LG DELUXE HIGH WALL MINI SPLIT User manual

DELUXE HIGH WALL MINI SPLIT
INSTALLATION INSTRUCTIONS
IMPORTANT!
Please read this instruction sheet completely before installing the product.
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of
your job to install or service the system so it operates safely and efficiently.
CAUTION
: Improper installation, adjustment, alteration, service or maintenance can void the warranty.
The weight of the condensing unit requires caution and proper handling procedures when lifting or moving to avoid
personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
• Always wear safety eye wear and work gloves when installing equipment.
• Never assume electrical power is disconnected. Check with meter and equipment.
• Keep hands out of fan areas when power is connected to equipment.
• R-22 causes frostbite burns.
• R-22 is toxic when burned.
NOTE TO INSTALLING DEALER:
The Owners Instructions and Warranty are to be given to the owner or prominently displayed
near the indoor Furnace/Air Handler Unit.
P/No:3828A30087J
When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified, experienced electrician
should attempt to wire this system.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when
wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When transporting:
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when
lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your finger.
When installing...
... in a wall: Make sure the wall is strong enough to hold the unit's weight.
It may be necessary to construct a strong wood or metal frame to provide added support.
... in a room: Properly insulate any tubing run inside a room to prevent "sweating" that can cause dripping and water
damage to wall and floors.
... in moist or uneven locatinons: Use a raised concrete pad or concrete blocks provide a solid, level foundation for the
outdoor unit. This prevents water damage and abnormal vibration.
... in an area with high winds:
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
... in a snowy area(for Heat Pump Model): Install the outdoor unit on a raised platform that is higher than drifting snow.
Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Check carefully for leaks before starting the test run.
When servicing
•
Turn the power OFF at the main power box(mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit
being serviced.
• Installation or repairs made by unqualified persons can result in hazards to you and others.
Installation MUST conform with local building codes or, in the absence of local codes, with the National Electrical Code NFPA
70/ANSI C1-1993 or current edition and Canadian Electrical Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and
equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal
injury and/or death.
WARNING
Special warnings
ENGLISH

INSTALLATION OVERVIEW
2
The following should be always
observed for safety....................3
Installation of indoor, outdoor
unit................................................4
Flaring work and connection of
piping...........................................7
Connecting the cable between
indoor unit and outdoor unit..10
Checking the drainage and
Forming the piping..................12
Air purging ...............................14
Panel Front Assembly ............16
Test running .............................17
❏ Installation guide map
❏Four type "A" screws & plastic
anchors
❏Connecting cable
❏Pipes: Gas side....................1/2"
Liquid side.................1/4"
(Refer to page 4)
❏Insulation materials
❏Additional drain pipe
Outer Diameter......15.5mm(5/8")
❏Two type "B" screws
❏Level gauge
❏Screw driver
❏Electric drill
❏Hole core drill Ø50mm(1.97")
❏Horizontal meter
❏Flaring tool set
❏Specified torque wrenches
Liquid side - 1.8kg.m(13ft.lbs):9K,12K,18K
4.0kg.m(28.9ft.lbs):24K
Gas side - 5.5kg.m(39.8ft.lbs):9K, 12K
6.6kg.m(47.7ft.lbs):18K, 24K
(Refer to page 9)
❏Spanner......................Half union
❏A glass of water
❏Screw driver
❏Hexagonal wrench 4mm(5/32")
❏Gas-leak detector
❏Vacuum pump
❏Gauge manifold
❏Owner's manual
❏Thermometer
❏Holder Remote Control
Installation
Requirements Required Parts Required Tools

