Lenovo RT8.0kVA User manual

6U Rack or Tower UPS RT8.0kVA
and RT11.0VA and Maintenance
Bypass Installation and User's uide

Note:
Beforeusingthisinformationandtheproductitsupports,readthegeneralinformationinAppendix
B“ettinghelpandtechnicalassistance”onpage69,AppendixC“Notices”onpage73,thesafety
information,warranties,andlicensesinformationontheLenovoWebsiteat:
https://support.lenovo.com/documents/LNVO-DOCS
SecondEdition(February2017)
©CopyrightLenovo20152017.
LIMITEDANDRESTRICTEDRIHTSNOTICE:IfdataorsoftwareisdeliveredpursuanttoaeneralServices
Administration“SA”contract,use,reproduction,ordisclosureissubjecttorestrictionssetforthinContractNo.
S-35F-05925

Contents
Safety.................iii
uidelinesfortrainedservicetechnicians.....iv
Inspectingforunsafeconditions.......iv
uidelinesforservicingelectricalequipment..v
Safetystatements..............vi
Productsafety................x
Chapter1.Introduction.........1
Noticesandstatements............1
Environmentalprotection...........1
Chapter2.Presentation.........5
Standardinstallations.............5
Rearpanels.................6
Controlpanel................6
LCDdescription...............7
Displayfunctions...............9
Usersettings...............10
ExtendedBatteryModules(EBMs).......13
HotSwapMBP...............13
StandardinstallationsfortheHotSwapMBP.13
HotSwapMBPcontrols.........14
Chapter3.Installation.........17
Inspectingtheequipment..........17
Unpackingtheunit.............17
Checkingtheaccessorykit:UPS.......18
Checkingtheaccessorykit:HotSwapMBP...19
Mechanicalmounting............21
ConnectingtheEBM(s)...........21
Rackinstallation..............22
PreparingtheEBMforrackmounting....22
RackmountingofUPS,EBM,andaccessory
modules...............23
Towerinstallation..............24
Installingthecommunicationcard.......24
Installationrequirements...........25
Installationdependingonthesystemearthing
arrangement(SEA).............26
Chapter4.Powercables
connection..............27
Accesstoterminalblocks..........27
Commoninputsourcesconnection(1Phase
units)..................28
Commoninputsourcesconnection(3Phase
units)..................28
Separateinputsourceconnection(1Phaseunits).29
Separateinputsourceconnection(3Phaseunits).29
Frequencyconverterconnection(1Phaseunits)..30
Frequencyconverterconnection(3Phaseunits)..30
HotSwapMBPconnection..........31
8/11kVA1Phase............31
8/11kVA3PhasewithcommonNormaland
BypassACsource...........33
8/11kVA3PhasewithseparateNormaland
BypassACsource...........34
Chapter5.Operation.........39
UPSstartupandshutdown..........39
StartingtheUPS............39
StartingtheUPSonBattery........39
ShuttingdowntheUPS.........40
UPSstart-upwithHotSwapMBP.......40
MonitoringtheUPSoperatingmode......41
Operatingmodes:descriptions......41
Operatingmodes:summary.......42
TransferringtheUPSbetweenmodes......42
SettingHighEfficiencymode.........42
ConfiguringBypasssettings.........43
Bypasstransferoutoftolerance......43
Interrupttime.............43
Configuringbatterysettings.........43
RetrievingtheEventlog...........44
RetrievingtheFaultlog...........44
Chapter6.Communication......45
Communicationports............45
ConnectingRS232orUSBcommunication
ports.................45
Relayoutputcontacts..........45
RemoteOn/Off.............46
RemotePowerOff...........46
Connectivitycard............47
Replacingthecommunicationcard......48
UPSPowerManagementsuite........48
Chapter7.UPSmaintenance.....49
Equipmentcare..............49
Storingtheequipment............49
Replacingbatterypacks...........49
Replacingtheinternalbatterypack.....50
ReplacingtheEBM(s)..........51
Testinganewbatterypack........52
ReplacingtheUPS.............52
©CopyrightLenovo2015,2017i

