LG G4F-TC2A User manual

User’s Manual
LG Programmable Logic Controller
G3F – RD3A
G4F – TC2A
GLOFA
MASTER-K
LG Industrial Systems

Be sure to read carefully the safety precautions given in data sheet and user’s manual before operating the module
and follow them.
The precautions explained here only apply to the G3F-RD3Aand G4F-RD2A.
For safety precautions on the PLC system, see the GLOFA GM3/4 User’s Manual or the MASTER-k 1000S/300S
User’s Manual.
A precaution is given with a hazard alert triangular symbol to call your attention, and precautions are represented
as follows according to the degree of hazard.
However, a precaution followed with can also result in serious conditions.
Both of two symbols indicate that an important content is mentioned, therefore, be sure to observe it.
Keep this manual handy for your quick reference in necessary.
PRECAUTIONS
WARNING
!
If not provided with proper prevention, it can cause death or fatal
injury or considerable loss of property.
CAUTION
!
If not properly observed, it can cause a hazard situation to result
in severe or slight injury or a loss of property.
CAUTION
!
CAUTION
!
Design Precautions
▶
Do not run I/O signal lines and
compensation wires near to high
voltage line or power line.
Separate them as 100 mm or
more as possible. Otherwise,
noise can cause module mal-
function.
CAUTION
!
Installation Precautions
▶Operate the PLC in the environ-
ment conditions given in the
general specifications.
▶If operated in other environment
not specified in the general spec-
ifications, it can cause an elec-
tric shock, a fire, malfunction or
damage or degradation of the
module
▶Make sure the module fixing pro-
jections is inserted into the mod-
ule fixing hole and fixed.
▶Improper installation of the mod-
ule can cause malfunction, dis-
order or falling.

CAUTION
!
Wiring Precautions
▶
When grounding a FG terminal, be sure to provide class 3 grounding which is dedicated to
the PLC. If not grounded, It can cause malfunction.
▶Before the PLC wiring, be sure to check the rated voltage and terminal arrangement for
the module and observe them correctly.
If a different power, not of the rated voltage, is applied or wrong wiring is provided, it can
cause a fire or disorder of the module.
▶Drive the terminal screws firmly to the defined torque.
If loosely driven, it can cause short circuit, a fire or malfunction.
▶Be careful that any foreign matter like wire scraps should not enter into the module.
It can cause a fire, disorder or malfunction.
WARNING
!
Test Run and Maintenance
Precautions
▶
Do not contact the terminals
while the power is applied.
It can cause malfunction.
▶When cleaning or driving a termi-
nal screw, perform them after the
power has been turned off
▶Do not perform works while the
power is applied, which can
cause disorder or malfunction.
CAUTION
!
▶
Do not separate the module from
the printed circuit board(PCB), or
do not remodel the module.
They can cause disorder, mal-
function, damage of the module
or a fire.
When mounting or dismounting
the module, perform them after
the power has been turned off.
▶Do not perform works while the
power is applied, which can
cause disorder or malfunction.
CAUTION
!
Waste Disposal Precautions
▶
When disposing the module, do it as an industrialwaste.

◎CONTENTS ◎
Chapter 1. INTRODUCTION
1.1 Features …………………………………………………………………………………… 1 – 1
1.2 Glossary …………………………………………………………………………………… 1 – 2
1.2.1 A – Analog Value ……………………………………………………………………… 1 – 2
1.2.2 D – Digital Value ……………………………………………………………………… 1 – 2
1.2.3 PT …………………………………………………………………………………… 1 – 2
1.2.4 Burn-out function ……………………………………………………………………… 1 – 2
Chapter 2. SPECIFICATIONS
2.1 General Specifications ……………………………………………………………………… 2 – 1
2.2 Performance Specifications ………………………………………………………………… 2 – 2
2.3 Names of Parts and Functions ……………………………………………………………… 2 – 3
2.3.1 G3F-RD3A ………………………………………………………………………………… 2 – 3
2.3.2 G4F-RD2A ………………………………………………………………………………… 2 – 4
2.4 RTD Input Module Characteristics ……………………………………………………… 2 – 5
2.4.1 Temperature Conversion Characteristics ………………………………………………… 2 – 5
2.4.2 Conversion Speed ……………………………………………………………………… 2 – 5
2.4.3 Accuracy ………………………………………………………………………………… 2 – 5
2.4.4 Burn-out Function ……………………………………………………………………… 2 – 6
2.5 Connection between a Pt and RTD Input Module ……………………………………… 2 – 7
Chapter 3. INSTALLATION AND WIRING
3.1 Installation ………………………………………………………………………………… 3 – 1
3.1.1 Installation Ambience …………………………………………………………………… 3 – 1
3.1.2 Handling Precautions ……………………………………………………………………… 3 – 1
3.2 Wiring Precautions ………………………………………………………………………… 3 – 2