ENGLISH
THE FOLLOWING SHOULD BE ALWAYS OBSERVED FOR SAFETY
3
■
Be sure to read "THE FOLLOWING SHOULD BE ALWAYS OBSERVED FOR SAFETY" before installing the air
conditioner.
■
Be sure to observe the cautions specified here as they include important items related to safety.
■
The indications and meanings are as follows.
■
After reading this instructions, be sure to keep it together with the owner's manual in a handy place on the
customer's site.
WARNING : Could lead to death, serious injury, etc.
CAUTION
: Could lead to serious injury in particular environments when operated
incorrectly.
WARNING
Incorrect installation could cause injury due to fire,
electric shock, the unit falling or leakage of water.
Consult the dealer from whom you purchased the
unit or special installer.
Do not install it yourself (customer).
When installed in an insufficiently strong place,
the unit could fall causing injury.
Install the unit securely in a place which can bear
the weight of the unit.
Incorrect connection and fixing could cause fire.
Use the specified wires to connect the indoor and
outdoor units securely and attach the wires firmly
to the terminal board connecting sections so the
stress of the wires is not applied to the sections.
If the electrical part cover of the indoor unit and/or
the service panel of the outdoor unit are not
attached securely, it could result in a fire or
electric shock due to dust, water, etc.
Attach the electrical part cover to the indoor unit
and the service panel to the outdoor unit securely.
The use of defective parts could cause an injury
due to a fire, electric shock, the unit falling, etc.
Be sure to use the part provided or specified parts
for the installation work.
Check that the refrigerant gas does not leak after
installation is completed.
Incorrect installation could cause a personal
injury due to fire, electric shock, the unit falling
or leakage of water.
Perform the installation securely referring to the
installation instruction.
If the capacity of the power circuit is insufficient
or there is incomplete electrical work, it could
result in a fire or an electric shock.
Perform electrical work according to the installation
manual and be sure to use an exclusive circuit.
CAUTION
If there is a defect in the drainage/piping work,
water could leak from the unit and household
goods could get wet and be damaged.
Perform the drainage/piping work according
to the installation instruction.
If gas leaks and accumulates in the area
surrounding the unit, it could cause an explosion.
Do not install the unit in a place where an
inflammable gas leaks.

4
9K 1/2" 1/4" 7.5 7 15 20
(24.6ft)
(23ft) (50ft)
12K 1/2" 1/4" 7.5 7 15 20
(24.6ft)
(23ft) (50ft)
INSTALLATION OF INDOOR, OUTDOOR UNIT
Read completely, then follow step by step.
Select the best location
Indoor unit
■
Do not have any heat or steam near the unit.
■
Select a place where there are no obstacles in
front of the unit.
■
Make sure that condensation drainage can be
conveniently routed away.
■
Do not install near a doorway.
■
Ensure that the space around the left and right
of the unit is more than 50cm(19.7”). The unit
should be installed as high on the wall as
possible, allowing a minimum of 10cm(3.9”)
from ceiling.
■
Use a stud finder to locate studs to prevent
unnecessary damage to the wall.
Outdoor unit
■If an awning is built over the unit to
prevent direct sunlight or rain exposure,
make sure that heat radiation from the
condenser is not restricted.
■Ensure that the space around the back
and sides is more than 10cm(3.9”).
The front of the unit should have more
than 70cm(27.5”) of space.
■Do not place animals and plants in the
path of the warm air.
■Take the air conditioner weight into
account and select a place where noise
and vibration are minimum.
■Select a place so that the warm air and
noise from the air conditioner do not
disturb neighbors.
■
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be
sure to level the unit. Ensure the roof structure and
anchoring method are adequate for the unit location.
Consult local codes regarding rooftop mounting.
Piping length and elevation
More than 10cm(3.9")
More than 50cm(19.7")
More than 2m(6.6ft) More than 50cm(19.7")
More than 10cm(3.9") More than 10cm(3.9")
More
than 60cm(24")
More than 60cm(24")
More than 70cm(28")
Pipe Size
Capacity
(Btu/h)
GAS LIQUID
Max.
length
A (m)
Additional
Refrigerant
(g/m)
Max.
Elevation
B(m)
Standard
Length
(m)
In case more than 5m(16.4ft)
A
B
•Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
•Oil trap should be installed every 5~7 meters(16.4~23ft).
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
CAUTION
Install the indoor unit on the wall where the height
from the floors more than 2m(6.6ft).
CAUTION

ENGLISH
5
Open panel front
■First,Pull the grille bottom, then remove
screws(2 pieces), and close grille bottom
again.
■ The moment of lifting the both lower parts
of panel front, you can hear sound this
panel came out, In this time panel front is
separated
■ After pull down this panel a bit, and
separate connecting wire with product.
Pipe hole
Panel Front
Connector
A
Cover pipe and cover side remove
■Remove two screws(for fixing cover pipe)
■ Pull up the cover side of desired connecting
direction, then cover side is separated.
■In case connecting direction is left or right, path
through the hole of cover side.
B
When connecting pipe path through rear
wall, don’t remove the hole.
Drain hose junction
■Remove the rubber stopple of desired drain
direction.
■ As the following picture, Insert drain hose in the
handle of drain pan, and join drain hose and
connecting hose.
C
rubber cap
Only one
desiring direction
Connecting
part
Adhesive
Drain
hose
Preparing work for Installation
After removing the pipe hole, cut the burr for safety.
CAUTION

