KEPCO INTELLECT-69 Series Manual

INTELLECT-69
INSTALLATION & OPERATING INSTRUCTIONS
Version V_41
MODELS
INT-69RT
INT-69R
INT-69T
(with RS232 &
RS422 Option)
99318 10/2/98
KESSLER-ELLIS PRODUCTS CO.
10 Industrial Way East
Eatontown, NJ 07724
Telephone: (732) 935-1320
TollFree: (800) 631-2165
Fax: (732) 935-9344
http://www.kep.com

Proprietary Notice
Theinformationcontainedinthispublicationisderivedinpartfromproprietaryandpatentdata.
This information has been prepared for the expressed purpose of assisting operating and
maintenance personnel in the efficient use of the instrument described herein. Publication of
thisinformationdoesnotconveyanyrightstouseorreproduceitortouseforanypurposeother
thaninconnectionwiththeinstallation,operationandmaintenanceoftheequipmentdescribed
herein.
Copyright 1990
Printed in USA. All Rights Reserved.
WARNING!
This instrument contains electronic components that are susceptible to damage by static
electricity. Properhandling* proceduresmustbeobservedduringtheremoval,installation,or
handling of internal circuit boards or devices.
*Handling Procedure
1. Power to unit must be removed.
2. Personnel must be grounded, via wrist strap or other safe, suitable means, before any
printed circuit board or other internal device is installed, removed or adjusted.
3. Printedcircuitboardsmustbetransportedinaconductivebagorotherconductivecontainer.
Boardsmustnot beremovedfromprotectiveenclosureuntil theimmediatetimeofinstallation.
Removedboards must beplaced immediately in protective containerfor transport, storage,or
return to factory.
Comments
This instrument is not unique in its content of ESD (electrostatic discharge) sensitive
components. Most modern electronic designs contain components that utilize metal oxide
technology (NMOS, CMOS, etc.). Experience has proven that even small amounts of static
electricity can damage or destroy these devices. Damaged components, even though they
appear to function properly, may exhibit early failure.
!

TABLE OF CONTENTS
SAFETY INSTRUCTIONS ........................................................... 1
DESCRIPTION & SPECIFICATIONS ..........................................2
MOUNTING .................................................................................3
WIRING........................................................................................4
TYPICAL WIRING HOOKUPS.....................................................5
OPEN COLLECTOR & RELAY OPERATION ............................. 5
PROGRAMMING FLOWCHART .................................................6
DEFINITIONS ..............................................................................7
FRONT PANEL OPERATIONS ...................................................10
PROGRAMMING ......................................................................... 10
SETTING PRESETS & PANEL LOCK.........................................15
RS 232/422 OPERATIONS ......................................................... 16
RS 232/422 WIRING....................................................................20
TROUBLESHOOTING GUIDE .................................................... 21
WARRANTY ................................................................................22
DECODING PART NUMBER ...................................................... 22

THIS PAGE IS BLANK

1
!
SAFETY INSTRUCTIONS
The following instructions must be observed.
• This instrument was designed and is checked in accordance with regulations in force
EN 60950 (“Safety of information technology equipment, including electrical business
equipment”).
A hazardous situation may occur if this instrument is not used for its intended purpose
or is used incorrectly. Please note operating instructions provided in this manual.
• The instrument must be installed, operated and maintained by personnel who have
been properly trained. Personnel must read and understand this manual prior to
installation and operation of the instrument.
• The us of an external line fuse is recommended. Add or replace the external fuse with
the following specified type and rating only:
Input Power Recommended Fuse
115 VAC 100 mA slow blow fuse
230 VAC 50 mA slow blow fuse
12-24 VDC 250 mA slow blow fuse
Disconnect power supply before adding or replacing fuse!
• The manufacturer assumes no liability for damage caused by incorrect use of the
instrument or for modifications or changes made to the instrument.
Symbols Used On Unit
Number Symbol Publication Description
1 IEC 417, No. 5031 Direct current
2 IEC 417, No. 5172 Equipment protected throughout by
DOUBLE INSULATION or REINFORCED
INSULATION (equivalent to Class II of IEC
536–see annex H)
3
!
ISO 3864, No. B.3.1 Caution (refer to accompanying documents)
Technical Improvements
• The manufacturer reserves the right to modify technical data without prior notice.