RemovingtheUPS...........52
Returningtonormaloperation.......54
Recyclingtheusedequipment........55
Chapter8.Troubleshooting......57
Alarmsandfaults..............57
Silencingthealarm.............60
Serviceandsupport............60
Chapter9.Partslisting........61
AppendixA.Specifications......63
UPSspecifications.............63
HotSwapMBPspecifications.........67
AppendixB.Gettinghelpand
technicalassistance.........69
Beforeyoucall...............69
Usingthedocumentation..........70
ettinghelpandinformationfromtheWorldWide
Web...................70
HowtosendDSAdata...........70
Creatingapersonalizedsupportwebpage...70
Softwareserviceandsupport.........71
Hardwareserviceandsupport........71
Taiwanproductservice...........71
AppendixC.Notices..........73
Trademarks................74
Importantnotes..............74
Recyclinginformation............74
Particulatecontamination..........75
Telecommunicationregulatorystatement....75
Electronicemissionnotices..........75
FederalCommunicationsCommission(FCC)
statement...............75
IndustryCanadaClassAemissioncompliance
statement...............76
Avisdeconformitéàlaréglementation
d'IndustrieCanada...........76
AustraliaandNewZealandClassA
statement...............76
EuropeanUnionEMCDirectiveconformance
statement...............76
ermanyClassAstatement.......76
Japaneseelectromagneticcompatibility
statements..............77
KoreaCommunicationsCommission(KCC)
statement...............78
RussiaElectromagneticInterference(EMI)
ClassAstatement...........78
People'sRepublicofChinaClassAelectronic
emissionstatement...........79
TaiwanClassAcompliancestatement...79
TaiwanBSMIRoHSdeclaration......80
Index..................81
ii 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's uide

Safety
Beforeinstallingthisproduct,readtheSafetyInformation.
Antesdeinstalaresteproduto,leiaasInformaçõesdeSegurança.
Læssikkerhedsforskrifterne,førduinstallererdetteprodukt.
Leesvoordatuditproductinstalleerteerstdeveiligheidsvoorschriften.
Ennenkuinasennattämäntuotteen,lueturvaohjeetkohdastaSafetyInformation.
Avantd'installerceproduit,lisezlesconsignesdesécurité.
VorderInstallationdiesesProduktsdieSicherheitshinweiselesen.
Primadiinstallarequestoprodotto,leggereleInformazionisullaSicurezza.
Lessikkerhetsinformasjonen(SafetyInformation)førduinstallererdetteproduktet.
©CopyrightLenovo2015,2017iii

Antesdeinstalaresteproduto,leiaasInformaçõessobreSegurança.
Antesdeinstalaresteproducto,lealainformacióndeseguridad.
Lässäkerhetsinformationeninnanduinstallerardenhärprodukten.
Guidelinesfortrainedservicetechnicians
Thissectioncontainsinformationfortrainedservicetechnicians.
Inspectingforunsafeconditions
UsethisinformationtohelpyouidentifypotentialunsafeconditionsinaLenovoproductthatyouare
workingon.
EachLenovoproduct,asitwasdesignedandmanufactured,hasrequiredsafetyitemstoprotectusers
andservicetechniciansfrominjury.Theinformationinthissectionaddressesonlythoseitems.Usegood
judgmenttoidentifypotentialunsafeconditionsthatmightbecausedbyalterationsorattachmentof
non-Lenovofeaturesoroptionaldevicesthatarenotaddressedinthissection.Ifyouidentifyanunsafe
condition,youmustdeterminehowseriousthehazardisandwhetheryoumustcorrecttheproblembefore
youworkontheproduct.
Considerthefollowingconditionsandthesafetyhazardsthattheypresent:
•Electricalhazards,especiallyprimarypower.Primaryvoltageontheframecancauseseriousorfatal
electricalshock.
•Explosivehazards,suchasadamagedCRTfaceorabulgingcapacitor.
•Mechanicalhazards,suchaslooseormissinghardware.
Toinspecttheproductforpotentialunsafeconditions,completethefollowingsteps:
1.Makesurethatthepowerisoffandthepowercordsaredisconnected.
2.Makesurethattheexteriorcoverisnotdamaged,loose,orbroken,andobserveanysharpedges.
3.Checkthepowercords:
•Makesurethatthethird-wiregroundconnectorisingoodcondition.Useametertomeasure
third-wiregroundcontinuityfor0.1ohmorlessbetweentheexternalgroundpinandtheframeground.
•Makesurethatthepowercordsarethecorrecttype.
iv 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's uide