Chapter 4. FUNCTION BLOCKS
4.1 Inserting Function Blocks for RTD Input Module in GMWIN ………………………………… 4 – 1
4.2 Local Function Blocks ……………………………………………………………………… 4 – 2
4.2.1 Module Initialization (G3F-RD3A:RTD3INI, G4F-RD2A:RTD2INI) …………………………… 4 – 2
4.2.2 Reading the Detected Temperature Value of the Module(ArrayType)
(G3F-RD3A:RTD3ARD, G4F- RD2A:RTD2ARD) ………………………………………… 4 – 3
4.2.3 Reading the Detected Temperature Value of the Module (Single Type)
(G3F-RD3A : RTD3RD, G4F-RD2A : RTD2RD) …………………………………………… 4– 4
4.3 Remote Function Blocks ……………………………………………………………………… 4 – 5
4.3.1 Module Initialization (G3F-RD3A:RTDR3INI, G4F-RD2A:RTDR2INI) ……………………… 4 – 5
4.3.2 Reading the Detected Temperature Value of the Module …………………………………… 4 – 6
(G3F-RD3A:RTDR3ARD, G4F-RD2A:RTDR2ARD)
4.4 Errors on Function Block …………………………………………………………………… 4 – 7
4.4.1 Errors Indicated by the Output Variable STAT …………………………………………… 4 – 7
4.4.2 Error Indicated by the Output VariableALM_CODE in theArray Type
Detected Temperature Value Reading Function Block …………………………………… 4 – 7
Chapter 5. PROGRAMMING
5.1 A Program for Output of the Detected Temperature Value as a BCD Value ………………… 5 – 1
5.2 A Program for Conversing the Detected Temperature Value(°C) into Fahrenheit(°F)
and Output as a BCD Value ………………………………………………………………… 5 – 6
5.3 A Program when Loading the RTD Input Module onto the Remote I/O Station ……………… 5 – 9
Chapter 6. BUFFER MEMORY CONFIGURATIONAND FUNCTIONS
6.1 Buffer Memory Configuration ……………………………………………………………… 6 – 1
6.1.1 G3F-RD3A Buffer Memory ……………………………………………………………… 6 – 1
6.1.2 G4F-RD2A Buffer Memory ……………………………………………………………… 6 – 2
6.2 Functions of Buffer Memory ……………………………………………………………… 6 – 3
6.2.1 Specifying Channel Enable/Disable ……………………………………………………… 6 – 3
(G3F-RD3A:Address 0, G4F-RD2A:Address 0)
6.2.2 Specifying the Type of the RTD ………………………………………………………… 6 – 3
(G3F-RD3A:Addresses 1 to 8, G4F-RD2A:Addresses 1 to 4)
6.2.3 Detected Temperature Value …………………………………………………………… 6 – 4
(G3F-RD3A:Addresses 9, 12, 15, 18, 21, 24, 27 and 30, G4F-RD2A:Addresses 5, 8, 11 and 14)

