manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Leviton
  6. •
  7. Accessories
  8. •
  9. Leviton OSSMD-FT User manual

Leviton OSSMD-FT User manual

WARNINGS AND CAUTIONS:
• Tobeinstalledand/orusedinaccordancewithappropriateelectricalcodesandregulations.
• Ifyouareunsureaboutanypartoftheseinstructions,consultaqualiedelectrician.
• Controllingaloadinexcessofthespeciedratingswilldamagetheunitandposeriskofre,electricshock,personalinjuryordeath.
Checkyourloadratingstodeterminesuitabilityforyourapplication.
• Donotinstallthisunittocontrolareceptacle.
WARNINGS AND CAUTIONS:
• Donottouchthesurfaceofthelens.Cleanoutersurfacewithadampclothonly.
• Disconnectpoweratcircuitbreakerorfusewhenservicing,installingorremovingxture.
• Usethisdeviceonlywithcopperorcoppercladwire.WithaluminumwireuseonlydevicesmarkedCO/ALRorCU/AL.
TwoCircuit(OneLocation)orMulti-Location
Multi-Technology Designer Wall Switch Occupancy Sensor with Dual Relays
California Title 24 2005 Compliant
Cat. No. OSSMD-MD, OSSMD-FT, OSSMD-GD
Incandescent/Tungsten:800W@120VPrimary/SecondaryBallast:1200VA@120VPrimary-800VA@120VSecondary
Ballast:2700VA@277VPrimary-1200VA@277VSecondaryMotor:1/4hp@120VPrimary/Secondary
Operating Temperature Range:0°Cto50°C
Relative Humidity:20%to90%non-condensing
No Minimum Load Required
Compatiblewithincandescentlamps,low-voltagelightingwithelectronicandmagnetictransformers,electronicandmagneticuorescentballasts,andfans.
INSTALLATION INSTRUCTIONS
TOOLS NEEDED TO INSTALL YOUR SENSOR
Slotted/PhillipsScrewdriver ElectricalTape 
Pliers   Cutters  
SmallSlottedScrewdriver
• Leviton’sDecora
®
styledesign
• Sensorcanbegangedtogetherwithotherunitsinamultiple-switch
wallplate.
• Self-AdaptiveTechnologyadjuststooccupancypatternsofuseinauto
adaptmode.
• TheAdaptingTime-outwalk-throughfeaturepreventslightsfrom
remainingONforanextendedperiodafteronlyamomentary
occupancy.
• Switchestwoseparateloadcircuits.
• Two(MDandGDmodels)convenientPush-Buttonsprovidemanual
ON/OFFswitchingatanytime.
• Adjustablehorizontaleldofview.
• IntegratedphotocellpreventslightsfromturningONwhenroomis
adequatelyilluminatedbynaturallight.
• TrueZero-Crossforprimaryrelayprovidesmaximumcontactlifeand
compatibilitywithelectronicballasts.
• Dualdetectiontechnology,bothPassiveInfraredandUltrasonic.Can
beconguredasUltrasonicOnlybydisablingPassiveInfrared.
Leviton'sDesignerMulti-TechnologyWallSwitchOccupancySensor,
Cat.No.OSSMD,isdesignedtodetectmotionusingthepassiveinfrared
(PIR)sensorfromsources(suchasapersonenteringaroom)withinits
eld-of-view(monitoredspace)andautomaticallyswitchlightsON.The
OccupancySensorsensesmotionwithinitsmaximumcoverageareaof
2400sq.ft(223m
2
).TheUltrasonic(US)sensorsworkwiththePIRto
keepthelightsONwhenoccupied.ThecontrolledlightswillremainON
untilnomotionisdetectedandthescheduledtime-delayhasexpired,at
whichpointthelightswillbeturnedOFF.Inadaptingtime-outmodethe
sensoradaptsitstimedelaysettingstotheoccupancypatternsofaroom.
TheOSSMD-MDisanOccupancySensorthatisdesignedtocontroltwo
separatelightingcontrolcircuitsfromasingleunit.Thisallowstheuserto
replacetwoswitcheswithasingleunitthatwillprovidetheconvenience
andenergysavingsofanoccupancysensor.Itisadualrelaydevice,
relayonecanbeAutoONorManualONandrelaytwoisManualON