•Makesurethattheinsulationisnotfrayedorworn.
4.Removethecover.
5.Checkforanyobviousnon-Lenovoalterations.Usegoodjudgmentastothesafetyofanynon-Lenovo
alterations.
6.Checkinsidethesystemforanyobviousunsafeconditions,suchasmetalfilings,contamination,water
orotherliquid,orsignsoffireorsmokedamage.
7.Checkforworn,frayed,orpinchedcables.
8.Makesurethatthepower-supplycoverfasteners(screwsorrivets)havenotbeenremovedortampered
with.
Guidelinesforservicingelectricalequipment
Observetheseguidelineswhenyouserviceelectricalequipment.
•Checktheareaforelectricalhazardssuchasmoistfloors,nongroundedpowerextensioncords,and
missingsafetygrounds.
•Useonlyapprovedtoolsandtestequipment.Somehandtoolshavehandlesthatarecoveredwithasoft
materialthatdoesnotprovideinsulationfromliveelectricalcurrent.
•Regularlyinspectandmaintainyourelectricalhandtoolsforsafeoperationalcondition.Donotuse
wornorbrokentoolsortesters.
•Donottouchthereflectivesurfaceofadentalmirrortoaliveelectricalcircuit.Thesurfaceisconductive
andcancausepersonalinjuryorequipmentdamageifittouchesaliveelectricalcircuit.
•Somerubberfloormatscontainsmallconductivefiberstodecreaseelectrostaticdischarge.Donotuse
thistypeofmattoprotectyourselffromelectricalshock.
•Donotworkaloneunderhazardousconditionsornearequipmentthathashazardousvoltages.
•Locatetheemergencypower-off(EPO)switch,disconnectingswitch,orelectricaloutletsothatyoucan
turnoffthepowerquicklyintheeventofanelectricalaccident.
•Disconnectallpowerbeforeyouperformamechanicalinspection,worknearpowersupplies,orremove
orinstallmainunits.
•Beforeyouworkontheequipment,disconnectthepowercord.Ifyoucannotdisconnectthepower
cord,havethecustomerpower-offthewallboxthatsuppliespowertotheequipmentandlockthe
wallboxintheoffposition.
•Neverassumethatpowerhasbeendisconnectedfromacircuit.Checkittomakesurethatithasbeen
disconnected.
•Ifyouhavetoworkonequipmentthathasexposedelectricalcircuits,observethefollowingprecautions:
–Makesurethatanotherpersonwhoisfamiliarwiththepower-offcontrolsisnearyouandisavailableto
turnoffthepowerifnecessary.
–Whenyouworkwithpowered-onelectricalequipment,useonlyonehand.Keeptheotherhandinyour
pocketorbehindyourbacktoavoidcreatingacompletecircuitthatcouldcauseanelectricalshock.
–Whenyouuseatester,setthecontrolscorrectlyandusetheapprovedprobeleadsandaccessories
forthattester.
–Standonasuitablerubbermattoinsulateyoufromgroundssuchasmetalfloorstripsandequipment
frames.
•Useextremecarewhenyoumeasurehighvoltages.
•Toensurepropergroundingofcomponentssuchaspowersupplies,pumps,blowers,fans,andmotor
generators,donotservicethesecomponentsoutsideoftheirnormaloperatinglocations.
©CopyrightLenovo2015,2017v

