• Connect one end of the negative DC input cable to the Power Inverter DC negative (black)
M5 terminal.
• Connect the other end of the negative DC input cable to the battery negative terminal.
• Make sure the Disconnect Switch is in the OFF position.
• Connect one end of the positive DC input cable to the Inverter DC positive (red) M5
terminal.
• Connect the other end of the positive DC input cable to one of the terminals of the
Disconnect Switch.
• Connect a DC input cable between the other terminal of the Disconnect Switch and one
side of the terminal of the fuse holder.
• Connect a DC input cable between the other terminal of the fuse holder and the battery
positive terminal.
• Install the selected fuse to the fuse holder.
• Turn Disconnect Switch to ON position.
Remote Switch (optional) Connection:
• The unit comes with a Remote port and an optional KISAE ‘Remote Switch’ accessory
(RM1201-00) can be used to turn unit On and OFF remotely. To install the ‘Remote
Switch’, just connect the switch’s RJ12 plug to the RJ12 ‘Remote’ port located at the
Front AC panel of the Power inverter. Please note polarity when connecting the plug.
• The Power ‘On/Off’ push button on the remote share the same function as the green
‘On/Off’ button on the main unit.
• With ‘Power Save’ Function set to OFF, the ‘Power’ indicator will remain solid ON when
AC Output Power is available and will be OFF when the unit has shutdown.
• With ‘Power Save’ Function set to ON, the ‘Power’ indicator will be flashing when AC
Output Power is available and will be OFF when the unit has shutdown.
Use of the Ignition Start Function on unit:
• An ‘Ignition Start’ port is located at the Front AC Panel of the unit using a ¼” width spade
terminal. This port is used for turning the unit On and OFF using a +12V signal. An
insulated female connector is required to connect to the port.
• Connecting to +12V will turn ON the unit and removing the +12V signal will turn OFF the
unit.
Power Inverter Test after installation:
• Press and hold the green ‘On/Off’ button on the unit to turn ON the unit.
• Check that the ‘Status’ indicator turns to solid green.
• Plug in a small AC load like a 40W table lamp or small appliance to the AC socket to verify
AC is available.
• The unit is successfully installed and functioning properly.
4. UNIT OPERATION
WARNING: RISK OF EQUIPMENT DAMAGE
Do not connect an AC power source like utility power or generator to the AC outlets of the unit.
Turn ON and OFF the unit
• Press and hold the green ‘On/Off’ button for about a second to turn ON the unit and
‘Status’ indicator will turn on.
• Press again the green ‘On/Off’ button to turn OFF the unit and the ‘Status’ indicator will
turn off.
Understanding the ‘Power Save’ function
The unit can pre-set with ‘Power Save’ function ON or OFF. If unit is turned ON with ‘Power
Save’ function pre-set to ON, with >10W AC load connected to the unit, the unit will provide
continuous AC Output and with <10W AC Load connected to the unit or with AC Load
changing from >10W to < 5W, the AC Output will change from continuous to pulsing AC
Output every 5 seconds.
The unit is default set to ‘Power Save’ OFF. To change the ‘Power Save’ function from OFF
to ON or switch back from ON to OFF, press and hold the green ‘On/Off’ button for more
than 5 second until the ‘Status’ light quickly flashes three times and the alarm beeps for
more than 2 seconds.
Understanding the ‘Status’ indicator
Function ‘Status’ Indicator Condition
Solid Green Unit is normal and continuous AC Output is
available
Power
Save
Function
‘OFF’ Solid Green with alarm
beep every 2 seconds Unit is detected with either DC Over/Under
Voltage or Over Temperature warning and
continuous AC Output is still available
Flashing Green Unit is normal and AC Load connected is
>10W
Flashing between Amber
and Red Unit is normal and AC Load connected is
<10W or AC Load connected is reduced from
>10W to < 5W
Flashing Green and alarm
beep every 2 seconds Unit is detected with either DC Under Voltage
or Over Temperature warning and
AC Load connected is > 10W
Power
Save
Function
‘ON’
Flashing between Amber
and Red and alarm beep
every 2 seconds
Warning detected with either DC Under
Voltage or Over Temperature
AC Load connected is <10W or AC Load
connected is reduced from >10W to <5W
Power
Save
Function
is either
‘ON’ or
‘OFF’
Solid Red with alarm
beep every second No AC Output as unit had shutdown due to
either DC Over/Under Voltage or AC Output
Overload or Over Temperature occurs.
See more details on “Understanding the
Warning and Shutdown Condition” in this
manual
Understanding the Warning and Shutdown Condition
Over Temperature Warning: Unit internal temperature is high. Unit requires better
ventilation.
DC Under Voltage Warning: DC Input Voltage is low and is close to the under-voltage
shutdown limit. Checking on battery voltage or battery connection is required.
Over Temperature Shutdown: Reduce the AC load and provide more ventilation to the unit.
Unit will automatically restart when the internal temperature of the unit cools down.
DC Over Voltage Shutdown / DC Under Voltage Shutdown: Check the battery voltage. On
the first 30 seconds, AC Output will resume when battery voltage is corrected to the unit
operating range. If the battery voltage shutdown condition is ignored, the unit will latch
OFF completely after 30 seconds and restart the unit using green ‘On/Off’button is
required after the battery voltage is corrected.
AC Output Overload Shutdown: Check AC Load connected to the unit. AC Output is short
circuited or AC Power draw by the load is beyond the unit’s limit. The indicator and alarm
will beep for about 30 seconds before it latched OFF completely. Restart the unit using the
green ‘On/Off’button is required after the AC Load condition is corrected.