2
DESCRIPTION & SPECIFICATIONS
Description:
Featuring 6 digits of bright, 7-segment LED displays,
this unit is an integrating totalizer/ratemeter which ac-
cepts analog signal inputs. The unit can be field
programmed to accept 0-20mA, 4-20mA, 0-5V, 0-
10V or 1-5V signals. An optional Square Law input is
available for inputs that require square root extrac-
tion. A 4-20mA output option is available to control
strip recorders or other peripherals. Two assignable
set points are standard for two stage shut off. The
high and low scaling settings are programmable from
the front panel. By pressing the "view" button, the
unit will display: integrated total, rate, peak or valley.
RS-422 or RS-232 serial communications are avail-
able options for data communication with a host com-
puter.
Specifications:
Display: 6 digit, .55" high, LED.
Input Power: 110, 220 VAC ±15% or 12 to 24VDC.
Current: maximum 300 mA DC or 10.0 VA at rated
AC voltage.
Output Power: (AC powered units only) + 24VDC.
@ 50 mA regulated ±5%
Temperature:
Operating: +41°F (5°C) to +130°F (+54°C).
Storage: -40°F (-40°C) to +200°F (93°C).
Memory: EEPROM stores data for ten years if power
is lost.
Reset:
Front Panel: resets displayed values and control out-
puts.
Remote: 4-30 VDC positive edge, resets totalizer and
control outputs.
Control Outputs:
Standard: Open collector sinks 250 mA from 30VDC
when active.
Optional: 2 each Form C SPDT 10Amp @ 120/240
VAC or 28 VDC. (Open collector outputs are also
supplied with 10VDC provided at transistor outputs
through relay coil. If greater than 2mA is used, relay
will remain energized. Applying greater than 10 VDC
may destroy unit. Transistor will sink 100mA in "ON"
state.)
Input:
Standard: Linear 0-20mA, 4-20mA, 0-5V, 0-10V or 1-
5V selectable from the front panel.
Optional: Square Law 0-20mA, 4-20mA, 0-5V, 0-10V,
or 1-5V, is available for inputs that require square root
extraction.
Input Impedance: Current: 100Ω; Voltage: 115KΩ
Calibration: The unit does all of the calibrations inter-
nally. Therearenopotentiometerstoadjustandtheunit
never needs to be removed from the case.
SetPoints:Thetwocontrolsetpointscanbesetatany
number from 0 to 59999. The set point outputs can be
assigned to rate or total. The unit comes standard with
twoopencollectorcontroloutputs. Two5Amp,FormC
relays are optional. The outputs are programmable
from .01 to 599.99 sec or latched until reset when
assigned to the total and a hysteresis (alarm range)
when assigned to the rate.
RateDisplay:Updates5timespersecond,Accurateto
4.5 digits. Set "low" greater than "high" for inverted
display (LINEAR ONLY).
Totalizer: Integrates from the rate reading and accu-
mulates up to 6 digits of total count. The time base
(hours,minutesorseconds)isfieldprogrammablefrom
the front panel.
Analog Out: The unit can be ordered with an optional
4-20mAoutputwhichisproportionaltotheratedisplay.
The high and low settings are programmable from the
front panel. Set "low" greater than "high" for inverted
output. A sinking driver generates a corresponding
linearcurrentthroughthe external devices. The output
updateswitheachupdateoftherate. Accuracyis50uA
worst case. For rated accuracy, load must be con-
nected to the analog output before unit is powered.
Compliancevoltagemustbe3to30VDCnoninductive.
(TheunitcanprovidetheDCsourceaslongasthedrop
acrossthedevicesbeing driven does not exceed 21V).
Programming: Decimal points, Scaling from 0 to
59999 units per selected time base, set points, input
type, security lock code, and assigning outputs are all
programmable from the front panel.
Housing: Standard 1/8 DIN, high impact 94VO plastic
case.
Shipping Weight: 2 lbs.
Overvoltage Protection:
50 V
Overcurrent Protection:
50 mA
Resolution: 14.5 Bits
Accuracy:
RANGE % FS ERROR % FS ERROR
(worst case) (typical)
4-20 mA 0.1% .05%
0-10 VDC 0.2% 0.1%
0-5 VDC .25% .15%
1-5 VDC .25% .15%
Square Law: (above 5% of bottom range) 0.1%
(5V inputs .4%) Worst case over complete range: 2%
Temperature Stability: Will not drift more than 20
parts per million per °C from 5°C to 54°C

3
MOUNTING
HOW TO MOUNT:
Slide the body of the unit through the rubber
gasket. Inserttheunitintothepanel.Slidethe
brackets up the groove to press against the
backofthepanel,asshownin"FIG.A". Insert
the screws into the rear of the brackets.
Tighten the screws evenly and alternately. A
panellessthan.1"maydistortiftheclampsare
screwed too tightly. Do not over tighten! A
normal level of torque is required. Maximum
torque should be 3" pounds.
The panel must be parallel to the bezel to
assure proper seal. Unit seals to NEMA 4/
IP65 if properly mounted.
FIG. A
4.437
(112.7)
2.625
(66.68)
3.925
(99.7)
3.622
(92)
1.772
(45)
.587 4.245
(107.8)
BEZEL
GASKET
CUSTOMER PANEL
Panel Thickness 0.062" (1.5)
to 0.187" (4.7) max.