•Ifanelectricalaccidentoccurs,usecaution,turnoffthepower,andsendanotherpersontogetmedical
aid.
Safetystatements
Thesestatementsprovidethecautionanddangerinformationthatisusedinthisdocumentation.
Eachcautionanddangerstatementinthisdocumentationislabeledwithanumber.Thisnumberisusedto
crossreferenceanEnglish-languagecautionordangerstatementwithtranslatedversionsofthecautionor
dangerstatementintheSafetyInformationdocument.
Forexample,ifadangerstatementislabeledD005,translationsforthatcautionstatementareintheSafety
InformationdocumentunderD005.
Besuretoreadallcautionanddangerstatementsinthisdocumentationbeforeyouperformtheprocedures.
Readanyadditionalsafetyinformationthatcomeswithyoursystemoroptionaldevicebeforeyouinstall
thedevice.
L001
DANGER
Hazardousvoltagecurrentorenergylevelsarepresentinsideanycomponentthathasthislabel
attached.Donotopenanycoverorbarrierthatcontainsthislabel.Therearenoserviceableparts
insidethesecomponents.Ifyoususpectaproblemwithoneofthesepartscontactaservice
technician.
DONOTopenupthechassisoranyotherpartsofanyUPSunit.Thiswillvoidtheunitwarranty.
OnlyreplacepartsforwhichaserviceablepartexiststhatisservicinganyUPSunitislimitedto
FRU/CRUreplacementparts.
(L001)
D005
DANGER
Whenworkingonoraroundthesystemobservethefollowingprecautions:Electricalvoltageand
currentfrompowertelephoneandcommunicationcablesarehazardous.Toavoidashockhazard:
•IfLenovosuppliedapowercord(s)connectpowertothisunitonlywiththeLenovo-provided
powercord.DonotusetheLenovo-providedpowercordforanyotherproduct.
•Donotopenorserviceanypowersupplyassembly.
•Donotconnectordisconnectanycablesorperforminstallationmaintenanceorreconfiguration
ofthisproductduringanelectricalstorm.
•Theproductmightbeequippedwithmultiplepowercords.Toremoveallhazardousvoltages
disconnectallpowercords.
vi 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's uide

•Connectallpowercordstoaproperlywiredandgroundedelectricaloutlet.Ensurethatthe
outletsuppliespropervoltageandphaserotationaccordingtothesystemratingplate.
•Connectanyequipmentthatwillbeattachedtothisproducttoproperlywiredoutlets.
•Whenpossibleuseonehandonlytoconnectordisconnectsignalcables.
•Neverturnonanyequipmentwhenthereisevidenceoffirewaterorstructuraldamage.
•Disconnecttheattachedpowercordstelecommunicationssystemsnetworksandmodems
beforeyouopenthedevicecoversunlessinstructedotherwiseintheinstallationand
configurationprocedures.
•Connectanddisconnectcablesasdescribedinthefollowingprocedureswheninstalling
movingoropeningcoversonthisproductorattacheddevices.Todisconnect:
1.Turnoffeverything(unlessinstructedotherwise).
2.Removethepowercordsfromtheoutlets.
3.Removethesignalcablesfromtheconnectors.
4.Removeallcablesfromthedevices.
Toconnect:
1.Turnoffeverything(unlessinstructedotherwise).
2.Attachallcablestothedevices.
3.Attachthesignalcablestotheconnectors.
4.Attachthepowercordstotheoutlets.
5.Turnonthedevices.
•Sharpedgescornersandjointsmightbepresentinandaroundthesystem.Usecarewhen
handlingequipmenttoavoidcutsscrapesandpinching.(D005)
C004
CAUTION:
Lead-acidbatteriescanpresentariskofelectricalburnfromhighshort-circuitcurrent.Avoidbattery
contactwithmetalmaterials;removewatchesringsorothermetalobjectsandusetoolswith
insulatedhandles.Toavoidpossibleexplosiondonotburn.
ExchangeonlywiththeLenovo-approvedpart.Recycleordiscardthebatteryasinstructedby
localregulations.IntheUnitedStatesLenovohasaprocessforthecollectionofthisbattery.For
informationcall1-800-426-4333.HavetheLenovopartnumberforthebatteryunitavailablewhen
youcall.
DONOTmixoldandnewbatteriesinanUninterruptiblePowerSupplyunit.
DONOTopenupanybatterypackretrievedfromanUninterruptiblePowerSupplyunit.
WearsafetygogglesforyourownprotectionwhenreplacingbatteriesofanUninterruptiblePower
Supplyunit.(C004)
C009
©CopyrightLenovo2015,2017vii