Plastic anchors
INSTALLATION GUIDE MAP
10mm(0.39")
INSTALLATION GU
INSTAIIATION GUIDE MAP
Put an Installation Guide Map
on the desired surface.
Make a hole with diameter of 6mm(0.24")
and depth of 30-35mm(1.18"~1.38") when
piercing a screw point.
Drive the fore plastic anchors into
drilled points.
Hang the hole of product at the upper
screws. (In this time, Remove the map)
(Falling attention)
Check the fixed product with light
power.
Look at suited horizon by horizontal
meter on the horizontal setting line,
and Fix lightly the map by adhesive
tape.
Drill the piercing part for connecting
pipe as diameter 50mm(1.97").
(In case of piercing rear surface)
Refer to No. 5 on this page when making a hole in the wall.
First, Drive the two points of the
upper parts by screws.
(Leave 10mm(0.39") for hanging product)
Drive the lower parts after facing
the hole of product with plastic
anchors, and fix completely the
upper screws.
In case of nothing wrong in the matter,
connect the pipe and the wire.
(Installation manual reference)
Horizontality
INSTALLATIONGUIDEMAP
Plastic anchors
INSTALLATIONGUIDEMAP
INSTALLATIONGUIDEMAP
Hanger hole
(Rear side of
product)
6
Preparing work for installation
Drill a hole in the wall
■
Drill the piping hole with a Ø50mm(1.97”)
hole core drill. Drill the piping hole at either
the right or the left with the hole slightly
slanted to the outdoor side.
5-7mm
(0.2~0.3")
Indoor WALL Outdoor
A
AB
CD
EF
GH
IJ
Sticking the installation guide map and fixing Indoor unit

ENGLISH
7
FLARING WORK AND CONNECTION OF PIPING
Flaring work
Main cause for gas leakage is due to defect in
flaring work. Carry out correct flaring work in the
following procedure.
Cut the pipes and the cable.
■Use the piping kit accessory or the pipes purchased
locally.
■
Measure the distance between the indoor and the
outdoor unit.
■
Cut the pipes a little longer than measured distance.
■
Cut the cable 1.5m(4.9ft) longer than the pipe length.
Burrs removal
■
Completely remove all burrs from the cut
cross section of pipe/tube.
■
Put the end of the copper tube/pipe in a
downward direction as you remove burrs in
order to avoid dropping burrs into the tubing.
A
B
Putting nut on
■
Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube
having completed burr removal.
(not possible to put them on after flaring work)
C
Copper
pipe
90°Slanted Uneven Rough
Bar
Copper pipe
Clamp handle Red arrow mark
Cone
Yoke
Handle
Bar
"A"
Pipe Reamer
Point down
Flaring work
■
Carry out flaring work using flaring tool as shown
below.
Firmly hold copper pipe in a die in the dimension
shown in the table above.
D
Check
■
Compare the flared work with figure below.
■
If flare is noted to be defective, cut off the flared
section and do flaring work again.
E
Flare nut
Copper tube
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged Cracked Uneven
thickness
= Improper flaring =
mm inch mm
Ø6.35 1/4 0~0.5
Ø9.52 3/8 0~0.5
Ø12.7 1/2 0~0.5
Ø15.88 5/8 0~1.0
Outside diameter A
Connection of piping
-Indoor
■
Preparing the indoor unit's piping and drain
hose for installation through the wall.
Route the indoor tubing and the drain hose
in the direction of rear left or right
A
Drain hose