only.ThedevicecontainsaphotocellthatprovidesanAmbientLightHold
Offfunctionforrelaynumberone.BothrelaysoperateasAutoOFF.The
devicecanbeconguredforeitherUltrasonicwithPIRorUltrasonicOnly
modesofoperation.
TheOSSMD-GDhasallthefunctionalityoftheOSSMD-MDwithouta
neutralconductor.Itisintendedforuseinretrotapplicationswherea
neutralisnotavailableinthewallbox.
TheOSSMD-FTmodelisintendedforapplicationssuchasacommercial
bathroomwhereaconvenienceexhaustfanmustbecontrolled.The
tworelaysturnONintandembutremainONfordifferentdurations.
ThedevicecanbeconguredtobeeitherintheAutoONorManual
ONmodes.TheAutoONmodeutilizesthesensortechnologytoturn
ONwhilethesinglepushbuttononthefrontofthedeviceprovidesthe
ManualONactivation.AxedtimedelayOFFof10minutes,whichstarts
whentherstrelayturnsoff,willapplytothesecondrelayinbothofthese
modesofoperation.ItcanbeconguredforeitherUltrasonicwithPIR
orUltrasonicOnlymodesofoperation.Thisdevicerequiresaneutral
conductor.
Cat. No. OSSMD is ETL listed, cETL listed and conforms to California
Title 24 requirements.
ThePIROccupancySensorusesasmallsemiconductorheatdetector
thatresidesbehindamulti-zoneopticallens.ThisFresnellens
establishesdozensofzonesofdetection.TheSensorissensitivetothe
heatemittedbythehumanbody.InordertoinitiallytriggertheSensor,
thesourceofheatmustmovefromonezoneofdetectiontoanother.The
deviceismosteffectiveinsensingmotionacrossitseld-of-viewanditis
lesseffectivesensingmotiontowardsorawayfromitseld-of-view.Keep
thisinmindwhenselectingtheinstallationlocation(refer to Field-of-View
diagrams).
TheUSOccupancySensorusesanon-audible,highfrequency(40kHz)
tosenseDopplershiftscausedbymotioninthespace.TheUSismore
sensitivetosmallmotionanddoesnotrelyonlineofsightfordetection.If
bothsensorshavenotdetectedanymotionforthesettimeoutperiod,the
relaysandtheircorrespondingloadswillbeturnedOFF.
Notethatoccupancysensorsrespondtorapidchangesintemperature,so
careshouldbetakennottomountthedevicenearaclimatecontrolsource
(i.e.radiators,airexchanges,andairconditioners).Hotorcolddraftswill
looklikebodymotiontothedeviceandwilltriggeritiftheunitismountedtoo
close.It is recommended to mount the Occupancy Sensor at least 6 feet
away from a climate control source.
Inaddition,itisalsorecommendedNOTtomounttheOccupancySensor
directlyunderalargelightsource.Largewattagebulbs(greaterthan
100Wincandescent)giveoffalotofheatandswitchingthebulbcausesa
temperaturechangethatcanbedetectedbythedevice.
MounttheOccupancySensoratleast6ft.awayfromlargebulbs.Ifitis
necessarytomountthedevicecloser,lowerthewattageofthebulbdirectly
overhead.
WARNING:TO AVOID FIRE, SHOCK, OR DEATH; TURN
OFF POWER atcircuitbreakerorfuseandtestthatpoweris
offbeforewiring!
Step 1
/./&&
/./&&
/./&&
/./&&
/./&&
/./&&
/./&&/./&&
/./&&
/./&&
/./&&
/./&&
• Pulloffpre-cutinsulationfromsensorleads.
• Makesurethattheendsofthewiresfromthewallboxarestraight
(cut if necessary).
• Removeinsulationfromeachwireinthewallboxasshown.
Preparing and connecting wires:
9/16"
(1.4 cm)
Strip Gage
(measure bare
wire here)
Cut
(if necessary)
Step 3
INSTALLING YOUR SENSOR
NOTE:UsecheckboxeswhenStepsarecompleted.
4
1
3
2
5
1.Line(Hot)
2.Neutral
3.Ground
4.Load
5.SecondaryLoad
Installing your Sensor - Single Location
Application:
Step 4
Identifying your wiring application
(most common):
Step 2