CAUTION:
or or Theweightofthispartorunitisbetween18
and32kg(39.7and70.5lb).Ittakestwopersonstosafelyliftthispartorunit.(C009)
C011
CAUTION:
or or Theweightofthispartorunitismorethan55
kg(121.2lb).Ittakesspeciallytrainedpersonsaliftingdeviceorbothtosafelyliftthispartor
unit.(C011)
C022
CAUTION:
Thisproductmightbeequippedwithahard-wiredpowercable.Ensurethatalicensedelectrician
performstheinstallationperthenationalelectricalcode.(C022)
R001
Important:Thefollowinggeneralsafetyinformationshouldbeusedforallrack-mounteddevices:
DANGER
ObservethefollowingprecautionswhenworkingonoraroundyourITracksystem:
•Heavyequipment—personalinjuryorequipmentdamagemightresultifmishandled.
•Alwayslowerthelevelingpadsontherackcabinet.
•Alwaysinstallstabilizerbracketsontherackcabinet.
•Toavoidhazardousconditionsduetounevenmechanicalloadingalwaysinstalltheheaviest
devicesinthebottomoftherackcabinet.Alwaysinstallserversandoptionaldevicesstarting
fromthebottomoftherackcabinet.
viii 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's uide

•Rack-mounteddevicesarenottobeusedasshelvesorworkspaces.Donotplaceobjectson
topofrack-mounteddevices.
•Eachrackcabinetmighthavemorethanonepowercord.Besuretodisconnectallpowercords
intherackcabinetwhendirectedtodisconnectpowerduringservicing.
•Connectalldevicesinstalledinarackcabinettopowerdevicesinstalledinthesamerack
cabinet.Donotplugapowercordfromadeviceinstalledinonerackcabinetintoapower
deviceinstalledinadifferentrackcabinet.
•Anelectricaloutletthatisnotcorrectlywiredcouldplacehazardousvoltageonthemetalparts
ofthesystemorthedevicesthatattachtothesystem.Itistheresponsibilityofthecustomerto
ensurethattheoutletiscorrectlywiredandgroundedtopreventanelectricalshock.
(R001part1of2)
CAUTION:
•Donotinstallaunitinarackwheretheinternalrackambienttemperatureswillexceedthe
manufacturer’srecommendedambienttemperatureforallyourrack-mounteddevices.
•Donotinstallaunitinarackwheretheairflowiscompromised.Ensurethatairflowisnotblocked
orreducedonanysidefrontorbackofaunitusedforairflowthroughtheunit.
•Considerationshouldbegiventotheconnectionoftheequipmenttothesupplycircuitsothat
overloadingofthecircuitsdoesnotcompromisethesupplywiringorovercurrentprotection.To
providethecorrectpowerconnectiontoarackrefertotheratinglabelslocatedontheequipment
intheracktodeterminethetotalpowerrequirementofthesupplycircuit.
•(Forslidingdrawers)Donotpulloutorinstallanydrawerorfeatureiftherackstabilizerbracketsare
notattachedtotherack.Donotpulloutmorethanonedraweratatime.Therackmightbecome
unstableifyoupulloutmorethanonedraweratatime.
•(Forfixeddrawers)Thisdrawerisafixeddrawerandmustnotbemovedforservicingunless
specifiedbythemanufacturer.Attemptingtomovethedrawerpartiallyorcompletelyoutofthe
rackmightcausetheracktobecomeunstableorcausethedrawertofalloutoftherack.
(R001part2of2)
Outputpowerandampereratings
Important:Makesurethatthepowerreceptacleisneartheequipmentandiseasilyaccessiblesothatthe
uninterruptiblepowersupply(UPS)canbedisconnectedquickly.
Toreducetheriskoffire,connectonlytoacircuitprovidedwithbranchcircuitovercurrentprotection
withanampereratinginaccordancewiththeNationalElectricalCode(NEC),ANSI/NFPA70oryourlocal
electricalcode:
©CopyrightLenovo2015,2017ix