8
Vinyl tape(narrow)
Connection
pipe
Connecting cable
Vinyl tape
(wide) Wrap with vinyl tape
Indoor
unit pipe
Pipe
■Wrap the area which accommodates the rear
piping housing section with vinyl tape.
■Bundle the piping and drain hose together by
wrapping them with vinyl tape over the range
within which they fit into the rear piping housing
section.
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Tape the tubing, drain hose and the connecting
cable. Be sure that the drain hose is located at
the lowest side of the bundle. Locating at the
upper side can cause drain pan to overflow
inside the unit.
B
NOTE: If the drain hose is routed inside the room,
insulate the hose with an insulation material*so that
dripping from "sweating"(condensation) will not damage
furniture or floors.
*Foamed polyethylene or equivalent is recommended.
Connecting
cable Gas side piping
Liquid side piping
Drain hose
Loop
Wrap the insulation material around the
connecting portion.
■ Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.
D
Plastic bands Insulation material
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
■When extending the drain hose at the indoor unit,
install the drain pipe.
Connecting the pipings to the in door unit and drain
hose to drain pipe
■ Align the center of the pipings and sufficiently
tighten the flare nut by hand.
C
Indoor unit tubing Flare nut Pipings
Torque wrench
Indoor unit tubing
Spanner (fixed)
Connection pipe
Flare nut
■Tighten the flare nut with a wrench.
Pipe Size[Torque]
GAS LIQUID
9K 1/2"[5.5kg.m] 1/4"[1.8kg.m]
12K 1/2"[5.5kg.m] 1/4"[1.8kg.m]
Capacity
(Btu/h)

ENGLISH
9
Connection of the
pipes-Outdoor
Align the center of the pipings and
sufficiently tighten the flare nut by hand.
Finally, tighten the flare nut with torque
wrench until the wrench clicks.
■When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
A
B
Outdoor unit
Liquid side piping
(Smaller diameter)
Gas side
piping
(Bigger
diameter)
Torque wrench
Outdoor unit
Gas side piping
(Bigger diameter)
Liquid side
piping
(Smaller
diameter)
Torque wrench
Outdoor unit
Liquid side piping
(Smaller diameter)
Gas side
piping
(Bigger
diameter)
Torque wrench
Pipe Size[Torque]
GAS LIQUID
9K 1/2"[5.5kg.m] 1/4"[1.8kg.m]
12K 1/2"[5.5kg.m] 1/4"[1.8kg.m]
Capacity
(Btu/h)
Installation Information (For right piping)
• Good case
For right piping, follow the instruction below.
■
Press on the upper side of clamp and
unfold the tubing to downward slowly.
• Bad case
■
Following bending type from right to left could
cause problem of pipe damage.
CAUTION
■
Bend the tubing to the right side of chassis.

CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT
10
1
Indoor Unit Outdoor Unit
2
3
4
1
2
3
4
5
6
GTo
branch
circuit
Ground
Power supply a
L1*
L2
Connecting cable(Low voltage) b
Terminal
(4P) Terminal
(6P)
Outdoor unit
Wiring Diagram
Terminal block
Over 5mm
(2")
Cover control
Conduit panel
Connecting
cable
Power supply
cord
*L1 is neutral for 115V models.
Connection of the cable
1. Remove the cover control from the unit
by loosening the 3 screws.
2. Dismount caps on the conduit panel.
3. Temporarily mount the conduit tubes on
the conduit panel.
4. Properly connect both the power supply
and low voltage lines to the
corresponding terminals on the terminal
block.
5. Ground the unit in accordance with local
codes.
6. Be sure to size each wire allowing
several inches longer than the required
length for wiring.
7. Use lock nuts to secure the conduit
tubes.
1. shows field wiring.
2. Separately wire the high and low voltage line.
3. Use heat-proof electrical wiring capable of
withstanding temperatures up to 167°F.
4. Use outdoor and waterproof connection cable
rated more than 300V for the connection between
indoor and outdoor unit.
(For example, Type SJO-WA)
• Be sure to comply with local codes while
running the wire from the indoor unit to
the outdoor unit(size of wire and wiring
method, etc).
• Every wire must be connected firmly.
• No wire should be allowed to touch
refrigerant tubing, the compressor or any
moving parts.
Connector trade size for this unit is 1/2".
Refer to "How to connect wiring to the
terminals" for instructions on connecting
depending on the wire type you are using.
WARNING
NOTE
NOTE
Power Supply
Model
Power source
9K 1ø, 115V 14 18 15A
12K 1ø, 115V 14 18 20A
AWG(MIN.)
ⓐⓑ
Fuse or breaker
Capacity

