manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. KMC Controls
  6. •
  7. Control Unit
  8. •
  9. KMC Controls KMD-5567 User manual

KMC Controls KMD-5567 User manual

Other KMC Controls Control Unit manuals

KMC Controls VEB-4303-SDL Series User manual

KMC Controls

KMC Controls VEB-4303-SDL Series User manual

KMC Controls VEP-43 Series User manual

KMC Controls

KMC Controls VEP-43 Series User manual

KMC Controls VEB-53 Series User manual

KMC Controls

KMC Controls VEB-53 Series User manual

KMC Controls VEP–3420 Series User manual

KMC Controls

KMC Controls VEP–3420 Series User manual

KMC Controls HPO-9001 User manual

KMC Controls

KMC Controls HPO-9001 User manual

KMC Controls VEP-34190186 User manual

KMC Controls

KMC Controls VEP-34190186 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

KMD-5567 1 Installation Guide
Introduction
The KMD-5567 is installed at building exits and
entrances to provide surge suppression for one or
two pairs of low-voltage data signal lines. When
properly installed and wired, the KMD-5567 can
protect the digital communication circuitry from
lightning damage.
In smoke control applications, one KMD-5567 is also
required for the EIA-485 terminals of every control-
ler and repeater as well.
See Illustration 1 for a diagram and dimensions
of the module and terminal connector. The sup-
pressor consists of two parts, the Suppressor
Module (HPO-0066) and the Terminal Connector
(HPO-0067).
Installation Guide
Suppressor Module and Terminal Connector
KMD-5567
DRAFT
NOTE: Watermark is
on nonwritable DRAFT
Watermark layer. Turn the
layer off or delete layer
to remove from the nal
document.
Illustration 1—KMD-5567 Components and Dimensions
Installation and Wiring
Network Protection, Multiple Building
The KMD-5567 should be located near locations
where communication circuits enter and exit the
building. See Illustration 3.
1. Mount the module in a suitable enclosure using
the provided mounting holes.
NOTE: Orienting the unprotected terminals on the
same side as the incoming or exiting wiring
may simplify the wiring process.
2. Connect the incoming or exiting wires to the
unprotected side (pairs 3/5 and/or 7/9). See
Illustrations 2 and 3.
3. Connect the protected side pairs (2/4 and/or 6/8)
to the destination device wiring.
4. Connect an equipment ground to either Pin 1 or
Pin 10, but not both.
Individual Controller Protection
NOTE: This is required in smoke control
applications on every controller and
repeater.
1. Mount the module in a suitable enclosure using
the provided mounting holes.
2. Connect the EIA-485 wires from the previous
controller or repeater to the appropriate terminals
as shown in Illustrations 2 and 4.
2. If applicable, connect the EIA-485 wires from
the next controller or repeater to the appropriate
terminals as shown in Illustrations 2 and 4.
3. Connect the KMD-5567 “protected side” terminals
to the controller as shown in Illustrations 2 and 4.
4. Connect an equipment ground to either Pin 1 or
Pin 10, but not both.






















Illustration 2—KMD-5567 Terminal Connections
KMD-5567 2 Installation Guide© 2008 KMC Controls, Inc. 717-019-01C
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
[email protected]
Maintenance
No routine maintenance is required. Each component
is designed for dependable, long-term reliability, and
performance. Careful installation will also ensure
long-term reliability and performance.
Operation
Once installed, the KMD-5567 Suppressor Module
requires lile user intervention. If the suppressor
is damaged because of a lightning strike, causing
the protected circuit to open, simply replace the
HPO-0066 Suppressor Module.
Specifications
Peak Surge Current 8 x 20 µs 10 kA
10 x 700 µs 500 A per line
Life Expectancy 8 x 20 µs (2000 A),
100 Occurrences
10 x 700 µs (400 A)
100 Occurrences
Response Time <1 Nanosecond
Voltage Clamp 15 Volts
Technology Silicon Avalanche Diode Hybrid
Resistance 8.0 ohms per line
Capacitance 1500 pf (average)
Weight 2.0 oz. (56.7 g)
Ambient Limits
Operating –40° to 185° F (–40° to 85° C)
Shipping –40° to 185° F (–40° to 85° C)
Humidity 0 to 95% RH, non-condensing
Illustration 3—Network Protection with Multiple Buildings
Illustration 4—Individual Controller Protection (Required in Smoke Control Applications)










































































Accessories
HPO-0066 Suppressor Module
HPO-0067 Terminal Connector