4
WIRING
WIRING CONNECTIONS
AC / DC CONNECTIONS:
NOTE: Connect power only after other connec-
tions are finished. Do not touch the live AC power
terminals. The unit has been designed with an
isolated AC input, therefore polarity is not a con-
cern for the AC power. The chassis is plastic,
thereforeearthgroundis notused. ForDCopera-
tion, connect +DC to terminal 10 and -DC to
terminal 3.
This Product complies with requirements of the
EuropeanCommunityDirective89/336/EEC[Elec-
tromagnetic Compatibility]. However, electrical
noiseorintenseelectromagneticfieldsinthevicin-
ity of the unit may disturb the microprocessor.
Usersshouldexercisecareandshouldtakeproper
precautions to avoid microprocessor disturbance.
Four common sources of noise are:
1) AC power line noise- The input power lines
should not be common to power lines for motors,
pumps, contactors, etc. If the unit cannot be con-
nected to an electrically clean power source, an
inductive load suppressing device (MOV as
GE#V130LA1 or Resistor Capacitor as Paktron#
.2uf/220ohm @ 400V) can beinstalled. Although
locating the suppressor across the AC supply at
the unit should help, best results are obtained by
connectingthe suppressoracross theleads ofthe
"load" at the device causing the spikes.
2)Inputlinenoise-Thenoiseiscarriedontheinput
and DC ground lines. Make sure the input wires
arenotrunintotheunitinabundlewithpowerinput
lines. Werecommendusingshieldedcable. Con-
necttheshieldtoDCgroundoftheunitand"earth"
at one point in the circuit preferably at the DC
ground terminal of the unit.
3) Output lines- The unit has two open collector
outputs and two optional relay outputs. When
these outputs are used to run external relays or
solenoids, spikes can be generated upon activa-
tion. Thisnoisecanspreadthroughtheinstrument
causingoperatingproblems. IfthesourceisaD.C.
operateddevice,ageneralpurposediode(IN4004)
placed across the solenoid prevents electrical
noise spikes. Connect the cathode (banded side)
to the more positive side of the coil. If the source
isanA.C.operateddevice,useaResistorCapaci-
tor or MOV across the coil.
4)24 VDC outputsupply- Noisecan be generated
on the 24 VDC output supply if it is used to drive
inductive loads or if the current draw exceeds
50mA. Insurethatallinductiveloadshaveadiode
(such as IN4004) across the coil and that the
current does not exceed 50mA.
REAR VIEW
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 15 17 18
RESET IN
ANALOG OUT (SINK)
SIGNAL GND (-DC)
(CURRENT) +I IN
(VOLTAGE) +V IN
NOT USED
+24V OUT
PRESET B COLLECTOR
PRESET A COLLECTOR
+D.C. IN
110 / 220 VAC
110 / 220 VAC
10
11
12
1
2
3
4
5
6
7
8
9
RELAY B
RELAY A
13
14
15
16
17
18
COMMON
N.C.
N.O.
COMMON
N.C.
N.O.
!

5
The open collector and relay outputs trigger when the
total or rate (assignable; see programming step 2)
equals the corresponding Preset (A or B).
Whentheoutputsareassignedtothe"total",theopera-
torcanassignadurationoftime (.01to599.99sec.)that
theoutputwillremainenergized. If0.00isassigned,the
outputwilllatchuntilreset. IfoutputAissetataduration
(other than 0.00), the totalizer will autorecycle when
Preset A is reached. At this time, output B will de-
energize (if it was energized). Preset A is the final
preset and should be set higher than Preset B, when
both outputs are assigned to the total. If output A is set
at a duration other than 0.00 and Preset A is set less
than Preset B, Preset B will be ignored (provided that
theyare bothassignedto total). Thetotalizerwillnever
autorecycle at Preset B.
Whentheoutputsareassignedtothe"rate",theoutputs
can be assigned a hysteresis (alarm range). The
hysteresis is the number of units below the preset that
theoutputwillremainenergized. EXAMPLE:Presetset
@ 100; Hysteresis set @ 10. The output will energize
when the rate equals 100 and de-energize when the
rate falls below 90 (10 below Preset).
NOTE: Iftheinputscalingisinverted,thecontroloutput
functions are inverted (LINEAR ONLY).
TYPICAL WIRING HOOKUPS
OPEN COLLECTOR & RELAY OPERATION
3-Wire 0-10V Transmitter2-Wire 4-20mA Transmitter
Flowmeter
(4-20mATransmitter)
110 VAC
60/50 Hz
•3 - Signal GND (-DC)
•4 - I In + (Current)
.
.
•11 - AC In
•12 - AC In
-
+
Power
Supply
Flowmeter
(4-20mATransmitter)
110 VAC
60/50 Hz
•2 - Analog Out
•3 - Signal GND (-DC)
•4 - I In + (Current)
.
•7 - +24V Out
.
•11 - AC In
•12 - AC In
+
-
-
Strip Chart
Recorder
+
•13 Common
•14 N.C.
•15 N.O.
•16 Common
•17 N.C.
•18 N.O.
Relay A
Relay B
AC Supply
MOV
recommende
for inductive
loads
Neutral
LOAD
-
+
DC
Supply
LOAD
-
+
Diode
recommende
for inductive
loads
Flowmeter
(4-20mATransmitter)
110 VAC
60/50 Hz
•3 - Signal GND (-DC)
•4 - I In + (Current)
.
•7 - +24V Out
.
•11 - AC In
•12 - AC In
+
Strip Chart
Recorder
-
+
-
2-Wire 4-20mA Transmitter
with Multiple Devices Relay Output
2-Wire 4-20mA Transmitter
with Analog Output
4-Wire 4-20mA Transmitter
Flowmeter
(4-20mATransmitter)
110 VAC
60/50 Hz
•3 - Signal GND (-DC)
•4 - I In + (Current)
.
•7 - +24V Out
.
•11 - AC In
•12 - AC In
-
+
Flowmeter
(0-10 V Transmitter)
110 VAC
60/50 Hz
•3 - Signal GND (-DC)
.
•5 - V In + (Voltage)
.
•7 - +24V Out
.
•11 - AC In
•12 - AC In
-
+
signal