ENGLISH
11
G
Terminal
block
Cap
(Remove)
Clamp cord
Lock nut
Conduit panel
Loop
Round
terminal
Screw with
special washer
Screw with
special washer
Round terminal
Terminal plate
Wire
Wire
Round terminal
Insulation
Strip 25mm(15/16")
Strip 10mm(3/8")
Solid wire
Cap(Reuse)
Taping
(for sealing)
Low voltage line
(connecting cable)
Power supply line
(1ø, 115V, 208/230V)
Hole
(for low voltage line)
Strand wire
Connection method of the
connecting cable(Example)
(1) Dismount two-caps on the conduit panel.
(2) Make a hole appropriate for the passage of
connection cable through on cap by tool.
(for low voltage line)
(3) Pass the connecting cable through the hole.
(4)
Properly connect the cable on the terminal block.
(5) Fix the connection cable with clamp cord
provided on the unit not to have strain at the
terminal when the connection cable is pulled
outside up to a 35 pound weight.
(6) Wind the vinyl tape round the connecting cable
for sealing between the surface of the
connection cable and cap.
(7) Mount the taped part of cable on the cap.
(8) Finally, mount the holed cap with the
wound cable on the conduit panel.
When connecting each power wire to the
corresponding terminal, follow instructions "How to
connect wiring to the terminals" and fasten the wire
tightly with the fixing screw of the terminal plate.
How to connect wiring to the terminals
■For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter of wire-
cutting pliers, then strip the insulation to expose
the solid wire about 25mm(15/16")
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal plate.
(3) Using pliers, bend the solid wire to from a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the
terminal plater and tighten securely with the
terminal screw using a screwdriver.
■For strand wiring
(1) Cut the wire end with a wire cutter or wire-
cutting pliers, then strip the insulation to expose
the strand wiring about 10mm(3/8").
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal plate.
(3) Using a round terminal fastener or pliers,
securely clamp each stripped wire end with a
round terminal.
(4) Position the round terminal wire, and replace
and tighten the terminal screw using a
screwdriver.
Loose wiring may cause the terminal to
overheat or result in unit malfunction. A fire
hazard may also exist. Therefore, be sure all
wiring is tightly connected.
WARNING

12
CHECKING THE DRAINAGE AND FORMING THE PIPINGS
Form the piping
Form the piping by wrapping the
connecting portion of the indoor unit with
insulation material and secure it with two
kinds of vinyl tapes.
■
If you want to connect an additional drain
hose, the end of the drain outlet should be
routed above the ground. Secure the drain
hose appropriately.
In cases where the outdoor unit is
installed below the indoor unit perform
the following.
■Tape the piping, drain hose and
connecting cable from down to up.
■Secure the tapped piping along the exterior
wall using saddle or equivalent.
A
A
B
Taping
Drain hose
Pipings
Connecting cable
Trap is required to prevent water
from entering into electrical parts.
Seal small openings
around pipings with a
gum type sealer.
In cases where the Outdoor unit is
installed above the Indoor unit perform
the following.
■
Tape the piping and connecting cable from
down to up.
■
Secure the taped piping along the exterior wall.
Form a trap to prevent water entering the room.
■
Fix the piping onto the wall by saddle or
equivalent.
C
Seal a small opening
around the pipings
with gum type sealer.
Trap
Trap
Checking the drainage
To check the drainage.
■
Pour a glass of water on the evaporator.
■
Ensure the water flows through the drain
hose of the indoor unit without any leakage
and goes out the drain exit.
Drain piping
■
The drain hose should point downward for
easy drain flow.
B
■
Do not make drain piping.
Downward slope
Do not raise Accumulated
drain water Tip of drain hose
dipped in water
Air
Waving
Water
leakage Water
leakage Ditch
Less than
50mm gap
Water
leakage

13
ENGLISH
CAUTION
CAUTION
Air
Conditioner Circuit Breaker
Use a circuit
breaker or time
delay fuse.
Main power source
If a power plug is not to be used, provide a circuit breaker between power source and the
unit as shown below.
Connecting cable
Connect the cable to the indoor unit
1. Connect the wires to the terminals on the
control board individually according to the
outdoor unit connection.
•Ensure that the color of the wires of outdoor unit
and the terminal No. are the same as those of
indoor unit respectively.
(Refer to Wiring diagram on page10.)
•Be sure to refer to the wiring diagram label
inside the grille and carry out the correct
field wiring.
Wrong wiring can cause the unit to misoperate
to result in a fire hazard.
•Check local electrical codes and any specified
wiring instructions or limitations.
WARNING

