Kisae 120V Series User manual

Inverter-Charger
120V Series
12V-2000W-80A (BIC1220080)
12V-3000W-100A (BIC1230100)
24V-2000W-40A (BIC2420040)
24V-3000W-50A (BIC2430050)
230V Series
12V-2000W-80A (BIC1220080i)
12V-3000W-100A (BIC1230100i)
24V-2000W-40A (BIC2420040i)
24V-3000W-50A (BIC2430050i)
Owner’s Manual

Page 2
For safe and optimum performance, the Inverter-Charger must be used properly. Carefully read and
follow all instructions and guidelines in this manual and give special attention to the CAUTION and
WARNING statements.
PLEASE KEEP THIS MANUAL FOR FUTURE REFERENCE
Disclaimer
While every precaution has been taken to ensure the accuracy of the contents of this guide,
KISAE Technology assumes no responsibility for errors or omissions. Note as well that
specifications and product functionality may change without notice.
Important
Please be sure to read and save the entire manual before using your KISAE Sinewave
Inverter-Charger. Misuse may result in damage to the unit and/or cause harm or serious
injury. Read manual in its entirety before using the unit and save manual for future reference.
Model Numbers
120VAC Series :
BIC1220080 Inverter-Charger 12V / 2000W / 80A - 120VAC (NEMA5-20)
BIC1230100 Inverter-Charger 12V / 3000W / 100A - 120VAC (NEMA5-20)
BIC2420040 Inverter-Charger 12V / 2000W / 40A - 120VAC (NEMA 5-20)
BIC2430050 Inverter-Charger 12V / 3000W / 50A - 120VAC (NEMA 5-20)
230VAC Series :
BIC1220080i-EU Inverter-Charger 12V / 2000W / 80A- 230VAC (Schuko Socket - CEE 7/4)
BIC1220080i-UK Inverter-Charger 12V / 2000W / 80A- 230VAC (British Socket - BS1363)
BIC1220080i-AU Inverter-Charger 12V / 2000W / 80A - 230VAC (Australia Socket –NS/NZS3112)
BIC1230100i-EU Inverter-Charger 12V / 3000W / 100A - 230VAC (Schuko Socket - CEE 7/4)
BIC1230100i-UK Inverter-Charger 12V / 3000W / 100A - 230VAC (British Socket - BS1363)
BIC1230100i-AU Inverter-Charger 12V / 3000W / 100A - 230VAC (Australia Socket –NS/NZS3112)
BIC2420040i-EU Inverter-Charger 24V / 2000W / 40A - 230VAC (Schuko Socket - CEE 7/4)
BIC2420040i-UK Inverter-Charger 24V / 2000W / 40A- 230VAC (British Socket - BS1363)
BIC2420040i-AU Inverter-Charger 24V / 2000W / 40A - 230VAC (Australia Socket –NS/NZS3112)
BIC2430050i-EU Inverter-Charger 24V / 3000W / 40A - 230VAC (Schuko Socket - CEE 7/4)
BIC2430050i-UK Inverter-Charger 24V / 3000W / 40A- 230VAC (British Socket - BS1363)
BIC2430050i-AU Inverter-Charger 24V / 3000W / 40A - 230VAC (Australia Socket –NS/NZS3112)
Document Part Number
MUBIC Rev A
Service Contact Information
Email: info@kisaetechnology.com
Phone : 1-877-897-5778
Web : www.kisaepower.com
WARNING: This product can expose you to chemicals, including Di (2-ethylhexyl) phthalate (DEHP) which is known
to the State of California to cause cancer, birth defects or other reproductive harm. For more information, go to
www.p65warnings.ca.gov
ADVERTENCIA Este producto puede exponerlo a productos químicos, incluidos Di (2-etilhexil) ftalato (DEHP) que
el estado de California sabe que causa cáncer, defectos de nacimiento u otros daños reproductivos. Para obtener
más información, vaya a www.p65warnings.ca.gov

Page 3
IMPORTANT SAFETY INFORMATION
This section contains important safety information for the Sinewave Inverter-Charger. Before using
the unit, READ ALL instructions and cautionary markings on or provided with the unit, and all
appropriate sections of this guide.
The Sinewave Inverter-Charger contains no user-serviceable parts. See Warranty section for how to
handle product issues.
DANGER: Fire and/or Chemical Burn Hazard
•Do not cover or obstruct any air vent openings and/or install in a zero-clearance compartment.
DANGER: Failure to follow these instructions can result in death or serious injury
•When working with electrical equipment or lead acid batteries, have someone nearby in case of an
emergency.
•Study and follow all the battery manufacturer’s specific precautions when installing, using and
servicing the battery connected to the inverter.
•Wear eye protection and gloves.
•Avoid touching your eyes while using this unit.
•Keep fresh water and soap on hand in the event battery acid comes in contact with eyes. If this
occurs, cleanse right away with soap and water for a minimum of 15 minutes and seek medical
attention.
•Batteries produce explosive gases. DO NOT smoke or have an open spark or fire near the system.
•Keep unit away from moist or damp areas.
•Avoid dropping any metal tool or object on the battery. Doing so could create a spark or short circuit
which goes through the battery or another electrical tool that may create an explosion.
WARNING: Shock Hazard. Keep away from children!
•Avoid moisture. Never expose unit to snow, water etc.
•Unit provides high voltage AC, treat the AC output socket the same as regular wall AC sockets at
home.
WARNING: Explosion hazard!
•DO NOT install the unit near flammable fumes or gases (such as propane tanks or large engines).
•AVOID covering the ventilation openings. Always operate unit in an open area.
•Prolonged exposure to high heat or freezing temperatures will decrease the working life of the unit.
•DO NOT connect AC power source like utility power or generator to the AC outputs of the unit. It will
damage the unit and may cause fire. Feeding AC to the AC output of the unit is not covered by
warranty.
•The 12V DC unit is designed for use on 12V House Battery System only. Use on a higher house
battery system will damage the unit and lead to unit explosion.
•The 24V DC unit is designed for use on 24V House Battery System only. Use on a lower house
battery system will damage the unit and lead to battery explosion.
FCC and EMC INFORMATION
This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the FCC Rules (for 120V models) and comply with the CE EMC Standard on
230V models. These limits are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment generates, uses, and can radiate radio frequency energy
and, if not installed and used in accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
•Re-orient or re-locate the receiving antenna.
•Increase the separation between the equipment and the receiver.
•Consult the dealer or an experienced radio/TV technician for help.
LIMITATIONS ON USE
Do not use in connection with life support systems or other medical equipment or devices.