UPSoutputpower120V208V230V
1500VA15ANotapplicable10A
2200VA20ANotapplicable10A
3000VA30A20A16A
Productsafety
•TheUPSconnectioninstructionsandoperationsdescribedinthemanualmustbefollowedinthe
indicatedorder.
•Important:Toreducetheriskoffire,theunitconnectsonlytoacircuitprovidedwithbranchcircuit
overcurrentprotectionasdescribedinthismanual,inaccordancewiththeNationalElectricCode,
ANSI/NFPA70.
TheupstreamcircuitbreakerforNormalACandBypassACmustbeeasilyaccessible.Theunitcanbe
disconnectedfromACpowersourcebyopeningthiscircuitbreaker.Thiscircuitbreakerisusedfor
backfeedprotectionandmustcomplywithIEC/EN62040-1(thecreepageandclearancedistancesshall
meetthebasicinsulationrequirementsforpollutiondegree2).
•Disconnectionandovercurrentprotectiondevicesshallbeprovidedbyothersforpermanentlyconnected
ACinput(NormalACandBypassAC)andACoutputcircuits.
•CheckthattheindicationsontheratingplatecorrespondtoyourACpoweredsystemandtotheactual
electricalconsumptionofalltheequipmenttobeconnectedtothesystem.
•ForPLUABLEEQUIPMENT,thesocket-outletshallbeinstalledneartheequipmentandshallbe
easilyaccessible.
•Neverinstallthesystemnearliquidsorinanexcessivelydampenvironment.
•Neverletaforeignbodypenetrateinsidethesystem.
•Neverblocktheventilationgratesofthesystem.
•Neverexposethesystemtodirectsunlightorsourceofheat.
•Ifthesystemmustbestoredpriortoinstallation,storagemustbeinadryplace.
•Theadmissiblestoragetemperaturerangeis-15ºCto+50ºC.
•ThisunitisnotdesignedtoconformtoANSI/NFPA75andthereforeisnotforuseinANSI/NFPA
75-certifieddatacenters.
•AlthoughtheUPSdoesnotcontainanti-backfeed(ABF)relays,somebackfeedprotectionisprovided.
Forexample,ifsomecomponentsaredamagedinbatterymode,theoutputvoltagemayfeedback
totheinput.Inthiscase,acurrenttransformer(CT)isusedtodetectthebypasscurrentfeedback
voltage.Ifacurrentbackfeedfaultconditionisdetected,theUPSwillterminatetheinverteroutputto
avoidpersonalinjury.
x 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's uide