14
AIR PURGING
Air purging
Air and moisture remaining in the refrigerant
system have undesirable effects as indicated
below.
■
Pressure in the system rises.
■
Operating current rises.
■
Cooling(or heating) efficiency drops.
■
Moisture in the refrigerant circuit may
freeze and block capillary tubing.
■
Water may lead to corrosion of parts in the
refrigeration system.
Therefore, the indoor unit and tubing between
the indoor and outdoor unit must be leak tested
and evacuated to remove any noncondensables
and moisture from the system.
Air purging with vacuum
pump
Preparation
■
Check that each tube(both liquid and gas
side tubes) between the indoor and
outdoor units have been properly
connected and all wiring for the test run
has been completed. Remove the service
valve caps from both the gas and the liquid
side on the outdoor unit. Note that both the
liquid and the gas side service valves on
the outdoor unit are kept closed at this
stage.
Leak test
■
Connect the manifold valve(with pressure
gauges) and dry nitrogen gas cylinder to
this service port with charge hoses.
■
Pressurize the system to no more than 150
P.S.I.G. with dry nitrogen gas and close the
cylinder valve when the gauge reading
reached 150 P.S.I.G. Next, test for leaks with
liquid soap.
Lo Hi
Indoor unit
Outdoor unit
Manifold valve
Charge hose
Nitrogen gas
cylinder(in vertical
standing position)
Pressure
gauge
A
B
■
Do a leak test of all joints of the tubing(both
indoor and outdoor) and both gas and liquid side
service valves.
Bubbles indicate a leak. Be sure to wipe off the
soap with a clean cloth.
■
After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening the
charge hose connector at the nitrogen cylinder.
When the system pressure is reduced to normal,
disconnect the hose from the cylinder.
Be sure to use a manifold valve for air
purging. If it is not available, use a stop valve
for this purpose. The "Hi" knob of the manifold
valve must always be kept close.
To avoid nitrogen entering the refrigerant system in a
liquid state, the top of the cylinder must be higher than its
bottom when you pressurize the system. Usually, the
cylinder is used in a vertical standing position.
CAUTION
CAUTION

15
ENGLISH
Evacuation
■
Connect the charge hose end described in the
preceding steps to the vacuum pump to
evacuate the tubing and indoor unit.
Confirm the "Lo" knob of the manifold valve is
open. Then, run the vacuum pump.
The operation time for evacuation varies with
tubing length and capacity of the pump. The
following table shows the time required for
evacuation.
■
When the desired vacuum is reached, close the
"Lo" knob of the manifold valve and stop the
vacuum pump.
Finishing the job
■
With a service valve wrench, turn the valve stem
of liquid side valve counter-clockwise to fully
open the valve.
■
Turn the valve stem of gas side valve
counter-clockwise to fully open the valve.
■
Loosen the charge hose connected to the gas side
service port slightly to release the pressure, then
remove the hose.
■
Replace the flare nut and its bonnet on the gas side
service port and fasten the flare nut securely with an
adjustable wrench. This process is very important to
prevent leakage from the system.
■
Replace the valve caps at both gas and liquid side
service valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.
C
D
(1) Remove the caps from the 2-way and 3-way
valves.
(2) Remove the service-port cap from the 3-way
valve.
(3) To open the 2-way valve turn the valve stem
counterclockwise approximately 90°, wait for
about 2~3 sec, and close it.
(4) Apply a soap water or a liquid neutral detergent
on the indoor unit connection or outdoor unit
connections by a soft brush to check for
leakage of the connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.
Soap water method
Gas side
Liquid side
Cap
Hexagonal wrench
2-way valve
(Open)
3-way valve
(Close)
Required time for evacuation when 30 gal/h
vacuum pump is used
10 min. or more 15 min. or more
If tubing length is less
than 10m (33 ft) If tubing length is longer
than 10m (33 ft)
Indoor unit
Outdoor unit
Lo Hi
Manifold valve
Vacuum pump
Pressure
gauge
Open Close

16
PANEL FRONT ASSEMBLY
First, Check the side cover assembly exactly,
Fix power cord in the bottom groove of cover
side left.
A
B
Assemble connecting lead wire with controller
and first fix the upper part of panel front, then
match the lower part of panel front
Panel Front
Connector
C
Drive two screws.