6
V41 & V_41 PROGRAMMING FLOWCHART
This symbol indicates any key.
Press this key to step through Menu choices
Press this key to enter displayed value.
PRGM
ENTER
NOTE:
SEVERAL PROGRAMMING SELECTIONS
WILL NOT APPEAR WITH "RATE ONLY"
& "TOTAL ONLY" UNITS
OPTIONS NOT ORDERED WILL NOT APPEAR
IN PROGRAM SELECTIONS
in
p
ut
i
4
-
20
i 0-20
e 0-5
e 1-5
e 0-10
LiN
EA
R
S9RT
RUN MODE
RR
RR
EE
EE
LL
LLAA
AAYY
YYSS
SS
AA
AA
RR
RR
AA
AA
TT
TTEE
EE
AA
AA
tt
tt
oo
oott
tt
HH
HH
YY
YYSS
SS
AA
AA
dd
dd
uu
uurr
rr
AA
AA
XXX.XX
HH
HH
YY
YYSS
SS
BB
BB
XXXXX
dd
dd
uu
uurr
rr BB
BB
RUN MODE
ll
ll
oo
oo
CC
CC
LL
LLCC
CC
AA
AA
LL
LL
LL
LL
LL
LLCC
CC pp
ppgg
gg
CC
CC
oo
oodd
ddee
ee
RUN MODE
ss
ssee
ee
tt
tt
uu
uu
pp
pp
rr
rrDD
DDEE
EECC
CC
SS
SSEE
EE
TT
TT
ll
ll
oo
oo
SS
SSEE
EE
TT
TT
HH
HHiiii
ll
ll
oo
oo
CC
CC
uu
uutt
tt
nn
nnoo
oorr
rr
XX.X
SS
SSEE
EECC
CCSS
SS
NN
NNNN
NNiiiiNN
NNSS
SS
hh
hhoo
oouu
uurr
rrss
ss
RUN MODE
oo
oo
pp
pp
tt
tt
oo
oouu
uutt
tt
ll
ll
oo
oo
oo
oouu
uutt
tt
HH
HHiiii
BB
BB
RR
RR
AA
AA
TT
TTEE
EE
BB
BB
tt
tt
oo
oott
tt
bb
bbaa
aa
uu
uudd
dd
uu
uunn
nniiiitt
tt
XX
PP
PP
LL
LL
iiii
SS
SS
TT
TT
tt
tt
oo
oott
ttaa
aa
ll
ll
RR
RRAA
AATT
TTEE
EE
PP
PPEE
EEAA
AACC
CC
uu
uuaa
aall
llll
llyy
yy
PP
PPRR
RREE
EE AA
AA
PP
PPRR
RREE
EE BB
BB
SS
SSEE
EETT
TT ll
lloo
oo
SS
SSEE
EETT
TT HH
HHiiii
EE
EENN
NNDD
DD
RUN MO
D
PRESS
"PRGM"
TO
ADVANCE
TO NEXT
SELECTION
300
1200
2400
9600
PRGM
ENTER
PRGM
ENTER
PRGM
ENTER
PRGM
ENTER
ENTER
PRGM
ENTER
ENTER
ENTER
PRGM
ENTERENTER
ENTER
ENTER
PRGM
ENTER
PRGM
ENTER
ENTER
PRGM
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
PRGM
ENTER
ENTER
PRGM
ENTER
E
PRGM
XXX.XX
XXXXX
XXXXX
XXXXX
XXXXX
XXXXX
XXXXX
XXXXX
tt
tt
DD
DDEE
EECC
CC
tt
ttff
ffaa
aaCC
CC
tt
tt
ENTER
11
11
11
1100
00
11
1100
0000
00
11
1100
0000
0000
00
PRGM
ENTER
PRGM
PRGM
S
ST
TA
AR
RT
T
*
* For Version V41,
RDEC
appears after
Lo Cut
. In Version V_41
(with space between V & 41) ,
rdeC
appears as shown
For best results, choose the highest resolution possible when
entering the "set lo", "set hi" and "lo cut" values.
Enter the proper decimal location at the "rdec" prompt.
For V41
EXAMPLE: To scale the unit from 0.00 to 100.00, enter 0 for "set
lo" and 10000 for "set hi", enter the decimal at "rdec".
The Version number is displayed at power up.
NOTE: Model INT69T & units with RS232/RS422 option can only
be used with V_41.