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor
Black
Blue
Red
Red
Green
Ground
Line
120/277VAC
60Hz
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor
Black
Blue
Red
Red (To Phase 2)
Green
Ground
Line
120/277VAC
60Hz
OSSMD-GD Wiring Methods
NOTE:TheoccupancysensorCat.No.OSSMD-GDdoesnotrequirea
neutralconnectioninordertooperate.Itmusthaveagroundconnection.
Usethegroundwireintheelectricalboxforgroundconnection.Ifthereis
nogroundwire,ensureelectricalboxisgroundedandattachgroundwire
toboxbyanapprovedconnectionmethod.
OSSMD-MD Wiring Methods
NOTE:TheoccupancysensorCat.No.OSSMD-MDrequiresaneutral
connectiontooperate.Usethegroundwireintheelectricalboxfor
groundconnection.Ifthereisnogroundwire,ensureelectricalboxis
groundedandattachgroundwiretoboxwithascrew.
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor
Black
Blue
Red
Red
Green
Ground
Line
120/277VAC
60Hz
White
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor
Black
Blue
Red
Red (To Phase 2)
Green
Ground
Line
120/277VAC
60Hz
White
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Fan/
Secondary
Load
Sensor
Black
Blue
Red
Red
Green
Ground
Line
120/277VAC
60Hz
White
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Fan/
Secondary
Load
Sensor
Black
Blue
Red
Red (To Phase 2)
Green
Ground
Line
120/277VAC
60Hz
White
OSSMD-FT Wiring Methods
NOTE:TheoccupancysensorCat.No.OSSMD-FTrequiresaneutral
connectiontooperate.Usethegroundwireintheelectricalboxfor
groundconnection.Ifthereisnogroundwire,ensureelectricalboxis
groundedandattachgroundwiretoboxwithascrew.
Installing your Sensor - Two Location Wiring
Application:
Step 5
WARNING:Ifyouareunsureaboutanypartoftheseinstructions,
consultaqualiedelectrician.
NOTE:EithersensorcanturnthelightsON.Bothsensorsmust
time-outtoOFF,orbothmanualbuttonsmustbepressedforthe
lightstoturnOFF.
NOTE:Allow1minuteforwarm-upafterconnectingandenergizing.
NOTE:BothoccupancysensorsCat.No.OSSMD-MDandOSSMD-FT
requireaneutralconnectioninordertooperate.Usethegroundwirein
theelectricalboxforgroundconnection.Ifthereisnogroundwire,ensure
electricalboxisgroundedandattachgroundwiretoboxwithascrew.
WARNING:Ifyouareunsureaboutanypartoftheseinstructions,
consultaqualiedelectrician.
NOTE:Allow1minuteforwarm-upafterconnectingandenergizing.
Hot (Black)
Phase 1
Neutral (White)
Primary
Load
Secondary
Load
Sensor 1 Sensor 2
Black
Black
Blue
Red
Blue
Red
Red
Red
Green
Ground
Green
Ground
Line
120/277VAC
60Hz
White
White
Hot (Black)
Phase 1
To Phase 2
Neutral (White)
Primary
Load
Secondary
Load
Sensor 1 Sensor 2
Black
Black
Blue
Red
Blue
Red
Red
Red
Green
Ground
Green
Ground
Line
120/277VAC
60Hz
White
White
DESCRIPTION
DI-000-OSSMD-00A
FEATURES
NOTE:Toaccesscontrolsettings,removethecontrolpanelcover.If
necessary,removethewarninglabelthatcoverstheadjustmentdials
(refer to Control Panel Diagram).
Factory Settings: Thesensorisshippedfromthefactorytowork
inalmostallsituations,withoutanyaddedadjustments.Thefactory
settingsare:Blindersopen,10minutesxedTime-Out,Lightsalways
turnONregardlessofexistinglightlevels,Mediumpassiveinfrared
(PIR)range,andHighUltrasonicrange.ThePIRandultrasonic
technologiesarebothactive.
Blinders:Theblindersaretwoindependentshuttersthatcannarrow
theeld-of-viewfromamaximumof180°downto32°.Theblinders