6.2.4 Digital Conversion Value ……………………………………………………………… 6 – 4
(G3F-RD3A:Addresses 10, 13, 16, 19, 22, 25, 28 and 31, G4F-RD2A:Addresses 6, 9, 12 and 15)
6.2.5 Error Code …………………………………………………………………………… 6 – 4
(G3F-RD3A:Addresses 11, 14, 17, 20, 23, 26, 29 and 32, G4F-RD2A:Addresses 7, 10, 13 and 16)
6.2.6 Specifying SET Data …………………………………………………………………… 6 – 5
(G3F-RD3A:Address 33, G4F-RD2A:Address 17)
6.2.7 Information on Run Channel …………………………………………………………… 6 – 5
(G3F-RD3A:Address 34, G4F-RD2A: Address 18)
6.2.8 Information on RTD Specification Error ………………………………………………… 6– 6
(G3F-RD3A:Address 35, G4F-RD2A:Address 19)
Chapter 7. DEDICATED INSTRUCTIONS FOR SPECIAL MODULES
(Read from/Write to Buffer Memory)
7.1 Local ………………………………………………………………………………………7 – 1
7.1.1 Read from Buffer Memory…GET, GETP…………………………………………………7 – 1
7.1.2 Write to Buffer Memory…PUT, PUTP……………………………………………………7 – 2
7.2 Remote ……………………………………………………………………………………7 – 3
7.2.1 Read from Buffer Memory…RGET …………………………………………………… 7 – 3
7.2.2 Write to Buffer Memory…RPUT …………………………………………………… 7 – 4
Chapter 8. PROGRAMMING
8.1 Basic Programming ………………………………………………………………………8 – 1
8.1.1 G3F-RD3A …………………………………………………………………………… 8 – 1
8.1.2 G4F-RD2A …………………………………………………………………………… 8 – 2
8.2 Application Programming ………………………………………………………………… 8 – 3
8.2.1 A Program for Output of the Detected Temperature Value as a BCD Value ……………… 8 – 3
8.2.2 A Program for Conversing the DetectedTemperature Value(°C) into Fahrenheit(°F)
and Output as a BCD Value ………………………………………………………… 8 – 4
8.2.3 A Program when Loading the RTD Input Module onto the Remote I/O Station ……………8 – 6
Chapter 9. TROUBLESHOOTING
9.1 Errors Indicated by RUN LED Flickering …………………………………………………… 9 – 1
9.2 Troubleshooting Procedure ………………………………………………………………… 9 – 2
9.2.1 RUN LED Flickering …………………………………………………………………… 9 – 2
9.2.2 RUN LED Off ………………………………………………………………………… 9 – 2
9.2.3 Detected Temperature Value Unreadable from the CPU Module …………………………… 9 – 3

9.2.4 Input Value of the RTD Is Not Consistent with
The Detected Temperature Value ……………………………………………………… 9 – 4
9.2.5 RTD Input Module Hardware Defect …………………………………………………… 9 – 4
Chapter 10.DIMENSIONS.
10.1 G3F-RD3A Dimensions ……………………………………………………………………10 – 1
10.2 G4F-RD2A Dimensions ……………………………………………………………………10 – 2
Appendix 1. Standard Resistance Value of Pt/RTD ……………………………………… A – 1

Chapter 1. INTRODUCTION
1 - 1
Chapter 1. INTRODUCTION
These two units are called G3F-RD3A and G4F-RD2A. The G3F-RD3Ais an Pt input module used with the
CPU of GLOFA GM1/2/3 series and MASTER-K1000S series, and the G4F-RD2A is used with the CPU of
GM4 series and K 300S series Hereafter, the two units are called the RTD input module
The RTD input module is a module that converts the temperature data(°C) input by the Pt (Pt100 or JPt100)
into a signed 16 bit digital binary data and outputs it.
1.1 Features
1) With direct connection of the RTD input module, the temperature data(°C) can be converted into a digital
value to be processed in the PLC.
2) The temperature data(°C) input can be processed to one digit after the point as a digital value.
3) One module can be connected to G3F-RD3A8-point or G4F-RD2A4-point Pt100 or JPt100.
4) The RTD input module has Pt100, Jpt100 or cable burn-out function at their every channel.
5) The RTD input module detects the out-of-range temperature that is input by Pt100 or JPt100.