7
DEFINITIONS
input
- INPUT; This section of the program menu assigns the type of input the unit will be using (0-20 mA, 4-
20 mA, 0-5 V, 0-10 V, 1-5 V, Linear or square root extraction).
i 4-20
- I 4-20; This sets the unit for a current input of 4 to 20 mA.
i 0-20
- I 0-20; This sets the unit for a current input of 0 to 20 mA.
E 1-5
- E 1-5; This sets the unit for a voltage input of 1 to 5 volts.
E 0-5
- E 0-5; This sets the unit for a voltage input of 0 to 5 volts.
E 0-10
- E 0-10; This sets the unit for a voltage input of 0 to 10 volts.
LiNEAR
- LINEAR; This sets the unit for linear input.
S9RT
- SQUARE ROOT; This sets the unit for square root extraction.
RELAYS
- RELAYS; This section of the program menu sets the control output variables (relays & open collec-
tor).
A RATE
- OUTPUT A FOR RATE; This assigns the A output to the rate.
HYS A
- HYSTERESIS FOR OUTPUT A; This value is the number of units below Preset A that the output will
remain "ON". EXAMPLE: Preset A set at 100, Hys set at 10. Output A will activate (turn on) when the
rate equals 100; Output A will deactivate (turn off) when the rate falls below 90 (10 below Preset A)
A tot
- OUTPUT A FOR TOTAL; This assigns the A output to the totalizer.
DuR A
- OUTPUT A DURATION; This is the duration of time (.01 to 599.99 sec) that Output A will remain
energized. If 0.00 is entered the output will latch until reset. If a value other than 0.00 is entered the unit
will autorecycle at Preset A.
B RATE
- OUTPUT B FOR RATE; This assigns the B output to the rate.
HYS B
- HYSTERESIS FOR OUTPUT B; Same as HYS A.
b tot
- OUTPUT B FOR TOTAL; This assigns the B output to the totalizer.
DuR B
- OUTPUT B DURATION; This is the duration of time (.01 to 599.99 sec) that Output B will remain
energized. If 0.00 is entered the output will latch until reset.
loc
- LOCK; This section of the program menu sets up the lockout type and code.
LC ALL
- LOCK ALL; When this is selected the lockout will lock the program as well as the Presets and reset
button. The presets can be viewed but not changed.

8
lc pg
- LOCK PROGRAM; When this is selected the lockout will lock only the program. The Reset can be
activated and the presets can be viewed and changed.
code
- CODE; This is a 5-digit code which will be used to lock and unlock the front panel.
setup
- SETUP; This section of the program menu sets up the operating variables.
rdec
- RATE DECIMAL LOCATION; This allows the user to program a decimal point for the rate display.
set lo
- SET LOW; This is the rate value for the lowest input (0 or 1 Volts; 4 mA). (i.e. 4 mA = 10 lbs/hr.)
SET Hi
- SET HIGH; This is the rate value for the highest input (5 or 10 Volts; 20 mA). (i.e. 20 mA = 500 lbs/
hr.)
lo cut
- LOW CUT-OFF; This is the lowest rate value to be recognized. All rate readings below this value will
assume the "set lo" value.
nor
- NORMALIZING FACTOR; This is an averaging factor (00.0 to 99.9). Higher settings provide more
normalizing (averaging) for a more stable display. Derived from the equation:
(OLD DATA x "NOR" + NEW DATA)
("NOR" + 1)
SECS
- SECONDS; This tells the unit that the High and Low input values are entered in units per second.
NNiNs
- MINUTES; This tells the unit that the High and Low input values are entered in units per minute.
hours
- HOURS; This tells the unit that the High and Low input values are entered in units per hours.
tdec
- TOTALIZER DECIMAL LOCATION; This allows the user to enter a decimal for the totalizer display.
This decimal is not a dummy decimal and will scale the totalizer display accordingly. (i.e. if the tdec is set
in the tenths position (#####.#), 100 will be displayed as 100.0)
tfact
- TOTALIZER FACTOR; This factor divides the totalizer display by 1, 10, 100 or 1000.
opt
- OPTIONS; This section of the program menu is for setting up optional features (analog out, RS232/422
serial communications).
out lo
- OUT LOW; The displayed rate value at which the unit will output 4 mA (2 lbs./hr = 4 mA out).
out hi
- OUT HIGH; The displayed rate value at which the unit will output 20 mA (2000 lbs./hr = 20 mA out).
BAuD
- BAUD RATE; The baud rate at which the RS232 or RS422 communications will operate.
9600
- 9600 BAUD; This sets the communications at 9600 Baud.
2400
- 2400 BAUD; This sets the communications at 2400 Baud.
1200
- 1200 BAUD; This sets the communications at 1200 Baud.
300
- 300 BAUD; This sets the communications at 300 Baud.