areoperatedbymovingtheblinderleverstowardsorawayfrom
thecenteroftheSensor.Theblinderleverscanbefoundabovethe
controldialsinthecontrolpanel(refer to Control Panel Diagram).
Time-Outs:TheSensorhasthreetypesofTime-Outs:Fixed,
Adapting,andWalkthrough.
• Fixed Time-Out:ThevalueofthisTime-Outisuserselected
throughtheuseoftheTimeControlSettings(refer to Control
Panel Diagram and Time-Out Settings).
• Adapting Time-Out:Whenactivated,thevalueofthisTime-Out
(30minutes)ischangedbytheSensorbasedonroomoccupancy
andlightingconditions.
• Walk-through Time-Out:ThevalueofthisTime-Outispresetto
2.5minutesandonlyexistsintheAdaptingTime-Outmode.
Fixed Time Delay:ThexedTime-Outvalueisselectedbyrotating
theTimeControldial.Therearefour(4)valuesfromwhichtochoose.
Eachmarkaroundthedialcorrespondstoadifferentvalueas
indicatedbelow(refer to Control Panel Diagram).
NOTE: Alltimedurationsareapproximatewithin±10seconds.
Adapting Time Delay:TheSensorhasbuiltinadaptingintelligence
thatmodiestheAdaptingTime-Outdurationinresponsetothe
occupancyconditionsoftheroomitisinstalledin.IftheSensor
detects“large,”infrequentmotionitwillINCREASEtheAdapting
Time-Outduration.IftheSensordetects“large,”frequentmotion(as
inseveralpersonsinaroomduringameeting),itwillDECREASEthe
time-outdurationonlyifitwasNEVERincreased(thisisbecausethe
built-inintelligencewillalwaysproceedinthedirectionof“increasing”
adaptingTime-Outonceithasincreaseditforanyoftheoccupancy
conditionssensed).TheAdaptingTime-Outdurationwillrangefrom10to
30minutesintimeplustheWalk-ThroughTimeDelay.
Walk-Through Time Delay:Thewalk-throughfeature,whichis
onlyactiveintheAdaptingTime-Outmode,isusefulwhenaroomis
momentarilyoccupied.Withthisfeature,theSensorwillturnthelights
OFFshortlyafterthepersonleavestheroom.Thewalk-throughfeature
worksinthefollowingmanner:Whenapersonenterstheroom,thelights
willturnON.Ifthepersonleavestheroombeforethewalk-throughtime-
outof2.5minutes,theSensorwillturnthelightsOFFafter2.5minutes.If
thepersonstaysintheroomforlongerthan2.5minutes,theSensorwill
insteadusethestoredAdaptingTimeDelay.
Iftheroomisoccupiedforlongerthan2.5minutes,theSensorwillenter
theOccupiedModewiththetime-outdurationspeciedbytheAdapting
Time-Outsetting.
IftheSensordetectsmotionwithin30secondsafterthelightsturnOFF,
itwillturnthelightsONandincreasethetime-outvalueby1.5timesthe
existingvalue.
TheAdaptingTime-Outmayberesettothebasevalueof30minutesby
rotatingtheTimeControltoanewtimeselectionvalueandthenbackto
theAdaptingTime-Outvalue(refer to Control Panel Diagram).
Ambient Light Override:TheAmbientLightOverrideisusedtokeep
thelightsOFFifthereisalreadyenoughnaturallightintheroom.
Forproperoperation,theAmbientLightOverrideadjustmentmustbe
performedwhenthereisenoughnaturallight(refer to the SETTINGS
section).Iftheadjustmentismadewhenthereislessnaturallight,the
lightsmaynotturnONeventhoughtheyareneededandwillrequire
manualactivationofthepush-buttonstoturnthelightsON.
NOTE: Theambientlightlevelinthecenterofaroomwillbedifferent
thanthelevelatthewallwheretheswitchislocated.
Ambient Light Dial:Theambientlightsettingisadjustedwiththe
AmbientLightDial(refer to Control Panel Diagram).TurningtheLight
Dialfullycounter-clockwise(CCW),setstheSensortomanualONmode
(see following section).IfthelightcontrolisinthefullyCWposition,