Chapter 1. INTRODUCTION
1 - 2
1.2 Glossary
1.2.1 A -Analog Value
The continuous changeable value such as voltage, current, temperature, velocity, pressure and flow is
called analog value. For example, temperature changes continuously with time as shown in Fig. 1.1. The
PLC can process that continuous changeable temperature by use of the RTD input module.
1.2.2 D - Digital Value
In Fig.1.2, the number of man can be counted as 0, 1, 2, 3. The non-continuous changeable value as such
is called a digital value. On and Off signals can be denoted as a digital value 0 and 1, respectively.
Analog value cannot be directly input to the CPU
module for digital processing. Therefore, analog value
should be converted into a digital value to be input to
the CPU module. In addition, for external output of
analog value, digital value of the CPU module should
be converted into analog value.
1.2.3 Pt
This is a sensor that detects temperature as the type of resistance.
The Pt 100 outputs the resistance value of 100.00 Ωfor the temperature of 0 °C
1.2.4 Burn-out Function
If a part of the connected RTD or cable is disconnected, the out-of-range voltage is input by the internal
burn-out circuit and the connection or disconnection is detected.
A/D
Conversion
CPU
(Digital
processing)
D/A
Conversion
Analog
-200~-600℃
Analog
0~±10V or
4~20mA
[Fig 1.3] Processing in the PLC
0
Temperature
time
time
Number of man
[Fig 1.1]Analog Value
[Fig 1.2] Digital Value
0

Chapter 2. SPECIFICATIONS
2 - 1
REMARK
Chapter 2. SPECIFICATIONS
2.1 General Specifications
Table 2.1 shows general specifications of the GLOFAGM series and MASTER-K series
No Item Specifications
Reference
specification
1
Operating
ambient
temperature
0 ~ 55 °C
2
Storage
ambient
temperature
-25 ~ +75 °C
3
Operating
humidity
5 ~ 95%RH, non-condensing.
4
Storage
humidity
5 ~ 95%RH, non-condensing.
5
Vibration
Occasional vibration
IEC 61131-2
Frequency
Acceleration
Amplitude
Sweep
Count
10≤f<57 Hz
-
0.075 mm
10 times in
each
direction
for X,Y,Z
57≤f≤150 Hz
9.8 m/s 2{1 G}
-
Continuous vibration
Frequency
Acceleration
Amplitude
10≤f <57 Hz
-
0.035 mm
57≤f≤150 Hz
4.9 m/s2{0.5G}
-
6 Shocks
Maximum shock acceleration: 147 m/s2{15G}
Duration time : 11ms
Pulse wave: half sine pulse (3 times in each of X, Y and Z directions)
IEC 61131-2
7 Noise
Immunity
Square wave impulse
noise
±1,500 V
LGIS
Standard
Electrostatic discharge Voltage : 4 kV (contact discharge)
IEC 61131-2,
IEC 1000-4-2
Radiated electromagnetic
field
27 ~ 500 MHz, 10 V/m
IEC 61131-2,
IEC 1000-4-3
Fast transient/burst noise Severity
Level
All
Power
modules
Digital
I/Os (Ue
> 24 V)
Digital I/Os
(Ue < 24 V)
Analog I/Os
interface
communication
I/Os
IEC 61131-2,
IEC 1000-4-4
Voltage
2 kV
1 kV
0.25 kV
8
Operating
Atmosphere
Free from corrosive gases and excessive dust.
9
Operation
Altitude
Up to 2,000m
10
Pollution
degree
2
11
Cooling
method
Self-cooling
[Table 2.1] General Specifications
1) IEC(International Electromechanical Commission) : The international civilian organization which produces standards
for electrical and electronic industry.
2) Pollution degree : It indicates a standard of operating ambient pollution level The pollution degree 2 means the condition
in which normally, only con-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by
condensation shall be expected.