17
ENGLISH
TEST RUNNING
Settlement of outdoor unit
■
Anchor the outdoor unit with a bolt and nut Ø10mm(0.39")
tightly and horizontally on a concrete or rigid mount.
■
When installing on the wall, roof or rooftop, anchor the
mounting base securely with a nail or wire assuming the
influence of wind and earthquake.
■
In the case when the vibration of the unit is conveyed to the
hose, secure the unit with an anti-vibration rubber.
1.
Check that all tubing and wiring have been
properly connected.
2.
Check that the gas and liquid side service valves
are fully open.
Prepare remote control
Remove the battery cover
by pulling it according to the
arrow direction.
Insert new batteries making
sure that the (+) and (–) of
battery are installed correctly.
Reattach the cover by
pushing it back into position.
NOTE:
• Use 2 AAA(1.5volt) batteries. Do not use
rechargeable batteries.
• Remove the batteries from the remote control if the
system is not going to be used for a long time.
Evaluation of the performance
Operate unit for 15~20 minutes, then check the
system refrigerant charge:
1.
Measure the pressure of the gas side service
valve.
2.
Measure the temperature of the intake and
discharge of air.
NOTE: If the actual pressure are higher than shown, the
system is most likely over-charged, and charge
should be removed. If the actual pressure are
lower than shown, the system is most likely
undercharged, and charge should be added.
The air conditioner is now ready for use.
A
C
B
Bolt
Tubin
g
connection
This is performed when the unit is to be
relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the
outdoor unit without loss in refrigerant gas.
CAUTION:
Be sure to perform Pump Down procedure with the
unit cooling mode.
Pump Down Procedure
1. Connect a low-pressure gauge manifold hose to the
charge port on the gas side service valve.
2. Open the gas side service valve halfway and purge
the air from the manifold hose using the refrigerant
gas.
3. Close the liquid side service valve(all the way in).
4. Turn on the unit's operating switch and start the
cooling operation.
5. When the low-pressure gauge reading becomes 1
to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the
gas side valve stem and then quickly turn off the
unit. At that time, Pump Down has been completed
and all refrigerant gas will have been collected in
the outdoor unit.
PUMP DOWN
3. Ensure the difference between the intake
temperature and the discharge is more than 8°C
(46°F)
4. For reference; the gas side pressure of optimum
condition is as below.(Cooling)
Discharge
temperature
Discharge air Intake temperature
R-22 35°C (95°F) 4~5kg/cm
2
G(56.8~71.0 P.S.I.G.)
Outside ambient
TEMP.
Refrigerant
The pressure of the gas side
service valve.
Other manuals for DELUXE HIGH WALL MINI SPLIT
3
This manual suits for next models
2
Table of contents
Other LG Air Conditioner manuals

LG
LG B62UWYN881 User manual

LG
LG Fast F05K1 User manual

LG
LG LSC091PMA User manual

LG
LG LW1013CR Assembly instructions

LG
LG ARNU 4 Series User manual

LG
LG Multi Type Air Conditioner User manual
![LG LZ-H080GBA2 [ARVU053ZEA2] User manual LG LZ-H080GBA2 [ARVU053ZEA2] User manual](/data/manuals/27/2/272ct/sources/lg-lz-h080gba2-arvu053zea2--manual.jpg)
LG
LG LZ-H080GBA2 [ARVU053ZEA2] User manual

LG
LG HBLG5200E User manual

LG
LG LAN125HV User guide

LG
LG MA09AH-NF1 User manual
Popular Air Conditioner manuals by other brands

Daikin
Daikin FFQ12LVJU Operation manual

Daikin
Daikin RX15RMVJU installation instructions

CLIMAVENETA
CLIMAVENETA i-ACCURATE i-AX Installation manual - user and maintenance

Fuji Electric
Fuji Electric RD-60FA Service manual

Gree
Gree GMV-ND07PLS/A-T(U) Service manual

Frigidaire
Frigidaire FAA074S7A12 Use & care manual