thelightswillturnONwhenevermotionisdetected,eveninfulldaylight.
IntermediatesettingswillcausethelightstoturnONonlywhenthe
ambientlightisbelowthelevelselectedbythelightcontrol.
NOTE:WhenthesettingisattheminimumCCWlevel,thelightswillstay
OFFwhentheroomisdim.Whenthesettingisatthemaximumlevel
clockwise(CW),thelightswillturnONwhentheroomisbright.
Manual ON Mode:WhenthelightcontrolisinthefullyCCWposition
thelightswillneverautomaticallyturnON.Inthismodethelightsneed
tobemanuallyturnedONbythepush-button,andwillturnOFFwiththe
absenceofmotion.
PIR RANGE: TodecreasePIRdetectionrangeandsensitivity,rotatethe
knobCCW(refer to Control Panel Diagram).Thedetectionrangecan
beadjustedfrom100%downto30%.
ULTRASOUND (US) SENSITIVITY AND PIR DISABLE:USsensitivity
canbeadjustedtoHIGH-MEDUIM-LOWbyholdingtheONbuttonfor
15seconds.TheLEDwillashtorepresenttheUltrasonicsensitivity
andPIRstatus.TappingthePrimaryorSecondaryONbuttonduringthe
desiredLEDashindicationwillsetthesensitivityandPIRstatus.Use
thefollowingchart:
NOTE:Theprogramtimesoutin30secondsfromthelastbuttonpress.
ThefactorysettingfortheUSsensitivityisHIGHwithPIRandUltrasonic
technologiesenabled.
Wall surface
Sensor
Mounting
screws
(2 places)
Testing your Sensor prior to completely
mounting in wall box:
Step 6
NOTE:Dresswireswithabendasshownindiagramtorelievestress
whenmountingdevice.
• Positionallwirestoprovideroominoutletwallboxfordevice.
• Partiallysecuredeviceusinglongmountingscrewsprovided.
• Restorepoweratcircuitbreakerorfuse.
NOTE:Allow1minuteforwarm-upafterenergizing.
NOTE:AllmodelsoftheOSSMDarefactorypresettoworkwithout
anyadjustments.Ifnecessary,adjusttheBlindersandPIRRange
Controltostopanyunwantedactivationofthelights(refer to
FEATURES section).
• ForadditionalTimeControlSettings(refer to the SETTINGS
section).
NOTE:ToavoidPERMANENTDAMAGEtotheunit,becareful
NOTTOOVERTURNthecontrolknobsorleverswhensettingthe
Sensor.Thecontrolscanbeaccessedbyremovingthewallplate
(ifapplicable)andcontrolpanelcover(refer to Control Panel
Diagram).Useasmallstraightbladescrewdrivertoadjustknobs
andblinderlevers.
NOTE:DONOTpressinonblinderleversoruseexcessiveforce
(refer to Control Panel Diagram).
• AttachtheControlPanelcoverwhenthedesiredsettingsare
complete.
If lights do not turn ON, refer to the TROUBLESHOOTING section.
TIME
1
2
A
3
RANGE
BLINDERS
LIGHT
4 7
10
4 7
10
S
la
s
h Mark
Blinder adjustment levers
Control Panel Cover
PUSH BUTTON(S)
Cat.No.OSSMD-FThasasinglepush-buttonswitchthattoggles
relaysandtheircorrespondingloads,ONandOFF.Iftherelaysare
OFF,therelayswillturnONwhenthepush-buttonispressed,and
remainONinthepresenceofmotion.Intheabsenceofmotion,the
SensorUnitwillTime-OutandturnrelayoneOFF.Relaytwowill
remainONforthexed10minuteadditionaldelay.Whenthatperiod
timesout,relaytwowillturnOFF.
IftherelaysandtheircorrespondingloadsareON,relayonewill
turnOFFwhenthebuttonispressed.Relaytwowillremainonfor
10minutesaftertheTime-Outexpires.Afterthesetwoevents,the
relayswillturnONwiththenextdetectedmotion.
Cat.No.OSSMD-MDandOSSMD-GDhavetwopush-button
switchesthattoggletherelaysandtheircorrespondingloads,ONand
OFF.Buttononecontrolsrelayoneandbuttontwocontrolsrelaytwo.
IftherelaysareOFF,therelayswillturnONwhentheirpush-buttonis
pressed,andremainONinthepresenceofmotion.Intheabsenceof