Chapter 2. SPECIFICATIONS
2 - 2
2.2 Performance Specifications
Table 2.2 shows performance specifications of the RTD input module.
Item
Specifications
G3F-RD3A
G4F-RD2A
Connectable RTD
Pt 100 (JIS C1640-1989, DIN 43760-1980)
JPt100 (KS C1603-1991, JIS C1604-1981)
Temperature input range
Pt100
JPt100
: -200.0°C to 600°C (18.48 to 313.59Ω)
: -200.0°C to 600°C (17.14 to 317.28Ω)
Digital output
Digital conversion value : 0 to 16,000
Detected temperature value : -2000 to 6000 (one digit after
point x10)
Buffer memory
Each of three wires at every channel has detection
function.
Accuracy
±0.5 %(full scale)
Maximum conversion speed
50ms per channel
Number of temperature input device points
8 channels per module
4 channels per module
Insulation method
Photo-coupler insulation between the input terminal and
the PLC power supply (non-insulation between channels)
Connection terminal block
38-point terminal block
20-point terminal block
Internal current consumption
0.5A
0.45A
Weight
630 g
350 g
[Table. 2.2 Performance Specifications]

Chapter 2. SPECIFICATIONS
2 - 3
2.3 Names of Parts and Functions
The following gives names of parts.
2.3.1 G3F-RD3A
The following gives the names and functions of each part of the G3F-RD3A.
No. Descriptions
�
RUN LED
It displays the operating status of G3F-RD3Amodule
On : Normal Operation
Flickering : Error occurred (For more information,
see Chapter 4.1
Off : DC 5V disconnection or the G3F-RD3A
module error

Chapter 2. SPECIFICATIONS
2 - 4
2.3.2 G4F-RD2A
The following gives the names and functions of each part of the G4F-RD2A.
RUN LED
G4F-RD2Amodule operating status Indication
-On : Normal operation
-Flickering : Error occurred (For more information, see
Section Common 4.1)
-Off : 5 VDC disconnection or G4F-RD2Amodule error

Chapter 2. SPECIFICATIONS
2 - 5
2.4 RTD Input Module Characteristics
2.4.1 Temperature Conversion Characteristics
The RTD input module, as shown in the Fig. 2.1, linearlizesthe non-linear characteristic resistance
input of the RTD.
[Fig. 2.1] Temperature conversion characteristics( Pt100)
2.4.2 Conversion speed
The conversion speed of the RTD input module is 50 ms per channel and its processing is
processed sequentially, that is, one channel is processed and then another channel is
processed.
Processing time = 50 ms �the number of the used channels
Example) When three channels are used
Processing time = 50 ms �3 = 150 ms
2.4.3 Accuracy
The accuracy of RTD input module is within ±0.5 % of all of the measurable temperature range.
Example) When the RTD Pt100 is used, the conversion values of –100°C and 400°C are as
below.
-Measurable temperature full range : 800°C (-200.0°C to 600.0°C)
-Accuracy : 800 �(±0.5%) = 800�(±0.005) = ±4°C
-Temperature conversion range : - 104 °C to – 96 °C when –100°C
396°C to 404°C when 400°C
Resistance
temperature
detection value

Chapter 2. SPECIFICATIONS
2 - 6
2.4.4 Burn-out Detection Function
The RTD input module has the function of burn-out detection on the Pt100, JPt100 or cable.
1) As shown in the Fig. 2.2, if disconnection occurs in the RTD or cable then a voltage outside the
measurable range voltage is inputted by the internal burn-out detection circuit and burn-out detection
error code is generated.
2) The RTD input module can detect disconnection for each channel. But, burn-out detection is possible
only in the channels enabled.
3) If disconnection is detected in two or more wires, first, disconnection error code is generated by ‘b’and
then disconnection error code is generated by ‘A’or ‘b’ sequentially. If disconnection is detected
simultaneously in ‘A’and ‘B’, only disconnection error code is generated by ‘b’.
Connection
Method Connection Example
Burn-out Detection
Function Remark
2-wire
type
- When specified as the
enabled channel
: The burn-out detection
function is enabled.
- When not specified as
the enabled channel
: The burn-out detection
function is disabled
- In 4-wire type, only all
wires marked '2'
connected to the
terminal block A are
all detected as
disconnection then
the A disconnection
error can be
detected.
*1 : Pt
*2: Shield wire
3-wire
type
4-wire
type
No wiring
[Fig. 2.2] Burn-out Detection Area
burn-out detection area
burn-out detection area
burn-out detection area