Page 4
Table of Contents
1. INTRODUCTION ............................................................................................. 5
2. PRODUCT DESCRIPTION.............................................................................. 5
3. UNDERSTANDING THE UNIT........................................................................ 6
4. INSTALLING THE UNIT................................................................................ 10
5. UNIT OPERATION......................................................................................... 13
6. TROUBLESHOOTING .................................................................................. 24
7. SPECIFICATIONS......................................................................................... 25
8. WARRANTY .................................................................................................. 27

Page 5
1. INTRODUCTION
Thank you for purchasing the KISAE Sinewave Inverter-Charger. With our state of the art, easy to
use design, this product will offer you reliable service by providing True Sinewave AC power for your
home, cabin, boat, RV or trailer and recharge your battery automatically when utility AC is available.
The Sinewave Inverter-Charger can run many AC-powered appliances when you need AC power
anywhere. The multi-stage battery charger will charge different type of batteries. The built-in transfer
switch will automatically switch the load to the battery power when the utility power is interrupted.
This manual will explain how to use this unit safely and effectively. Please read and follow these
instructions and precautions carefully.
2. PRODUCT DESCRIPTION
The Sinewave Inverter-Charger includes the items listed below.
•Inverter-Charger base unit
•Universal Multi-Function Display
•25’ RJ12 Display Cable
•Owner’s manual
Series
Model No.
Rating
AC Output Types
Inverter
Charger
By-Pass
12V
120VAC
BIC1220080
2000W
12V-80A
30A
•20A GFCI
•Hardwire
BIC1230100
3000W
12V-100A
30A
24V
120VAC
BIC2420040
2000W
24V-40A
30A
BIC2430050
3000W
24V-50A
30A
12V
230VAC
BIC1220080i
2000W
12V-80A
16A
•EU: Schuko-CEE 7/4)
UK: British- BS1363
AU: Australia-NS/NZS3112
•Hardwire
BIC1230100i
3000W
12V-100A
16A
24V
230VAC
BIC2420040i
2000W
24V-40A
16A
BIC2430050i
3000W
24V-50A
16A

Page 6
3. UNDERSTANDING the UNIT
WARNING: It is recommended that all wiring be done by a certified technician or electrician to ensure
adherence to the applicable electrical safety wiring regulations and installation codes. Failure to follow
these instructions can damage the unit and could also result in personal injury or loss of life.
CAUTION: Before beginning unit installation, please consider the following:
•The unit should be used or stored in an indoor area away from direct sunlight, heat, moisture or
conductive contaminants.
•When placing the unit, allow a minimum of three inches of space around it for optimal ventilation.
Main Unit Front
Main Unit Rear
Display

Page 7
Typical Wiring Block Diagram of Inverter-Charger:
○
aBattery Bank
•The use of deep cycle battery is highly recommended for power inverter application
•For battery size, you need to identify how much and for how long the inverter has to provide AC
power to the loads (based on Amps x hour energy consumption). It is recommended to
purchase as much battery capacity as possible.
AC Load
Estimated run time on 12V Battery
bank on 12V Input Models
Estimated run time on 24V Battery
bank on 24V Input Models
12V/120AH
12V/240AH
24V/60AH
24V/ 120AH
50 W
22 hrs.
44 hrs.
22 hrs.
44 hrs.
100 W
11.5 hrs.
23 hrs.
11.5 hrs.
23 hrs.
200 W
5 hrs.
11 hrs.
5 hrs.
11 hrs.
500 W
2 hrs.
4 hrs.
2 hrs.
4 hrs.
1000 W
49 mins
2 hrs.
49 mins
2 hrs.
1500 W
27 mins
1 hr
27 mins
1 hr
2000 W
15 mins
49 mins
15 mins
49 mins
2500 W
N.R.
37 mins
N.R.
37 mins
3000 W
N.R.
27 mins
N.R.
27 mins
N.R. - Not Recommended. Based on more than 2C discharged on battery capacity.
Estimated run times are for reference use only. Actual run times may vary on battery type used.
○
bDC Fuse or Circuit Breaker
•DC-rated fuse or DC-rated circuit breaker connected along the DC positive line is required.
Fuse/Circuit
Breaker Rating
12V 2000W
System
12V 3000W
System
24V 2000W
System
24V 3000W
System
300Adc
450Adc
150Adc
225Adc
•Based on the size of the Battery Bank, determine the overall short circuit current rating of the
battery bank from the battery manufacturer. The fuse or circuit breaker has to be able to
withstand the short circuit current that can be generated by the battery bank. Typically, an
ANL/Class-T fuse with fuse holder is used.
○
c DC Disconnect Switch
•A DC Disconnect Switch connected along the DC positive line is recommended. The rating of
the switch is with the same or higher rating of the selected fuse or circuit breaker. Use ignition
protected switches when required by local codes.
•This switch is used to disconnect the positive of the battery bank to the unit’s positive terminal
during maintenance/repair service, when not in-use, or when troubleshooting. It could also be
an A/ B/A+B/OFF type switch to select either one of two or both (paralleling) battery banks (if
available).