motion,theSensorUnitwillTime-OutandturnbothoftherelaysOFF.
IftherelaysandtheircorrespondingloadsareON,therelayswillturn
OFFwhentheircorrespondingbuttonsarepressed.Therelayswillstay
OFFregardlessofmotiondetected,untiltheTime-Outexpires.Afterthe
Time-Outexpires,therelayswillturnONwiththenextdetectedmotion.
NOTES:
• TheMotionIndicatorLEDwillblinkevery1secondwhilemotionis
detected.
• WhentheTime-OutexpiresandtherelaysturnOFFa30second
vacancyconrmationexiststoturntherelay(s)backON.Afterthis
timethedevicewillbeplacedintoalowerdetectionthresholdmode.
• InManual-ONmode,thebuttonmustbepressedtoturnthelights
ON.Intheabsenceofmotion,theunitwillTime-Outandturnthe
lightsOFF.
• IfManual-Onmodeisdesired,keeptheLightknobinthefully
counter-clockwise(CCW)position.
NOTE:ToavoidPERMANENTDAMAGEtotheunit,becarefulNOT
TOOVERTURNoruseexcessiveforcewhensettingthecontrolknobs
orleversofCatNo.OSSMD.Useasmallstraightbladescrewdriverto
adjusttheknobsandyourngertoadjusttheblinderlevers.
1. RemoveDecora®wallplateandControlPanelCoverfromSensor.
2. RotatetheTimedialtoselectthedesiredxedTime-Outvalue.
3. IftheSensorisinstalledwithin6feetofanairduct,rotatetheRange
Control1/4turncounter-clock-wise(CCW).
4.Set the Ambient Light Level - AMBIENT LIGHT:Cat.No.OSSMD
hasanadjustmenttodetermineatwhatminimumambientlight
leveltheunitwilloperate.Theadjustmentshouldbemadewhenthe
ambientlightisatthelevelwherenoarticiallightisneeded.Follow
thesestepstomakeamoreaccurateadjustmentofthelightcontrol.
ThisfeaturewillnotworkinManual-Onmode.
A. WiththelightsON,rotatetheTimeControlfullyCCWtothesetthe
Time-Outtothethirty(30)secondtestmode(refertoControlPanel
Diagram).
B. RotatetheLightControlfullyCCW.
C. ManuallyturnOFFthelights.
D. RotatetheLightControlclockwise(CW)SLOWLY,untilthelights
turnON.Thisisthesettingforthecurrentleveloflightintheroom.
 NOTE:WhenthelightcontrolisinthefullyCCWpositionthelights
willneverautomaticallyturnON.ThisistheManual-Onmode,
wherethelightsneedtobemanuallyturnedONbythepush-
button,andwillturnOFFwiththeabsenceofmotion.
  IfthelightcontrolisinthefullyCWposition,thelightswillturnON
whenevermotionisdetected,eveninfulldaylight.
  IntermediatesettingswillcausethelightstoturnONonlywhenthe
ambientlightisbelowthelevelselectedbythelightcontrol.
 NOTE:Theambientlightinaroomwillchangewiththetimeofday
andtheseasonoftheyear.
5. Time-Out Settings:
A. AdjusttheTimedial.TheSensorAmberLEDwillashtwiceeach
timetheTimedialispointedatanewTime-Outvalue.TheTime-
Outvaluesfornon-adaptingmodeare:
NOTE:Toreturntoadaptingmode,rotatetheTimedialtofullCW
position(Asetting).BesuretheTimedialisrotateduntilanAmber
LEDashisissuedtobesureanewsettingwasselected.
6. Ifdesired,adjusttheblinderstoblockanyunwantedmotion.
(/)SlashMark
1
2
3
A
30secondxedtime-outforperformingawalktest
10minutesxedtime-out
20minutesxedtime-out
30minutesxedtime-out
AutoAdapting
Value of TimeFace Marking
FEATURES
SETTINGS OPERATION
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
LevitonwarrantstotheoriginalconsumerpurchaserandnotforthebenetofanyoneelsethatthisproductatthetimeofitssalebyLevitonisfreeofdefectsinmaterialsandworkmanshipundernormalandproperuseforveyearsfromthepurchasedate.Leviton’sonlyobligationistocorrectsuchdefectsbyrepairorreplacement,atitsoption,ifwithinsuchveyearperiodtheproductisreturnedprepaid,