Chapter 2. SPECIFICATIONS
2 - 7
2.5 Connection between a Pt and RTD inputmodule
-Number of method of connection between Pt and RTD input module are three, that is, 2-wired type, 3-
wired type and 4-wired type.
-The resistance of the wires used to connect Pt to RTD input module should be 10 Ωor less per wire.
The same wire (in thickness, length, and kind, etc.) should be used for each channel.
REMARK
�
The difference between the resistance values of the wires used should be 1 Ωor less, or the accuracy
shown in the Table 2.2 could not be satisfied.
Connection
Method Connection Example Wire Conditions
2-wired type
�wire resistance≤10Ω
�wire resistance≤10Ω
�wire resistance≤10Ω
The difference between the
resistance values of the wires �and
�: 1Ωor less
The difference between the
resistance values of the wires �and
�: 1Ωor less
The difference between the
resistance values of the wires �and
�: 1Ωor less
3-wired type
4-wired type
[Fig. 2.3] Method of Connection between Pt and RTD Input Module
*1: RTD (Pt100 or JPt1000)
*:2: Shielded wire
- The shields of the RTD and shields of wire should be connected to the FG of the RTD input
module.

Chapter 3. INSTALLATION AND WIRING
3 - 1
Chapter 3. INSTALLATIONAND WIRING
3.1 Installation
3.1.1 Installation Ambience
This module has high reliability regardless of its installation environment, but be sure to check the
following for system reliability and stability.
1)Ambience requirements
Avoid installing this unit in locations which are subjected or exposed to :
-Water leakage and dust.
-Continuous shocks or vibrations.
-Direct sunlight.
-Dew condensation due to rapid temperature change.
-Higher or lower temperatures outside the range of 0 to 55 °C
2) Precautions during installing and wiring.
-During drilling or wiring, do not allow any wire scraps to enter into the PLC.
-Install it on locations that are convenient for operation.
-Make sure that it is not located on the same panel that high voltage equipment located.
-Make sure that the distance from the walls of duct and external equipment be 50 mm or more.
-Be sure to be grounded to locations that have good ambient noise immunity.
3.1.2 Handling Precautions
From unpacking to installing the RTD input module, be sure to check the following:
1) Do not drop it off, and make sure that strong shock should not be applied.
2) Do not unload the PCB from its case. It can cause faults.
3) During wiring, be sure to check any foreign matter like wire scraps should not enter into the upper side
of the PLC. If any foreign matter has entered into it, alwayseliminate it.
4) Do not load or unload the module while the power supply is being connected.

Chapter 3. INSTALLATION AND WIRING
3 - 2
3.2 Wring Precautions
1) When connecting Pt with the RTD input module, refer to the Chapter 2.5 for wiring.
2) Be sure to separate the external input signal of the RTD input module from an alternating current so
that surge or induction noise generated from the alternating current could not effect.
3) When wiring, locating this unit too near from high temperature generating devicesor materials or
contacting it with the material like oil can cause short-circuit and occur damage or disorder.
4) When wiring to the terminal block, wiring with high-pressure wire or power supply wire can occur flow
inhibition and cause disorder or malfunction.

