Controller Accessories
Many functions that required optional accessories with
the M340+ controller are integrated into the
Decision-MakerrMPAC 1500 controller operation. For
example, an active time delay can be ended by pressing
a button on the Decision-MakerrMPAC 1500 controller.
Separate time delay bypass switches are not required.
See Figure 3 for accessory information.
M340+
Decision-MakerrMPAC
1500
Bypass (end) Time Delay
Switches Integrated
Source Monitor Integrated
Test Switch Integrated
Override Switches Integrated
Preferred Source Switch Alarm Module required
(see Figure 4)
Current Meter (amps) Current Sensing Kit required
(see Figure 6)
Plant Exerciser Integrated
Manual Switch Operation Supervised Transfer Control
Switch (see Figure 5)
Voltage/Frequency Meters Integrated
Load Shed Contact Integrated Load Control
Function (one output
connection required)
Figure 3 Accessories
Accessory Modules
Optional accessory modules are listed in Figure 4. One
module mounting kit holds up to five accessory
modules.
Accessory Modules Part Number
Module Mounting Assembly * GM46258-S
Standard I/O Module GM46888-S
High Voltage/Current I/O Module GM46890-S
Alarm Module GM40808-S
External Battery Supply Module GM46889-S
* One mounting assembly holds up to 5 modules.
Figure 4 Accessory Modules for Decision-Makerr
MPAC 1500
Other Accessories
Other Decision-MakerrMPAC 1500 accessories are
available. See Figure 5. Contact your local
distributor/dealer for more information.
Other MPAC 1500 Accessories Part Number
Controller Disconnect Switch GM46770-S3
Supervised Transfer Control
Switch [GM40807-S1
[Includes alarm module GM40808-S.
Figure 5 Other Accessories
Current Sensing
If current sensing is required (i.e. for current [amps]
monitoring and display), obtain the appropriately rated
current sensing kit (with 3 m [10 ft.] harness) before
starting the conversion procedure. If the transfer switch
is equipped with current transformers (CTs), they will
need to be replaced with the new current transformers
during the controller conversion procedure. See
Figure 6 for current sensing kit numbers. Check the
amp rating and number of phases of the transfer switch
and select the closest current sensing kit with an equal
or higher amp rating.
Kit Description Current Sensing
Kit Number
Amps Phases
200 3GM89028-S3
200 1GM89028-S21
400 3GM89028-S6
400 1GM89028-S24
1000 3GM89028-S8
1000 1GM89028-S26
1200 3GM89028-S11
1200 1GM89028-S28
2000 3GM89028-S15
3000 3GM89028-S17
Figure 6 Current Sensing Kits