withproofofpurchasedate,andadescriptionoftheproblemtoLeviton Manufacturing Co., Inc., Att: Quality Assurance Department, 59-25 Little Neck Parkway, Little Neck, New York 11362-2591.Thiswarrantyexcludesandthereisdisclaimedliabilityforlaborforremovalofthisproductorreinstallation.Thiswarrantyisvoidifthisproductisinstalledimproperlyorinanimproperenvironment,
overloaded,misused,opened,abused,oralteredinanymanner,orisnotusedundernormaloperatingconditionsornotinaccordancewithanylabelsorinstructions.There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose,butifanyimpliedwarrantyisrequiredbytheapplicablejurisdiction,thedurationofanysuchimpliedwarranty,
includingmerchantabilityandtnessforaparticularpurpose,islimitedtoveyears.Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation.Theremediesprovidedhereinaretheexclusiveremediesunderthiswarranty,
whetherbasedoncontract,tortorotherwise.
1. IfthereisnoresponsefromtheunitandtheLEDneverblinksor
thepushbuttondoesnotactivatethelights1-1/2minutesafter
powerisapplied,thenuninstalldeviceandverifywiring(Step 4).
2. IfthelightsconstantlystayON,evenwhentheroomisunoccupied:
A.ChecktheTimesetting.Seehowthistimecomparestohow
longthelightsstayON.
B.TryloweringthePIRRangeControl.Rotatetheknob
counterclockwiseabout30°.
C.Iftheproblempersists,tryreducingagain.
NOTE:DonotreducesomuchthattheSensorUnitcannotsee
normaloccupancy.
D.TryloweringtheUltrasonicSensitivity.
E.BesuretousetheBlinderstoblockanyunwantedhallway
trafc.
F. Checkforreectedheat/motionastheSensorUnitmaybe
seeingmotionthroughawindow.
G.CheckforadjacentHVACand/orheaterducts.
TROUBLESHOOTING
Lens
Blinders
Control panel
cover
Push buttons
LED window
US sensor ports
Thisequipmenthasbeentestedandfoundtocomplywiththelimits
foraClassAdigitaldevice,pursuanttopart15oftheFCCRules.
Theselimitsaredesignedtoprovidereasonableprotectionagainst
harmfulinterferencewhentheequipmentisoperatedinacommercial
environment.Thisequipmentgenerates,usesandcanradiateradio
frequencyenergyand,ifnotinstalledandusedinaccordancewith
theinstructionmanual,maycauseharmfulinterferencetoradio
communications.Operationofthisequipmentinaresidentialarea
islikelytocauseharmfulinterferenceinwhichcasetheuserwillbe
requiredtocorrecttheinterferenceattheirownexpense.
FCC COMPLIANCE STATEMENT
• Fortechnicalassistancecontactusat1-800-824-3005
• Visitourwebsiteatwww.leviton.com
PRODUCT INFORMATION
• Securedevicebyrmlytighteningmountingscrews.
• InstallDecora®stylewallplate(soldseparately).
Wall surface
Device mounting screw
(2 places)
Wallplate
Wallplate
mounting
screw
(2 places)
20 ft (6.1 m)
small motion
30 ft (9.1 m)
20 ft (6.1 m)
small motion
40 ft
(12.2 m)
Field - of - View (Horizontal)
40 ft.
(12.2 m)
4 ft.
(1.2 m)
Sensor
Side (Vertical) Field - of - View
DI-000-OSSMD-00A2008©LevitonMfg.Co.,Inc.
Control Panel Diagram
US Sensitivity and PIR Disable
3 amber flashes High ultrasonic sensitivity, PIR enabled
2 amber flashes Medium ultrasonic sensitivity, PIR enabled
1 amber flash Low ultrasonic sensitivity, PIR enabled
3 green flashes High ultrasonic sensitivity, PIR disabled
2 green flashes Medium ultrasonic sensitivity, PIR disabled
1 green flash Low ultrasonic sensitivity, PIR disabled
7. ReplacetheControlPanelCoverandDecora®wallplate.