Page 8
○
d DC Input
•All DC Input Wires should be insulated multi-strand low resistance wires.
•The DC wires must be copper and rated 105℃minimum.
Model
Thinnest DC Input Wires Gauge Used
≤ 5 feet (Recommended)
≤ 7.5 feet
≤ 10 feet
12V 2000W series
AWG # 2/0
AWG # 3/0
250 kcmil
12V 3000W series
AWG # 4/0
300 kcmil
400 kcmil
24V 2000W series
AWG # 1/0
AWG # 2/0
AWG # 3/0
24V 3000W series
AWG # 2/0
AWG # 3/0
AWG # 4/0
The typically recommended wire length is limited to 5 feet or less for each of the positive and the negative. For longer
wires, a proportionally thicker gauge is required to compensate for additional voltage drop
CAUTION: These guidelines assume you are using the DC supplied cable and fuse sizes
recommended in this manual. The use of a thinner gauge in the DC wires may cause the
inverter to trigger the under-voltage shut down under heavy load conditions. It may also melt the
wire insulation and catch fire, resulting in death or serious injury. The choice of the wire gauge
should also match or exceed the ampacity rating of the DC fuse being used.
○
e Chassis DC Grounding
DANGER: The unit chassis has to be grounded properly before use. Never operate the unit
without proper grounding. Failure to do so will result in death or serious injury.
Model
Thinnest Wire Gauge Used
Recreation Vehicle
Marine
12V 2000W series
AWG # 8
AWG # 1/0
12V 3000W series
AWG # 3/0
24V 2000W series
AWG # 0/0
24V 3000W series
AWG # 1/0
- These guidelines assume you are using the DC supplied cable and fuse sizes recommended in this manual. If
you are using different sizes, refer to the applicable installation code for the DC grounding detail.
- In marine applications, the main AC-DC ground bonding may require galvanic isolators to avoid galvanic
corrosion. Check your local electrical codes (i.e. NEC, UL, ABYC...).
○
fAC Input Source
An AC source is usually grid power or an AC Generator. The acceptable AC Input voltage rage
and frequency are as shown:
Model
Acceptable AC Input Voltage Range
Acceptable AC Input Frequency Range
120VAC series
90 - 140 VAC
30 - 100 Hz
230VAC series
180 - 260 VAC
30 - 100 Hz
An automatic or manual AC source selector switch can be used to switch between the multiple
sources of shore power to the unit. Usually the AC Main Panel includes a main circuit breaker
which serves as over-current protection and as a disconnect for the AC shore power supply line.
Additional AC circuit breakers serve individual circuits and one of the AC circuit breakers will serve
the unit. During By-Pass mode, the AC Input source will serve the AC Output Load and also the
AC Input current for the charger when it is used to charge the battery.
Model
AC Input Circuit Breaker to serve
the unit
AC Input Wire
120VAC series
30A (maximum)
#10 AWG (minimum)
230VAC series
16A (maximum)
#14 AWG (minimum)
- Follow the electrical and/or building code when you choose AC Branch Breaker and AC Input wire Size. Connect the
unit to any AC Input Source
- Smaller size AC Input wire can be used when a lower amperage rated AC Input Circuit Breaker is used from upstream
to feed the unit.
The unit is designed to acceptable non-Sinewave AC Input Source generated by generator.
○
gAC Hardwire Output
An AC Sub-Panel is recommended to incorporate an AC output circuit breaker and breakers for
individual load circuits.

Page 9
○
hAC Output Socket and ○
i AC Output Thermal Breaker:
A single AC Output socket is provided for direct AC output from the unit. An over-current
protective device (thermal breaker) is connected in series with the AC Output Socket to avoid over
current being withdraw from the AC Output socket.
Model
AC Output Socket Type
AC Output Thermal Breaker
120VAC series
NEMA 5-20 GFCI
20A
230VAC series
EU: Schuko-CEE 7/4)
16A
UK: British- BS1363
13A
AU: Australia-NS/NZS3112
10A
Model
By-Pass Mode Current (Maximum)
Inverter Mode Current (Maximum)
Total AC
Output
AC Output
Hardwire
AC Output
Socket
Total AC
Output
AC Output
Hardwire
AC Output
Socket
2000W/120VAC
30A
30A
20A*
16.7A
16.7A
16.7A
3000W/120VAC
30A
30A
20A*
25A
25A
20A *
2000W/230VAC
16A
16A
EU: 16A*
UK: 13A*
AU: 10A*
8.7A
8.7A
EU: 8.7A**
UK: 8.7A**
AU: 8.7A**
3000W/230VAC
16A
16A
EU: 16A*
UK: 13A*
AU: 10A*
13A
13A
EU: 13A**
UK: 13A**
AU: 10A*
* Limited by AC Output Thermal Breaker connected in series with the AC Output Socket.
** Limited by Inverter maximum AC Output Current during inverter mode.
○
jDisplay Port
The port is used to connect to the Multi-Function Display of the unit.
○
kMulti-Function Display
The display is used to provide unit information and for setting and programming the unit.
○
lBTS Port
The port is used for connecting to the optional Battery Temperature Sensor. The thermistor
installed inside the ring terminal is used to measure the battery terminal temperature and the unit
will make compensation on battery charging voltage for battery charging.
○
mIgnition Start Port
The port is used for connecting to the ignition start signal from vehicles to control the operation of
the inverter.
* Program Port (not shown on wiring block diagram)
This USB port is for internal use only. This CANNOT be used for charging Smart phones or USB
powered devices. Mis-use of this port can potentially damage the unit and is not covered by the
warranty. This port is located on the Display Panel and is also located below the Ignition Start Port
on 2000W models.
* CAN BUS Port (not shown on wiring block diagram)
This is for unit communication through CAN interface. Mis-use on this port can potentially damage
the unit and is not covered by the warranty. This port is located on the Display Panel and is also
located below the Ignition Start Port on 2000W models.