9
unit
- UNIT NUMBER; This assigns the unit an ID number from 1 to 99. This number is to be addressed
when the unit is to be on line. A unit with 0 assigned will never come on line.
P LiST
- PRINT LIST; This sets a list of data that will be transmitted whenever the strobe is activated.
total
- TOTAL COUNT; When this is added to the print list, the unit will transmit the total when the strobe is
activated.
RATE
- RATE; When this is added to the print list, the unit will transmit the present rate value when the strobe
is activated.
PEAK
- PEAK; When this is added to the print list, the unit will transmit the present peak value when the strobe
is activated.
uALLEY
- VALLEY; When this is added to the print list, the unit will transmit the present valley value when the
strobe is activated.
PRE A
- PRESET A; When this is added to the print list, the unit will transmit the Preset A value when the
strobe is activated.
PRE B
- PRESET B; When this is added to the print list, the unit will transmit the Preset B value when the
strobe is activated.
set lo
- SET LOW; When this is added to the print list, the unit will transmit the Set Low value when the
strobe is activated.
set hi
- SET HIGH; When this is added to the print list, the unit will transmit the Set High value when the
strobe is activated.
END
- END; This is the only exit from the P List. If END is not entered the unit will start at the beginning of the
P List again.
PXXXXX
- P; This will appear in the 6th (furthest to the left) digit when viewing the Peak. The peak value is the
highest rate reading that the unit had displayed since the peak had been reset. The peak is not retained
in memory when power is lost.
uXXXXX
- U; This will appear in the 6th (furthest to the left) digit when viewing the Valley. The valley value is
the lowest rate reading that the unit had displayed since the valley had been reset. The valley is not
retained in memory when power is lost.
RXXXXX
- R; This will appear in the 6th (furthest to the left) digit when viewing the Rate.

10
A B C D E
RST
ENTER LOCK PRE A PRE B VIEW PRGM
PROGRAMMING
REMARKS
Thissectionofthemenuisusedtoset
up the type of signal the unit will be
receiving.
Press the PRGM key to step through
choices. Press the RST/ENTER key
to enter the displayed choice.
This section will only appear on units
with the square root extraction option.
Press the PRGM key to toggle be-
tweenthechoicesandpresstheRST/
ENTERkeytoenterthedesiredchoice.
DISPLAY
iNPuT
i 4-20, i 0-20
E 1-5, E 0-5
or
E 0-10
LiNEAR
or
S9RT
PRESS
FRONT PANEL OPERATIONS
Press to RESET
in operating
mode; Press to
"ENTER" in
programming
mode.
Press to view or
change Preset A Press to view or
change Preset B Press to alter-
nately view Rate,
Total, Peak &
Valley.
Press to cycle
through PRO-
GRAM choices;
Press to step
through set up
choices in
program mode.
PRGM
ENTER
ENTER
SETTING
INPUT
STEP
1
Press once to freeze
display. Press any
key to update display
normally.
Press rapidly
(3 times within 5
seconds) to "enter"
LOCK code for panel
lock.

11
PRESS DISPLAY REMARKS
input
RELAYS
A RATE
or
A ToT
(IF TOT SELECTED)
DuR A
(hit any key to view or
change existing dur A
value XX.X)
(IF RATE SELECTED)
HYS A
(hit any key to view or
change existing HyS A
value XXXXX)
B RATE
or
B ToT
(IF TOT SELECTED)
DuR B
(IF RATE SELECTED)
HYS B
STEP
2
SETTING
RELAYS
PRGM
PRGM
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
NOTE: Ifrelay outputs
are not used,
set dur A &
dur B at "0.0"
to prevent the
counters from
resetting at the
presets.
This section of the menu sets up the
open collector outputs and/or relays.
Output A assigned to the rate or total.
Press the PRGM key to toggle be-
tweenchoices,presstheRST/ENTER
key to enter the displayed choice.
dur A = the duration of time (.01 to
599.99 sec) that output A will remain
on or energized. When dur A is dis-
played, hit any key to view or change
dur A. Press the RST/ENTER key to
enter displayed value. When dur A is
set at 0.00,output A will latch until re-
set; when dur A is set other than 0.00
the counter will autorecycle at Preset
A.
Hys(hysteresis)=Thenumberofunits
below the preset that the output will
remain "ON". EXAMPLE: Preset set
@ 100; HyS set @ 10. Output will
activate (turn on) when rate = 100 and
turn off when rate falls below 90 (10
below preset).
Follow instructions for A RATE & A
TOT.
Follow instructions for dur A
Follow instructions for hys A