Chapter 4. FUNCTION BLOCKS
4 - 1
Chapter 4. FUNCTION BLOCKS
The followings explain the function blocks for the RTD input module used in GMWIN
The types of function block are given here.
No.
G3F-RD3A
G4F-RD2A
Function
Local
Remote
Local
Remote
1
RTD3INI
RTDR3INI
RTD2INI
RTDR2INI
Module Initialization
2 RTD3ARD RTDR3RD RTD2ARD RTDR2RD
Reading the detected temperature value
(Array type)
3 RTD3RD - RTD2RD -
Reading the detected temperature value
(Single type)
4.1 Inserting Function Blocksfor the RTD Input Module in GMWIN.
Function blocks can be registered with the following procedure while the GMWIN is running.
Registering function blocks is only possible when a project is open.
G4F-RD2A
1. Special. 4fb
•RTD2INI
•RTD2ARD
•RTD2RD
2. Remote4.4fb
•RTDR2INI
•RTDR2RD
3. Remote3.4fb
•RTDR3INI
•RTDR3RD
Project(P)
Library Insert(I)
G3F-RD3A
1. Special. 3fb
•RTD3INI
•RTD3ARD
•RTD3RD
2. Remote3.3fb
•RTDR3INI
•RTDR3RD
3. Remote4.3fb
•RTDR3INI
•RTDR2RD
Inserting local
function block
InsertingGM3 remote
function block
InsertingGM4 remote
function block
Inserting local
function block
InsertingGM4 remote
function block
InsertingGM3 remote
function block
Selection

Chapter 4. FUNCTION BLOCKS
4 - 2
4.2 Local Function Blocks
4.2.1 Module Initialization (G3F-RD3A: RTD3INI, G4F-RD2A:RTD2INI)
Module initialization function block specifies RTD input module base location, slot location, run channel
enable/disable and the type of RTD for use in program.
Function
Block
I/O Variable
Data
Type
Descriptions
I
REQ BOOL
Function block execution request area
- Used to request an execution of the initialization function block
- If the conditions connected with this area
are established while program is
running and input condition changes from low to high, the initialization function
block is executed
BASE USINT
Base location No.
- Used towrite the number of the base where the RTD input module is loaded.
- Setting range: GM1 series(0~31), GM2 series(0~7), GM3/4 series(0-3)
SLOT USINT
Slot location No.
- Used towrite the number of the slot where the RTD input module is loaded.
- Setting range: 0~7
CH BOOL
[Array]
*Note1
Run channel enable/disable specification
- Used toenable or disable a channelfor run.
- Specify “1” for enabling, and “0” for disabling
TYPE BOOL
[Array]
*Note 1
Specifying the type ofRTD for use
- Used to specifythe type of “0” for Pt100 and “1” for JPt100 for each channel
"0" :Pt100
"1" : JPt100
O
DONE BOOL
Function blockexecution complete status
- “1”
is output when the initialization function block is finished with no error and
“1” remains until next execution. If an error occur, ‘0’
is displayed and the
operation enters into the stop state.
STAT USINT
Error statusindication area
-
Used to output the number of an error when it occurs during initialization function
blockexecution.
- For description oferrors,see GMSection 7.4
ACT BOOL
[Array]
*Note 1
Run channel status indication area
- After the initialization function block is finished with no error, “1” is output if the
channel is in normal state. But “0” is output for the disabled channels.
REMARK
Note 1: The numbers ofArray are 8 in G3F-RD3A, 4 in G4F-RD2A.
This manual suits for next models
1
Table of contents
Other LG Controllers manuals
Popular Controllers manuals by other brands

SMC Networks
SMC Networks LECSN-T Series Operation manual

Analog way
Analog way Axion2 Programmer's guide

ESYLUX
ESYLUX ELC quick guide

ATI Technologies
ATI Technologies TRACON FPT 130 Installation and operation manual

Mi-Light
Mi-Light MiBOXER FUT041 manual

Hitachi
Hitachi ATW-YCC-03 Installation and operation manual

SMC Networks
SMC Networks CRB10 Operation manual

BAFANG
BAFANG CR C101.C Dealer's manual

Tilia
Tilia Termoventiler ThermOmatic ERA 10 Installation and user instructions

ESK Schultze
ESK Schultze ERM5 Installation and operating instructions

Hunter
Hunter Hydrawise HC-1200M owner's manual

Zander Aachen
Zander Aachen ZX Series quick start guide