Page 10
4. Installing the Unit
WARNING: Explosion hazard!
•DO NOT install the unit near flammable fumes or gases (such as propane tanks or large engines).
•AVOID covering the ventilation openings. Always operate unit in an open area.
Choosing the location:
The unit should only be installed in locations that meet the following requirements:
•Do not allow water or other fluids to drip or splash on the unit.
•Environment temperature should be between -4 °F and 104 °F (-20 °C and 40 °C)
•Allow at least three inches of clearance around the unit. The more clearance for ventilation around
the unit, the better the performance.
Mounting the Unit:
•Choose an appropriate mounting location.
•The unit can be mounted in any direction.
•Use the mounting template below to mark the positions of the mounting screws.
•Drill the 4 mounting holes and place the unit in position and fasten the unit to the mounting surface.
DC Input Connection:
WARNING: Electrical Shock Hazard
The unit ‘On/Off’ switch does not disconnect the DC power from the battery. Use the DC Disconnect
Switch or disconnect the DC input cables to disconnect the DC power from the battery before working
on any circuits connected to the unit. Failure to follow these instructions can result in death or serious
injury.
CAUTION: Reversing the DC Input terminals will damage the unit and it cannot be repaired. Damage
caused by reverse polarity connection is not covered by the warranty.
IMPORTANT: Field wiring DC terminals tightening torque 12-13 Nm
•Connect a negative DC input cable between the unit DC negative terminal and battery negative
terminal.
•Make sure the Disconnect Switch is in the OFF position. Connect a positive DC input cable
between the unit DC positive terminal and one terminal of the Disconnect Switch.
•Connect another DC input cable between the other terminals of the Disconnect Switch to one side
of the terminal of the fuse holder or DC rated circuit breaker (OFF position).
•Connect another DC input cable between the other terminal of the fuse holder or DC rated circuit
breaker to the battery positive terminal.
Note: For Marine application, either the DC fuse or DC rated circuit breaker needs to be installed within 7 inches
(17.8cm) from the battery positive terminals.
•Install the selected fuse to the fuse holder.
Chassis DC Ground Connection:
•Connect the grounding wire to the unit’s Chassis DC Ground Lug located near the DC Input
terminal and the other side of the cable to the common grounding point.
•For a Recreation Vehicle, the common ground point is usually the vehicle chassis or a dedicated
DC ground bus.
•For Marine, the common ground point is usually the DC ground bus or engine negative bus.
Note: Do not use the Chassis DC Ground Lug for your AC Grounding, For AC Grounding, see AC Wiring

Page 11
instructions for more details.
AC Input and AC Output Hardwire Connections:
Warning: Before making any AC Input and AC Output Hardwire connection, please be sure the AC
Input Source is not energized and the DC disconnect switch is switched OFF.Please double check
the location of the AC input connector located inside the wiring compartment. Misconnecting to the
AC output connector inside the same compartment will damage the unit and may cause fire.
Remove the AC compartment cover by unscrewing the four screws located at the front of the AC
compartment cover.
For AC Input Connections:
•Insert the AC Input cable through the AC Input Strain relief ○g on the unit.
•Connect the AC Main Panel AC Ground wire to the AC Input Ground terminal ○a on the unit. If
solid ground wire is used, the wire can be connected directly under the screw head. If stranded
ground wire is used, ring terminals must be used
•Connect the AC Main Panel AC Live or Hot wire to unit’s AC Input ‘L’ Live or ‘H’ Hot’ terminal ○b .
•Connect the AC Main Panel AC Neutral wire to unit’s AC Input Neutral ‘N’ terminal ○c .
•Tighten the strain relief to secure the AC Input wire.
For AC Output Hardwire Connections:
•Insert the AC Input cable through the AC Output Strain relief ○h on the unit.
•Connect the AC Sub-Panel AC Ground wire to the AC Output Ground terminal ○f on the unit. If
solid ground wire is used, the wire can be connected directly under the screw head. If stranded
ground wire is used, ring terminals must be used
•Connect the AC Sub-Panel AC Live or Hot wire to unit’s AC Output ‘L’ Live or ‘H’ Hot terminal ○d .
•Connect the AC Sub-Panel AC Neutral wire to unit’s AC Output Neutral ‘N’ terminal ○e .
•Tighten the strain relief to secure the AC Input wire.
Display Connection:
•Install the RJ12 cable in your desired location and connect the RJ12 cable to the unit and the other
end of the cable to the Display Panel.
BTS (Battery Temperature Sensor) Connection (optional):
To provide more accuracy and precision on battery voltage charging against battery temperature, a
BTS (sold separately) can be used.
•Connect the RJ12 end of the BTS cable to the BTS Port of the unit.
•Install the ring terminal end of the BTS cable to the negative terminal of the battery bank.
Ignition Start Port Connection (optional):
The ignition start connection provides an inverter ON/OFF function through the Ignition Start Port. See
more details on Understanding of Ignition Start On/Off function.