12
DISPLAY REMARKS
STEP
3
SETTING
LOCK Thissection of the menu is used toset
up the lockout type and code.
LC PG = Locks program but presets
are accessible.
LC ALL= Locks program & presets.
Press the PRGM button to toggle be-
tween choices; Press RST/ENTER to
enter displayed choice.
When CODE is displayed, press any
key to view existing lock code. To
change the code press the key under
each digit to be changed. Press RST/
ENTER to enter displayed value.
input
RELAYS
LoC
LC PG
or
LC ALL
CoDE
Press any key to view
or change the lock
code
PRGM
PRGM
PRGM
ENTER
PRESS
ENTER
Thissectionofthemenuisusedtoset
up important operating variables.
RDEC= rate decimal location; Press
thekeyunderthedigitwiththedesired
location. Pressthe"E"key ifadecimal
is not desired. Press RST/ENTER to
enter the displayed location.
SET LO= Rate value for the lowest
input(0or1V; 4mA).(i.e.4mA=10lbs/
hr.) Key in the desired low value and
press RST/ENTER to enter displayed
value.
SET HI= Rate value for the highest
input (5 or 10V; 20mA).(i.e. 20mA =
500 lbs/hr.). Key in the desired high
value and press RST/ENTER to enter
displayed value.
input
RELAYS
LoC
SETuP
rDEC
SET Lo
Press any key to view
or change existing
value
SET Hi
Press any key to view
or change existing
value
PRGM
PRGM
PRGM
PRGM
ENTER
ENTER
ENTER
CONTINUED ON NEXT PAGE
STEP
4
SETTING
SETUP

13
REMARKS
DISPLAYPRESS LO CUT= Low cut-off; Lowest rate
value to be recognized. All rate read-
ingsbelowthe"cutoff"willassumethe
"setlo"value. Keyinthedesiredvalue
and press RST/ENTER to enter dis-
played value.
NOR= Normalizing (averaging) factor
(00.0to99.9);Keyinthedesiredvalue
and press RST/ENTER to enter dis-
played value. Higher settings provide
more normalizing (averaging) for a
more stable display.
This section tells the unit that the high
& low setting are entered in units per
Minutes,HoursorSeconds. Pressthe
PRGM key to step through choices.
Press RST/ENTER to enter displayed
choice.
TDEC= Totalizer Decimal; Press the
arrow keys to enter in the desired
totalizer decimal. Press RST/ENTER
to enter displayed choice. Entering a
decimalwilladdresolutiontothetotal.
(i.e. tdec=#####.#; 100 will be dis-
played as 100.0)
TFACT= Totalizer Factor; This factor
allows you to divide the totalizer by 1,
10, 100, 1000
Press the PRGM key to step to the
desired factor. Press RST/ENTER to
enter displayed choice.
Lo CuT
Press any key to view
or change existing
value
NoR
Press any key to view
or change existing
value
NNiNS, HouRS
or
SECS
tdec
tfact
Press any key to view
or change existing
value
1
,
10
,
100
or
1000
STEP
4
CONT...
SETTING
SETUP
ENTER
ENTER
ENTER
ENTER
PRGM
ENTER
ENTER
PRGM

14
REMARKS
DISPLAYPRESS
This section of the menu is for setting
up the variables for any options which
were ordered (Analog out or Serial
communications).
OUT LO= The rate value represented
bythe4mAendofthe4-20mAoutput
Key in the desired value and press
RST/ENTERtoenterdisplayedvalue.
OUT HI= The rate value represented
by the 20 mA end of the 4-20 mA
output. Key in the desired value and
press RST/ENTER to enter displayed
value.
BAUD = Baud rate for RS 232 or RS
422 communications option. Press
any key to view existing value.
PressthePRGMkeytoviewavailable
baud rates; Press RST/ENTER to en-
ter displayed value.
UNIT = Unit ID number. Key in the
desired unit number (1-99) and press
RST/ENTERtoenterdisplayedvalue.
P LIST = Print list.
PressRST/ENTERtoadditemstolist;
Press PRGM to remove items from
list.
TOTAL = Total
RATE = Rate
PEAC = Peak
UALLY = Valley
PRE A = Preset A
PRE B = Preset B
SET LO = Low Input Value
SET HI = High Input Value
END = Press RST/ENTER to exit (end) print list;
Press PRGM to recycle through list choices.
PRGM
PRGM
PRGM
PRGM
PRGM
STEP
5
SETTING
OPTIONS
OR
ENTER
PRGM
ENTER
ENTER
ENTER
ENTER
THE PROGRAM SETUP IS COMPLETE! YOU ARE NOW READY TO SET THE PRESETS.
input
RELAYS
LoC
SETuP
oPT
ouT Lo
Press any key to view
or change existing
value
ouT Hi
Press any key to view
or change existing
value
BAuD
Press any key to view
or change existing
value
9600, 1200,
2400
or
300
unit
Press any key to view
or change existing
value
P LiST
Press any key to enter
print list
ToTAL
RATE
PEAK
uALLY
PRE A
PRE B
set lo
set hi
END