This manual suits for next models

5

Other Leviton Accessories manuals

Leviton 37820 User manual

Leviton

Leviton 37820 User manual

Leviton decora LEVODS15TDW User manual

Leviton

Leviton decora LEVODS15TDW User manual

Leviton ODS10-ID Series User manual

Leviton

Leviton ODS10-ID Series User manual

Leviton Decora ODS10-IQ User manual

Leviton

Leviton Decora ODS10-IQ User manual

Leviton OSC04-I User manual

Leviton

Leviton OSC04-I User manual

Leviton 9864-LED User manual

Leviton

Leviton 9864-LED User manual

Leviton OPB15 User manual

Leviton

Leviton OPB15 User manual

Leviton ZW15R User manual

Leviton

Leviton ZW15R User manual

Leviton OSMHD-VDW User manual

Leviton

Leviton OSMHD-VDW User manual

Leviton enocean alliance WAC1x-M9N User manual

Leviton

Leviton enocean alliance WAC1x-M9N User manual

Leviton OSW12-M User manual

Leviton

Leviton OSW12-M User manual

Leviton OSW12-M0W User manual

Leviton

Leviton OSW12-M0W User manual

Leviton OSC10-M0W User manual

Leviton

Leviton OSC10-M0W User manual

Leviton 5207-S00 User manual

Leviton

Leviton 5207-S00 User manual

Leviton Lumina ZSC15 User manual

Leviton

Leviton Lumina ZSC15 User manual

Leviton ODS15-I1I User manual

Leviton

Leviton ODS15-I1I User manual

Leviton Acenti ACP10 User manual

Leviton

Leviton Acenti ACP10 User manual

Leviton OSM3D-DDW User manual

Leviton

Leviton OSM3D-DDW User manual

Leviton OFDUZ User manual

Leviton

Leviton OFDUZ User manual

Leviton OMNISTAT2 Mounting instructions

Leviton

Leviton OMNISTAT2 Mounting instructions

Leviton OSFHP-ITW User manual

Leviton

Leviton OSFHP-ITW User manual

Leviton Solo Sensor ZLS05-ILW User manual

Leviton

Leviton Solo Sensor ZLS05-ILW User manual

Leviton OSWHB-I User manual

Leviton

Leviton OSWHB-I User manual

Leviton ODP10-I1I User manual

Leviton

Leviton ODP10-I1I User manual

Popular Accessories manuals by other brands

Quincy lab 140AE-1 operating manual

Quincy lab

Quincy lab 140AE-1 operating manual

HomePro ZIR000 user manual

HomePro

HomePro ZIR000 user manual

DOL 20SCR Technical user guide

DOL

DOL 20SCR Technical user guide

RAB Smart Task installation manual

RAB

RAB Smart Task installation manual

Kemppi KMS 300 quick guide

Kemppi

Kemppi KMS 300 quick guide

Stearns 57,500 Series Installation and service instructions

Stearns

Stearns 57,500 Series Installation and service instructions

iGuzzini TWILIGHT COPENAGHEN manual

iGuzzini

iGuzzini TWILIGHT COPENAGHEN manual

Adelaide Annexe & Canvas Avan Deluxe installation guide

Adelaide Annexe & Canvas

Adelaide Annexe & Canvas Avan Deluxe installation guide

OHAUS 5000 instruction manual

OHAUS

OHAUS 5000 instruction manual

HOME8 WLS1300 quick start guide

HOME8

HOME8 WLS1300 quick start guide

MAXBOTIX MaxSonar quick start guide

MAXBOTIX

MAXBOTIX MaxSonar quick start guide

ioSmart iSmart56 Installation and user guide

ioSmart

ioSmart iSmart56 Installation and user guide

Focusrite Scarlett 18i8 user guide

Focusrite

Focusrite Scarlett 18i8 user guide

Velleman ED38105 user manual

Velleman

Velleman ED38105 user manual

JumpSport SkyBounce user manual

JumpSport

JumpSport SkyBounce user manual

Prima-Temp PRIYA Instructions for use

Prima-Temp

Prima-Temp PRIYA Instructions for use

Tefcold BC85I-BC85I W user manual

Tefcold

Tefcold BC85I-BC85I W user manual

Vaisala WMS302 user guide

Vaisala

Vaisala WMS302 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.