Page 12
Quick Test on Unit after Installation:
•Connect a small AC load like 40W light bulb to the AC Output of the unit.
•Switch DC disconnect switch to ON to provide battery power to the unit, then press and hold ‘On/Off
button on Main unit or ‘Power’ button on Display panel for 1 second to turn unit or Inverter ON
•The ‘Status’ LED on display will turn Amber indicating inverter is ON. AC Output indicator turns
green indicating the AC is available at the AC Output terminal of the unit.
•Verify the 40W light bulb is ON.
•Switch ON the Main Circuit Breaker on the AC Input Panel.
•Switch ON the AC Input Circuit Breaker that provides AC Input power to the unit.
•If AC input source is available, the ‘Status’ LED amber will flash for about 10 seconds indicating the
AC Input source is available. It will then turn to solid green or flashing green indicating the unit is
running from the AC input source.
•Verify the 40W light bulb remains ON.
•The unit is successfully installed and functioning properly.
GFCI Monthly Testing on 120VAC 2000W/3000W model
•For unit equipped with GFCI, the GFCI function is required to test monthly.
•To test the GFCI, turn unit ON in either in By-pass mode or battery power mode. Plug a small AC
load (e.g. 40W light bulb) to the AC Output GFCI Socket.
•Check that the AC load is ON.
•Press ‘TEST’ button and observe a clicking sound. Check that the AC load is turned off.
•Press ‘RESET’ button and check that the AC load is back ON again.

Page 13
5. UNIT OPERATION
The unit is preset with factory default settings and will fulfill the basic needs for inverter-charger
operation. Display is used to provide information about the unit status and the unit function can be
customized through the Display.
Once the unit function is customized, Display can be removed if desired, as the unit can run without
the Display.
Understanding the Indicator and Unit Functions on Display and Main unit
Understanding the Display Push Buttons Functions
Normal Operation
Pressing any button illuminates the back lighting of the display for about 10 seconds.
Display shows Battery Voltage ‘V’. Can use ‘↑’○f and ‘↓’○g button to scroll through DC Current
‘A’, AC Output Power ‘KW’.
‘Power’○d button (Same function as the ‘On/Off’push button on the main unit):
- To turn Inverter ON: Press and hold for 3 seconds to turn unit ON. Display will turn ON and is
followed by a beep.
- Display show ‘-- -- --‘, All icons turn ON, followed by the revision levels of the unit (Rx.x, rx.x)
Note: When AC Input is available, this Power button cannot be used to turn OFF the unit.
‘Menu/SET’○e button:
•can be used to view the unit setting.
‘ESCAPE’○h button:
- Press and hold for 5 seconds to turn OFF or ON the AC Output Switch. (Use as AC Output
ON/OFF button).
Viewing Unit Setting
‘Menu/SET’button: Press once to enter the Unit Functions chart listed below.
‘↑’& ‘↓’Buttons: Use the ‘↑’& ‘↓’buttons to view other unit functions.
‘Escape’Button: Press once to exit viewing of the unit settings.
Changing Unit Settings
a) At normal operation, press ‘Menu/Set’ once.
b) Use ‘↑’& ‘↓’button to select the function that needs to be changed
c) Press and hold ‘Manu/Set’ button until the display flashes, use ‘↑’& ‘↓’button to select the new
parameters
Indicator
Status
Function
Power
ON
Unit is power ON
AC Output
ON
AC Output is turned ON
OFF
AC Output is turned OFF
Status
Green
AC Output is running from Utility
Green (Flash)
AC Output is running from utility and battery charger is charging the battery
Amber
AC Output is running from Inverter
Amber
(Flash)
Utility is detected and is under verification.AC Output is still running from
Inverter and will switch to Utility in about 10 seconds.
Red
Error/Warning occurs. Display will show Error or Warning code

