflow
monitor 1-2; Cellar
Valve B1;
Cellar
Valve C1;
Cellar,
time
controlled
1st UF
GF
Cellar
Valve A2; GF;
time
controlled
C1 B1
Temperature sensor
2;
GF
This manual suits for next models
4
Table of contents
Other Kemper Control System manuals
Popular Control System manuals by other brands

Scientific Games
Scientific Games CPU-4.2.2.X Service manual

Movacolor
Movacolor MC-TC manual

Hologic
Hologic Aquilex Fluid Control System Instructions for use

Whelen Engineering Company
Whelen Engineering Company Traffic Advisor TACTLD1 Installation and operating guide

HESCH
HESCH HE 5731 Compact operating instructions

Rubix
Rubix POD2 user guide

Buderus
Buderus Logamatic 2107 operating instructions

Dickey-John
Dickey-John IntelliAg MVT Operator's manual

ProMinent
ProMinent DULCOMARIN 3 Compact Assembly and operating instructions

Neets
Neets QueBec II installation manual

Nivetec
Nivetec Echo Smart Series Operation & installation manual

CAME
CAME GARD series manual