Chapter1.Introduction
ThankyouforselectingaLenovoproducttoprotectyourelectricalequipment.
Readthismanualtotakefulladvantageofthefeaturesofyourequipment.
Beforeinstallingyourequipment,readthesafetyinstructions.Then,followtheinstructionsinthismanual
forsettingupandusingtheproduct.
TodiscovertheentirerangeofLenovoproductsandtheoptionsavailablefortheLenovoUPSdevice,we
inviteyoutovisitourwebsiteorcontactyourLenovorepresentative.
Noticesandstatements
ThecautionanddangerstatementsinthisdocumentarealsointhemultilingualSafetyInformation
document,whichisontheLenovoWebsiteathttps://support.lenovo.com/documents/LNVO-DOCS.Each
statementisnumberedforreferencetothecorrespondingstatementintheSafetyInformationdocument.
Noticesandstatementsinthisdocument
Thefollowingnoticesandstatementsareusedinthisdocument:
•Note:Thesenoticesprovideimportanttips,guidance,oradvice.
•Important:Thesenoticesprovideinformationoradvicethatmighthelpyouavoidinconvenientor
problemsituations.
•Attention:Thesenoticesindicatepossibledamagetoprograms,devices,ordata.Anattentionnoticeis
placedjustbeforetheinstructionorsituationinwhichdamagemightoccur.
•Caution:Thesestatementsindicatesituationsthatcanbepotentiallyhazardoustoyou.Acaution
statementisplacedjustbeforethedescriptionofapotentiallyhazardousproceduresteporsituation.
•Danger:Thesestatementsindicatesituationsthatcanbepotentiallylethalorhazardoustoyou.A
dangerstatementisplacedjustbeforethedescriptionofapotentiallylethalorhazardousprocedure
steporsituation.
Environmentalprotection
Lenovohasimplementedanenvironmental-protectionpolicy.Productsaredevelopedaccordingtoan
eco-designapproach.
Substances
ThisproductdoesnotcontainCFCs,HCFCsorasbestos.
Packing
Toimprovewastetreatmentandfacilitaterecycling,separatethevariouspackingcomponents.
•Thecardboardweusecomprisesover50%ofrecycledcardboard.
•Sacksandbagsaremadeofpolyethylene.
©CopyrightLenovo2015,20171

•Packingmaterialsarerecyclableandbeartheappropriateidentificationsymbol .
MaterialsAbbreviations
Numberinthesymbols
PolyethyleneterephthalatPET01
High-densitypolyethyleneHDPE02
PolyvinylchloridePVC03
Low-densitypolyethyleneLDPE04
PolypropylenePP05
PolystyrenePS06
Follow all local regulations for the disposal of packing materials.
Refer to the Lenovo Environmental Notices and User's Guide, provided on the Lenovo Web site at
https://support.lenovo.com/documents/LNVO-DOCS.
End of life
Lenovo will process products at the end of their service life in compliance with local regulations. Lenovo
works with companies in charge of collecting and eliminating our products at the end of their service life.
Product
The product is made up of recyclable materials. Dismantling and destruction must take place in compliance
with all local regulations concerning waste. At the end of its service life, the product must be transported to a
processing center for electrical and electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations
concerning batteries.
The battery pack can be removed to comply with regulations and in view of correct disposal.
With the Lenovo UPS device, you can eliminate the effects of power disturbances and guard the integrity
of your equipment. Providing outstanding performance and reliability, the Lenovo UPS device's unique
benefits include:
2 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's uide

•Trueonlinedouble-conversiontechnologywithhighpowerdensity,utilityfrequencyindependence,and
powergeneratorcompatibility.
•AdvancedBatteryManagement(®ABM)technologythatusesadvancedbatterymanagementtoincrease
batteryservicelife,optimizerechargetime,andprovideawarningbeforetheendofusefulbatterylife.
•SelectableHighEfficiencymodeofoperation.
•Standardcommunicationoptions:oneRS-232communicationport,oneUSBcommunicationport,and
relayoutputcontacts.
•UPSNetworkManagementCardwithenhancedcommunicationcapabilities.
•ExtendedruntimewithuptofourExtendedBatteryModules(EBMs)perUPS.
•Firmwarethatiseasilyupgradablewithoutaservicecall.
•RemoteOn/OffcontrolthroughRemoteOn/Off(ROO)andRemotePowerOff(RPO)ports.
Chapter1.Introduction3

4 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's uide

Chapter2.Presentation
Standardinstallations
Description
Weights
(lb/kg)
Dimensions(inch/mm)
DxWxH
8kVA3:1PowerModule51/2327.6x17.3x5.1/700x440x130
8kVAPowerModule(1:1)42/1927.6x17.3x5.1/700x440x130
11kVA3:1PowerModule51/2327.6x17.3x5.1/700x440x130
11kVAPowerModule(1:1)46/2127.6x17.3x5.1/700x440x130
8kVA/11kVABatteryModule143/6526.8x17.3x5.1/680x440x130
Rackinstallation
Towerinstallation
Shippingbracketkit
IfyouareshippingtheUPSanditsassociatedEBMspreinstalledinarack,youmustusetheshipping
bracketkittopreventdamageduringshipment.ThekitisavailablefromLenovo.Refertotheinstructionsin
thekittoinstallthebracketsproperly.ThebracketsarenotrequiredwhentheUPSandEBMsareinstalledin
apre-positionedrack.
©CopyrightLenovo2015,20175