Page 14
d) To save the new setting, press and hold button until display stops flashing.
Understanding the Unit Functions
Function
Display
Description and Available Setting
Inverter
: Use as Inverter only. No By-pass functions.
: Auto Backup. Inverter automatically turns ON when AC Blackout. (Default)
: Manual Backup. Inverter has to be manually turned ON when AC Blackout
occurs
: Inverter function is disable. No AC backup when AC Blackout.
Load Sense
:Continuous AC Output when inverter is ON (Default)
10: Continuous AC Output when inverter is ON and AC load is > 10W
15: Continuous AC Output when inverter is ON and AC load is > 15W
20: Continuous AC Output when inverter is ON and AC load is > 20W
25: Continuous AC Output when inverter is ON and AC load is > 25W
Battery Low
Disconnect
10.5*
Battery Low Disconnect Voltage selectable range: 10.5 - 12.0V (0.1V steps) *
(Default: 10.5V*)
Battery Low
Warning
11.0*
Battery Low Warning Voltage selectable range: 11.0 - 12.5V (0.1V step)*
(Default: 11.0V*)
Battery Under
Voltage
Recovery
12.0*
Battery Low Recovery Voltage selectable range: 11.5 - 13.0V (0.1V step)*
(Default: 12.0V*)
Audible
Buzzer
:Buzzer is enabled. Unit buzzes when Warning or Error occurs. (Default)
: Buzzer is disabled. Unit does not buzz when Warning and Error occurs.
Charger
:Charger is enabled. Charge battery when AC Input is available. (Default)
: Charger is disabled. No battery charging when AC Input is available.
Battery Type
: GEL Battery, Default Bulk Charge/Float Voltage is 14.2V/13.8V* (Default)
: Flooded Battery, Default Bulk Charge/Float Voltage is 14.4V/13.5V*
: AGM Battery, Default Bulk Charge/Float Voltage is 14.3V/13.4V*
: Lithium Battery, Default Bulk Charge/Float Voltage is 13.9V/13.5V*
: Program, Default Bulk Charge/Float Voltage is 13.8V/13.2V*
: Power Supply Mode, Default Power Supply Voltage 13.8V*
Bulk Current
100
12V/3000W Models: Selectable Range: 100A (Default), 80A, 60A, 40A, 25A
12V/2000W Models: Selectable Range: 80A (Default), 60A, 40A, 20A, 10A
24V/3000W Models: Selectable Range: 50A (Default), 40A, 30A, 20A, 10A
24V/2000W Models: Selectable Range: 40A (Default), 30A, 20A, 10A, 5A
Bulk/Absorpt-
ion Voltage
14.2*
Bulk/Absorption voltage is based on the battery type choose.
Selectable Range 13.8 –14.8V*. (Default on GEL: 14.2V*)
Absorption to
Float Current
10
12V/3000W Models: Selectable Range: 20A, 15A, 10A(Default), 5A, 2A
12V/2000W Models: Selectable Range: 15A, 10A, 8A(Default), 4A, 2A
24V/3000W Models: Selectable Range: 8A, 6A, 5A(Default), 3A, 2A
24V/2000W Models: Selectable Range: 6A, 5A, 4A(Default), 3A, 2A
Float Voltage
13.8*
Float voltage is based on the battery type chosen.
Selectable Range 13.0 –14.0V*. (Default on GEL: 13.8V*)
Recharge
Voltage
12.8*
Battery Recharge Voltage Selectable Range: 12.8 to 14.0V (0.1V step)*
(Default: 12.8V*)
Battery
Temperature
: High > 35 °C
: Normal 15 - 35°C (Default)
: Low <15°C
AC Input
Circuit
Breaker
30
120 Vac Models: Range: 30A (Default), 20A, 15A
230 Vac Models: Range: 16A (Default), 13A, 10A
Factory
Default
Select to reset all settings to default.
* for 24 V Models (BIC2430050, BIC2420040, BIC2430050i, BIC2420040i), all the voltage values are doubled.

Page 15
Understanding the Display ICONs during Unit Operation
Icon
Meaning
Solid: Unit is running as Charger and is charging the battery
Solid: Unit is running in By-pass mode, AC Output is available from AC Input Source.
- AC Output is available at both the AC Output socket and the AC Output Hardwire terminal if
AC Output switch is turned On (indicated by AC Output indicator on the Display and the
main unit being On).
Note: Press and hold the ‘ESCAPE’ button on the Display panel for 5 seconds to toggle AC
Output switch On/Off.
Solid: AC Input is available and is in the operating range.
Flashing: AC Input is detected and is under verification before switching to By-pass mode. This
normally takes about 10 seconds.
Solid: Unit is running in Battery Mode (inverter is running and providing AC Output).
Inverter
Mode
Battery bar(s) in solid indicating the unit is running in Battery Mode. The bars show estimated
remaining battery power.
4 solid bars: Battery is Full
3 solid bars: Battery capacity with 75% remaining
2 solid bars: Battery capacity with 50% remaining
1 solid bar: Battery capacity with 25% remaining
No bar: Battery is empty. Inverter will shutdown when it reaches under voltage shutdown point.
Note: This indicator is for reference use only. It varies depending on battery health or type used.
Charger
Mode
Battery bar(s) with the last bar flashing indicates the unit is running in By-Pass mode and the
battery is in charging process. The charging stages are indicated by the number of bars.
4 bars in solid: indicates the battery is fully charged and it is in Float stage
Top bars flashing: indicates the battery is in Absorption charging stage
Second top bar flashing: indicates the battery is in Bulk charging stage and the battery
is > 13.5V
Second bottom bar flashing: indicates the battery is in Bulk charging stage and the
battery is > 12.5V
Bottom bar flashing: indicates the battery is in Bulk charging stage and the battery is >
11.5V
No bar: indicates the battery is in Bulk charging stage and the battery is > 10.5V
Battery icon flashing, indicates the battery is in Bulk charging stage and the battery is
below 10.5V
‘A’ icon on indicates the display shows battery discharge current (28A as shown)
‘kW’ icon on, it indicates the display shows AC Output power in kW (0.80kW as shown)
‘V’ icon on, it indicates the display shows battery voltage in V (12.8V as shown)
Warning icon on, it indicates the display shows Error/Warning Code (E01 as shown)
Equalization on Flooded battery is in process. This function is only available with Flooded
battery only. The display will also show the equalization voltage during the process. Follow the
instruction provided by the battery manufacturer when performing the equalization process on
the flooded battery.
Indicating the Main unit software revision (R:1.0 shown)
Indicating the Display Panel software revision (r:1.0 shown)