USB Port on unit
With unit on, 2.1A 5V USB is provide on the 5V USB port. This can be used to charge 5V
USB Powered devices.
Understanding the Fan Operation
The fan on the unit is AC load and internal temperature activated. It will automatically turn on
when AC output power exceeds the pre-set values (~ 200W) and turn off when AC output
power is reduced to 150W. It will also automatically turn on when it senses the internal
components have reached to around 80°C (176°F) and turn off when temperature drops to
below 60°C (140°F).
AC Load on Power Inverter
Although the Power Inverter can provide high surge power up to two times the rated output
power, some appliances may still trigger on the unit protection system during start up or
surge period. A higher power inverter is required for those appliances.
Estimated Run time on Load
Following run time is an estimate based on using a 12V-120AH battery bank. Actual runtime
may vary. Load Consumption Estimate Run time
Cordless Phone 5W 150 hrs
Clock / Radio 8W 100 hrs
Table Lamp 40W / 60W 27 hrs / 18 hrs
Small Freezer (8.8 cu. ft.) 80W 15 hrs
20” LCD TV 100W 11.5 hrs
Flooded Light 500W 1 hr
Sump Pump (1/2 hp) 350W Not applicable (surge too high)
5. TROUBLESHOOTING
Problem Symptom Solution
The unit is off Turn unit ONNo AC output and
‘Status’ light is OFF No power to
inverter Check fuse or the Disconnect switch (if
installed) is either blown or turned OFF
‘Status’ indicator is
in green or flashing
between amber and
red (alarm beeps
every 2 seconds)
Unit has detected
a warning and is
going to shutdown
Verify the warning condition and make
adjustment. See “Understanding the
‘Status’ indicator”in this manual
‘Status’ indicator is
in red (alarm beeps) Unit has shutdown Check unit condition and make correction.
See “Understanding the ‘Status’
indicator” in this manual
6. SPECIFICATIONS
Note: Specifications are subject to change without notices.
Specifications SW1206 SW1206i
Inverter
AC Output Power 600 Watt
AC Output Current 5.0A 2.6A
AC Surge Power 1200 Watt
AC Output Voltage 120Vac / 60Hz 230Vac / 50Hz
AC Output Waveform True Sinewave (<5% THD)
DC Input Voltage 12.5 VDC
No Load Current (Power Save OFF) < 0.8 A
No Load Current (Power Save ON) < 0.2 A
DC Operating Range 10.5 – 15.9 VDC
Under Voltage Alarm 11.0 VDC
Under Voltage Alarm Recovery 11.3 VDC
Under Voltage Shutdown 10.5 VDC
Under Voltage Recovery 12.0 VDC
Over Voltage Shutdown 15.9 VDC
Over Voltage Recovery 15.0 VDC
Power Save OFF >10W
Power Save OFF to ON ~ 5W
AC Output Socket GFCI EU, AU, UK
Safety and Environmental
Agency Markings cETLus* CE LVD, EMC,
Operating Temp. 0℃to 40℃(32℉to 104℉)
Storage Temp. -20℃to 60℃(-4℉to 140℉)
Relative Humidity 5 - 90% non-condensing
Operating Altitude Up to 6,560ft (2000 m) above sea level
Weights and Dimensions
Weights 2.0 kg 2.0 kg
Dimensions 9-3/8 x 6-7/8 x 3-1/2” (237 x 175 x 89 mm)
* The product conforms to UL STD.458 and is certified to CSA STD. C22.2 No.107.1
7. WARRANTY
One Year Limited Warranty
The limited warranty program is the only one that applies to this unit, and it sets forth all the
responsibilities of KISAE. There is no other warranty, other than those described herein. Any
implied warranty of merchantability of fitness for a particular purpose on this unit is limited in
duration to the duration of this warranty.
This unit is warranted, to the original purchaser only, to be free of defects in materials and
workmanship for one year from the date of purchase without additional charge. The warranty
does not extend to subsequent purchasers or users.
Manufacturer will not be responsible for any amount of damage in excess of the retail
purchase price of the unit under any circumstances. Incidental and consequential damages are
specifically excluded from coverage under this warranty.
This unit is not intended for commercial use. This warranty does not apply to damage to units
from misuse or incorrect installation/connection. Misuse includes wiring or connecting to
improper polarity power sources.
Return/Repair Policy:
If you are experiencing any problems with your unit, please contact our customer service
retail store. After speaking to a customer service representative, if products are deemed non-
working or malfunctioning, the product may be returned to the purchasing store within 30 days
of original purchase. Any defective unit that is returned to manufacturer within 30 days of the
date of purchase will be replaced free of charge. If such a unit is returned more than 30 days
but less than one year from the purchase date, manufacturer will repair the unit or, at its option,
replace it, free of charge. If the unit is repaired, new or reconditioned replacement parts may
be used, at manufacturer’s option. A unit may be replaced with a new or reconditioned unit of
the same or comparable design. The repaired or replaced unit will then be warranted under
these terms for the remainder of the warranty period. The customer is responsible for the
shipping charges on all returned items.
Limitations:
This warranty does not cover accessories, such as adapters and batteries, damage or defects
result from normal wear and tear (including chips, scratches, abrasions, discoloration or fading
due to usage or exposure to sunlight), accidents, damage during shipping to our service facility,
alterations, unauthorized use or repair, neglect, misuse, abuse, failure to follow instructions for
care and maintenance, fire and flood.
If your problem is not covered by his warranty, call our Customer Service Department
Service Contact Information