1
8
ON
DIP DIP-SWITCH status Description of operation
DIP 1-2
MOTOR
ON ON Connected gearmotors: swinging series “Jet 24V”, “Linear 24V”, “Intro 24-400” or “Couper24”
ON OFF Connected gearmotors: “Modus” series swing gate
OFF ON Connected gearmotor: sliding series “Dynamos 24V”
OFF OFF Connected gearmotor: swinging series “Minimodus”
DIP 3
STEP
ON Step-by-step command mode: Open / Stop / Close / Stop
OFF Command mode: opening only, if automatic closing is activated
DIP 4
AUTO
ON Automatic closing activated (time set with the “Pause” trimmer)
OFF Automatic closing deactivated
DIP 5
PHO2
ON Safety devices connected to “PHO2” set as photocells (movement stopped during opening and
closing)
OFF Safety devices connected to “PHO2” set as edges (reverse of opening movement)
DIP 6
HAZ
ON Intermittent warning light power supply
OFF Fixed warning light power supply
DIP 7
FAST
ON Immediate re-closing after intervention of “PHO1” photocells
OFF No intervention of the photocells during re-closing
DIP 8
FUNC
SWINGING
(see DIP 1-2)
ON Ram function enabled
OFF Ram function disabled
SLIDING
(see DIP 1-2)
ON Reverse opening direction (the system must be programmed afterwards)
OFF Reverse opening direction (the system must be programmed afterwards)
A variation of DIP 1-2 “MOTOR” and DIP 8 “FUNC” (if the
control unit is set to sliding gate) will not become effective
until a new gate path is programmed (Paragraph 5).
DIP1-2 “MOTOR”:
Set DIP 1 and 2in relation to the connected gearmotor. Depending
on the selected gearmotor, the control unit may set backjumps at
the end of the gate’s travel and vary the power supply to the motors.
DIP3 “STEP”:
If the dip-switch is put to ON, the step-by-step operating mode is
activated. At every start pulse (wired or via transmitter), the control
unit performs an action. Starts the motor if the automation system is
stopped, and stops it if it is moving. If the “STEP” dip-switch is put
to OFF, the OPEN FULLY/PAUSE/CLOSE FULLY/STOP operating
mode is activated (apartment block). The control unit only accepts
commands (either wired or via transmitter) for the opening phase.
Starts again from zero with the set delay when the automation sys-
tem is open. With the automation in the opening phase, it continues
to open, and with the system in the closing phase it reopens fully.
The automation can re-close with the time set through the “PAUSE”
trimmer, if the “AUTO” dip-switch is set to ON. If not, it is necessary
to give a START command (either wired or via transmitter) with the
automation fully open.
DIP4 “AUTO”:
If the dip-switch is put to ON, the automatic re-closing function is
activated. The control unit automatically closes the leaves after the
time set through the “PAUSE” trimmer (see Paragraph 3.2). If the
“AUTO” dip-switch is put to OFF, the automatic re-closing function
is deactivated. To close the leaves, therefore, a command must be
given (either wired or via transmitter).
DIP5 “PHO2”:
If the dip-switch is put to ON, the safety devices for the opening
phase (see Paragraph 8.6) are set as photocells: they intervene dur-
ing both the opening and closing phases, by locking the movement
of the leaves and resuming the movement once they are released.
2
DIP SWITCHES
(Paragraph 3.1)