Page 16
Understanding of Ignition Start ON/OFF function
With the setting that required manual On/Off of the inverter, the ignition start port share the same
function as the Power On/Off functions on the unit.
Providing a +12V dc to the Ignition Start Port will turns on the inverter and removing the +12VDC to
the port will turns Off the inverter.
Understanding the Error Codes
Code
Condition
Corrective Action
E01
When unit is in Battery/Inverter mode,
Input battery voltage is too low and AC
Output is shutdown.
Recharge the battery immediately and restart unit.
When unit is in By-Pass Mode the unit
continues supplying AC-Output power.
Check that the battery is connected to the unit.
Although the unit still provides AC Output power from
Utility, recharge the battery ASAP.
E02
When unit is in Battery/Inverter mode,
battery voltage is too high and unit has
shutdown
Check battery voltage or determine if any external
charger is connected to the battery bank
E03
When unit is in Battery/Inverter mode,
AC output is overloaded or short
circuited and unit has shutdown
Check load connected to the output. Reduce load and
restart the unit
E04
When unit is in Battery/Inverter mode
Internal temperature is too high and unit
has shutdown
Turn unit off and wait for 15 minutes before restarting.
Check if any object has blocked the air flow of the unit
E05
When unit is in Battery/Inverter mode
Input battery voltage is low and warning
occurs
Recharge battery as unit will shutdown shortly
E06
When unit is in Battery/Inverter mode
AC output load connected has been
sensed high and is close to shutdown
limit
Reduce load
E07
When unit is in Batter/Inverter mode
Internal temperature is high and is close
to over temperature shutdown limit
Reduce load and check if any ventilation of the unit is
blocked
E10
When unit is in By-pass mode, Battery
Charging voltage too high
Check battery setting
E11
When unit is in By-pass mode, Battery
fault, battery does not accept charge.
Check battery
E12
When unit is in By-pass mode, Internal
transfer switch temperature is high and
shutdown occurs
Reduce load and check if any ventilation of the unit is
blocked
E13
AC Output GFCI Tripped
Check the GFCI installed in the unit. Reset the GFCI.
E14
Display panel has communication error
Check RJ12 cable connected between the main and
Display panel
E15
AC Back Feed to Unit AC Output
Check AC Output wiring
AC Load on Inverter
Although the Power Inverter can provide high surge power up to two times the rated output power,
some high surge loads like air conditioners, sump-pumps, heavy duty motors etc. may still trigger the
inverter protection system even though the load falls within the power rating of the inverter. A higher
power Inverter-Charger is required for these appliances.

Page 17
Exploring the Unit Settings
a) Inverter and Charger Functions
INT
ABU
Automatic Backup with Charger set to On (Default setting)
CHG
ON
By-Pass
Mode Display
Unit is running in By-Pass mode. Both AC Output Hardwire and AC Output Socket are
connected to AC Input Source.
- AC Charger is enabled and will charge the battery, battery icon shows Battery
Charging stage.
- Inverter is in standby condition.
- Display shows battery voltage, DC Charging current, AC Input Power.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator – solid green (battery is fully charged) or flashing (battery charging is
in progress).
Note: ‘Power’ button function is disabled in this stage.
Battery Mode
Display
During a blackout, unit will automatically provide AC Backup by the inverter. AC Charger
is off.
- Display shows battery voltage, DC Current discharge from battery, AC Output Power.
- Battery icon shows estimated battery capacity.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator – solid amber. If it changes to flashing amber, it indicates AC Input
Source is detected and will switch to By-Pass Mode shortly.
Note: During blackout, ‘Power’ button can be used to temporarily turn inverter Off to
save battery power if AC Output power is not required.
INT
ABU
Automatic Backup with Charger set to Off
CHG
OFF
By-Pass
Mode Display
Unit is running in By-Pass mode. Both AC Output Hardwire and AC Output Socket are
connected to AC Input Source.
- AC Charger is disabled. When this setting is used, a separate AC Charger or other
battery charging source is required to charge the battery.
- Battery icon shows estimated battery capacity.
- Inverter is in standby condition.
- Display shows battery voltage, DC Charging current (0A), AC Input Power.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator – solid green.
Note: ‘Power’ button function is disabled in this stage.
Battery Mode
Display
During a blackout, unit will automatically provide AC Backup by the inverter.
- Display shows battery voltage, DC Current discharge from battery, AC Output Power.
- Battery icon shows estimated battery capacity.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator – solid amber. If it changed to flashing amber, it indicates AC Input
Source is detected and will switch to By-Pass Mode shortly.
Note: During blackout, ‘Power’ button can be used to temporarily turn inverter Off to
save battery power if AC Output power is not required.

Page 18
INT
MBU
Manual Backup with Charger set to On
CHG
ON
By-Pass
Mode Display
Unit is running in By-Pass mode. Both AC Output Hardwire and AC Output Socket are
connected to AC Input Source.
- AC Charger is enabled and will charge the battery, battery icon shows Battery
Charging stage.
- Inverter is in turned Off.
- Display shows battery voltage, DC Charging current, AC Input Power.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator – solid green (battery is fully charged) or flashing green (battery
charging is in progress).
Note: ‘Power’ button function is disabled in this stage.
Blackout
Display
When a blackout occurs, Unit will not provide AC Backup. Display remains On for 10
seconds with the following appearance:
- Display shows battery voltage, DC Current discharge from battery (0A), AC Output
Power (0W)
- Battery icon shows estimated battery capacity.
- Inverter is disabled.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – Off (AC Output is not available due to the inverter being set to
Manual Backup Mode –MBU).
- ‘Status’ indicator – Off
After 10 seconds, Display and unit will turn Off.
If AC Input Source is detected, unit will switch back to By-Pass Mode automatically in
about 10 seconds. During the 10 second period, ‘Power’ indicator turns On and ‘Status’
indicator remains Off.
Blackout and
Manually
turns On
Inverter
If AC Output is required during a blackout, press and hold the ‘Power’ button for one
second to turn On the inverter.
- Display shows battery voltage, DC Current discharge from battery, AC Output Power.
- Battery icon shows estimated battery capacity.
- ‘Power’ indicator - On,
- ‘AC Output’ indicator –On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator –solid amber. If it changes to flashing amber, it indicates AC Input
Source is detected and will switch to By-Pass Mode shortly.
Note: During blackout, ‘Power’ button can be used to temporarily turn inverter Off to
save battery power if AC Output power is not required.