15
REMARKS
DISPLAYPRESS
SETTING THE PRESETS & PANEL LOCK
SETTING
THE
PRESETS
PRE A
Press any key to view
or change existing
value
PRE B
Press any key to view
or change existing
value
CoDE
Press any key to enter
the 5-digit lock code.
LoC
or
UN LoC
PRE A = Preset A (Final Preset); The
set point at which output A will trigger.
If the displayed value is not the de-
sired preset, press the key(s) under
the digit to be changed.
PRE B = Preset B (Prewarn); The set
point at which output B will trigger. If
the displayed value is not the desired
preset,pressthekey(s)underthedigit
to be changed.
Key in the lock code (see program-
ming step 3) by pressing the keys
under the digits to be changed. Each
time a key is pressed the digit will
increment one. Press the RST/EN-
TER key to enter the displayed code.
After the code is entered the unit will
displayLOC(unitislocked)orUNLOC
(unit is un-locked). This message will
be displayed for approximately 3 sec-
onds before the unit returns to the run
mode. Ifaninvalidcodeisentered,no
message is displayed; try again.
PRE A
PRE B
ENTER
LOCK
LOCK
LOCK
Press LOCK 3 times within 5 seconds
(If LOCK is pressed once, unit freezes display)
SETTING
THE
LOCK
STATUS
NOTE:
Presets can
be set at any
value form 0
to 59999.

16
This section applies to units which have the
serialcommunicationsinterfaceoption. Upto
99 units can be linked together. Unit status
can be accessed and many menu items can
be entered through the serial port. Data is
transmittedatselectedbaud rates using stan-
dardeight bitASCIIcharactersandone“stop”
bit. Theunitdoesnotcheckortransmitaparity
bit.
UNIT I.D. (DEVICE #)
Each unit in the hookup must be assigned a
unitnumberfrom 1 to99. Thiscanbeentered
through the front panel (see step 5 of the
programmingsection). If “00”isassigned,the
unit can not be brought on line through the
serialport. Theunitswillremaininan“off”high
impedance state until addressed by the as-
signedunitnumber. Onceaunitisaddressed,
do not address another unit until the data has
been sent and any data requested has been
transmitted back.
BAUD RATE
The baud rate is the speed at which data is
transmitted, expressed in bits per second.
Baud rates of 300, 1200, 2400 or 9600 are
available. Select the desired baud rate from
the menu. (see step 5 of the programming
section).
PRINT LIST
The serial interface card is equipped with a
strobe line. When the strobe line is activated
a user selectable set of data (print list) is
transmitted. This transmission can be sent to
acomputerorprinter. Theprintlistconsistsof
eightselectableitems:COUNT,RATE,PEAK,
VALLEY, PRE A, PRE B, LOW SET, HIGH
SET. Thelistcanbeenteredthroughthefront
panel(seestep5oftheprogrammingsection)
or through the serial port (read on).
HELP
A help command has been installed for easy
access of the command and data variables.
When help is needed, type a “?” and press
return (enter) whenever a unit is on line. The
following list will be transmitted:
D#XX:
S Set
E Exam
R Reset
G Lock
L*List
C*Count
R*Rate
P*Peak
V*Valley
A*PreA
B*PreB
L*Lo Set
H*Hi Set
J Lo Out
K Hi Out
N Norm
D Unit
E Input
G Hy/DrA
I Hy/DrB
M Time
T Baud
W Lock
X Meter
Y A Typ
Z B Typ
O Code
F RDec
Q TDec
U TFact
TheunittransmitstheunitID(D#XX)aswellas
thevariablesforthecorrespondingcommands
and data. A “*” indicates that the data is
available for the print list.
RS 232/422 OPERATIONS
This manual suits for next models
3
Table of contents
Other KEPCO Measuring Instrument manuals

KEPCO
KEPCO 52U User manual

KEPCO
KEPCO ES-756 Manual

KEPCO
KEPCO ml-PI8 User manual

KEPCO
KEPCO LEVELtrol-II User manual

KEPCO
KEPCO 520 Series User manual

KEPCO
KEPCO SUPERtrol-1LE User manual

KEPCO
KEPCO 520K Series User manual

KEPCO
KEPCO 528 Series User manual

KEPCO
KEPCO BAT R/T Millennium-S1 User manual

KEPCO
KEPCO MINItrol-S Series Manual