Rearpanels
Figure.5594-8KX,5594-8PX
Figure2.5594-9KX,5594-9PX
RS232communicationport
USBcommunicationport
Dry(relay)contactscommunicationport
ConnectorforRemoteOn/Off(ROO)control
Connectorsforautomaticrecognitionofbattery
module
ConnectorforRemotePowerOff(RPO)control
SlotwhereUPSNetworkManagementCardis
installed
Connectorforbatterymodulepower
TerminalblocksforACpowerinputandoutput
ConnectorforHotSwapMBPdetection
Figure3.5594-9BXExtendedBatteryModule
Connectorsforbatterymodules(totheUPSor
totheotherbatterymodules)
Connectorsforautomaticrecognitionofbattery
modules(UPS-to-EBMorEBM-to-EBM)
Batterycircuitbreaker
Controlpanel
TheUPShasafive-buttongraphicalLCDfrontpanel.ItprovidesusefulinformationabouttheUPSitself,
loadstatus,events,measurements,andsettings.Italsoprovidesamethodtochangesettings.
6 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's uide

Thefollowingtableshowstheindicatorstatusanddescription:
IndicatorStatusDescription
reen
OnTheUPSisoperatingnormallyin
OnlineorinHighEfficiencymode.
Orange
OnTheUPSisinBatterymode.
Orange
OnTheUPSisinBypassmode.
Red
OnTheUPShasanactivealarmorfault.
SeeChapter8“Troubleshooting”on
page57foradditionalinformation.
LCDdescription
After5minutesofinactivity,theLCDdisplaysthescreensaver.
TheLCDbacklightautomaticallydimsafter10minutesofinactivity.Pressanybuttontorestorethescreen.
Chapter2.Presentation7

ThefollowingtabledescribesthestatusinformationprovidedbytheUPS.
Note:Ifanyotherindicatordisplays,seeChapter8“Troubleshooting”onpage57foradditionalinformation.
Operation
statusCauseDescription
IsBatteryBeing
Charged?
Standbymode TheUPSoutputisOff.Equipmentisnotpowereduntil
buttonispressed.
Yes
Onlinemode TheUPSisoperatingnormally.TheUPSispoweringandprotecting
theequipment.
Yes
Batterymode
1beepevery10
seconds
Autilitypowerfailurehasoccurred
andtheUPSisinBatterymode.
TheUPSispoweringtheequipment
withbatterypower.Prepareyour
equipmentforshutdown.
No
Endofbackup
time
1beepevery3
seconds
TheUPSisinBatterymodeandthe
batterypacksarerunninglow.
Thiswarningisapproximate,andthe
actualtimetoshutdownmightvary
significantly.
DependingontheUPSloadand
numberofExtendedBatteryModules
(EBMs),the"BatteryLow"warning
mightoccurbeforethebatterypacks
reach20%capacity.
No
8 6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's uide
Other manuals for RT8.0kVA
1
This manual suits for next models
1
Table of contents
Other Lenovo UPS manuals

Lenovo
Lenovo RT5.0kVA User manual

Lenovo
Lenovo 5594-6KX User manual

Lenovo
Lenovo Smart 750XLa User manual

Lenovo
Lenovo IBM UPS5000 User manual

Lenovo
Lenovo RT8.0kVA User manual

Lenovo
Lenovo RT1.5kVA User manual

Lenovo
Lenovo 5594-5KX User manual

Lenovo
Lenovo 55948KX User manual

Lenovo
Lenovo RT1.5kVA User manual

Lenovo
Lenovo T1kVA User manual