Page 19
INT
MBU
Manual Backup with Charger set to Off
CHG
OFF
By-Pass
Mode Display
Unit is running in By-Pass mode. Both AC Output Hardwire and AC Output Socket are
connected to AC Input Source.
- AC Charger is disabled. Unit will not charge the battery. When this setting is used, a
separate AC Charger or other battery charging source is required to charge the
battery.
- Display shows battery voltage, DC Charging current (0A), AC Input Power.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator – green
Note: ‘Power’ button function is disabled in this stage.
Blackout
Display
When a blackout occurs, Unit will not provide AC Backup. Display remains On for 10
seconds with the following appearance:
- Display shows battery voltage, DC Current discharge from battery (0A), AC Output
Power (0W).
- Battery icon shows estimated battery capacity.
- Inverter is disabled.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – Off (AC Output is not available due to the inverter being set to
Manual Backup Mode –MBU).
- ‘Status’ indicator – Off
After 10 seconds, Display and unit will turn Off.
If AC Input Source is detected, unit will switch back to By-Pass Mode automatically in
about 10 seconds. During the 10 seconds period, ‘Power’ indicator turns On and ‘Status’
indicator remains Off.
Blackout and
Manually
turns On
Inverter
If AC Output is required during a blackout, press and hold the ‘Power’ button for one
second to turn On the inverter.
- Display shows battery voltage, DC Current discharge from battery, AC Output Power.
- Battery icon shows estimated battery capacity.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator –solid amber. If it changed to flashing amber, it indicates AC Input
Source is detected and will switch to By-Pass Mode shortly.
Note: During blackout, ‘Power’ button can be used to temporarily turn inverter Off to
save battery power if AC Output power is not required.

Page 20
INT
OFF
No Backup and Charger set to On
CHG
ON
By-Pass
Mode Display
Unit is running in By-Pass mode. Both AC Output Hardwire and AC Output Socket are
connected to AC Input Source.
- AC Charger is enabled and will charge the battery, battery icon shows Battery
Charging stage.
- Inverter is disable.
- Display shows battery voltage, DC Charging current, AC Input Power.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator – solid green (battery is fully charged) or flashing (battery charging is
in progress).
Note: ‘Power’ button function is disabled in this stage.
Blackout
Display
When a blackout occurs, Unit will not provide AC Backup. Display remains On for 10
seconds with the following appearance:
- Display shows battery voltage, DC Current discharge from battery (0A), AC Output
Power (0W)
- Battery icon shows estimated battery capacity.
- Inverter is disabled.
- ‘Power’ indicator – On.
- ‘AC Output’ indicator – Off (AC Output is not available due to the inverter is set to Off.)
- ‘Status’ indicator –Off.
After 10 seconds, Display and unit will turn Off.
Press and hold the ‘Power’ button for 1 second to turn On the display to check the
battery status.
If AC Input Source is detected, unit will switch back to By-Pass Mode automatically in
about 10 seconds. During the 10 second period, ‘Power’ indicator turns On and ‘Status’
indicator remains Off.
INT
ON
Inverter Only: (Unit is running as inverter only, no By-Pass function)
CHG
OFF/ON
This setting is specially designed so that the AC load connected to AC Output is always getting clean
sinewave power from the inverter. When this mode is used, a separate AC Charger or other battery
charging source is required to charge the battery.
Inverter is
turned On.
No AC Input
Source
If AC Output is required, press and hold the ‘Power’ button for one second to turn On the
Inverter. This function is not affected by the AC Input Source.
- Display shows battery voltage, DC Current discharge from battery, AC Output Power.
- Battery icon shows estimated battery capacity.
- ‘Power’ indicator - On,
- ‘AC Output’ indicator – On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator – solid amber.
Note: ‘Power’ button can be used to turn inverter Off and On
Inverter is
turned On
with AC Input
Source is
detected.
If AC Output is required, press and hold the ‘Power’ button for one second to turn On the
Inverter. With AC Input Source detected, the ‘AC Input’ icons will be shown on the
display but AC Output is still provided by the Inverter.
- Display shows battery voltage, DC Current discharge from battery, AC Output Power.
- Battery icon shows estimated battery capacity.
- ‘Power’ indicator - On,
- ‘AC Output’ indicator – On (AC Output Switch is turned On, AC Output is On).
- ‘AC Output’ indicator – Off (AC Output Switch is turned Off, AC Output is Off).
Note: Press and hold ‘ESCAPE’ button for 5 seconds to toggle AC Output Switch
On/Off.
- ‘Status’ indicator – solid amber.
Note: ‘Power’ button can be used to turn inverter Off and On.
Other manuals for 120V Series
3
This manual suits for next models
17
Table of contents
Other Kisae Inverter manuals

Kisae
Kisae 120V Series User manual

Kisae
Kisae MW 1204 User manual

Kisae
Kisae SW2420 User manual

Kisae
Kisae 120V Series User manual

Kisae
Kisae IC1220100 User manual

Kisae
Kisae SW 1220 User manual

Kisae
Kisae 3000W - 120V User manual

Kisae
Kisae SWXFR1210 User manual

Kisae
Kisae MW 1204 User manual

Kisae
Kisae SWXFR1210 User manual
Popular Inverter manuals by other brands

Hitachi
Hitachi SJ700B SERIES instruction manual

Solplanet
Solplanet ASW LT-G2 Series user manual

Mitsubishi Electric
Mitsubishi Electric F700 instruction manual

SMA
SMA SUNNY BOY 3.0-US installation manual

Fintek
Fintek OSLO 3.0 DCI Installation and user manual

Clenergy
Clenergy PV-ezRack SolarRoof ER-TL-10/15 installation guide