manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Lindab
  6. •
  7. Fire And Smoke Damper
  8. •
  9. Lindab WH25 User manual

Lindab WH25 User manual

English
Technical Manual
Installation type with re resistance class
Cert. N° 1812-CPR-1023
CIRCULAR SERIES WH25 - 500 Pa
PATENTED FIRE DAMPER
WH25
LINDAB SAFE
This is a 50 page manual.
TABLE OF CONTENTS
WH25
LINDAB SAFE
3/50
Overview � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�4
Description � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�4
General characteristics � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�4
European Standards applied � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�4
Certications and approvals � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�4
Components � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�4
Available dimensions � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�5
Performances � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�5
Fire resistance classication according to EN 13501-3-2009 � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�5
Mechanism type � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�8
Technical data � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�11
Dimension � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�11
Weights � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�11
Installation � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�12
Intended use � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�12
Not allowed uses � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�12
Positioning brackets before xing � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�12
Blade rotation axis positioning � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�12
Installation of exible connectors in order to balance out the ventilation ducts expansion � � � � � � � � � � � � � � � p�12
Transfer Application (application not connected to air ducts on one or both sides) � � � � � � � � � � � � � � � � � � p�13
Minimum distances � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�15
Construction supports characteristics � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�17
Installations within vertical rigid wall � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�19
Installations within vertical light wall (plasterboard) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�21
Installations within vertical light wall (gypsum blocks wall) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�22
Installations within oor � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�23
Installations within vertical wall with Fire Batt (Weichschott) sealing � � � � � � � � � � � � � � � � � � � � � � � � � p�24
Installation within oor with Fire Batt (Weichschott) sealing � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�25
Installation remote from the vertical rigid wall and the vertical light wall (gypsum blocks wall) � � � � � � � � � � � � p�26
Installation remote from the vertical light wall (plasterboard) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�28
Installations remote from the vertical wall with Fire Batt (Weichschott) sealing � � � � � � � � � � � � � � � � � � � � p�30
Installations remote from the oor � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�32
Installation within vertical light wall (Shaft wall) � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�34
Electrical connections � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�35
Electrical wiring � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�35
Electrical specications � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�36
Maintenance and inspections � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�38
Periodic inspection and cleaning � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�38
Repair � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�38
Disposal � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�38
Selection � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�39
Air ow rates in relation to the diameter � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�39
Air ow rates as a function of the pressure drop � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�39
Air ow rates as a function of generated sound levels � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�39
Pressure drop and sound level graph � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�40
Sound spectrum table � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�40
Accessories and spare parts � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�41
How to order � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�45
Motorized re dampers � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�45
Fire damper with manual control � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�45
Electric motor driven actuators � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�45
Specication Text � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�46
Series WH25 compact circular re dampers � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�46
Revision Index � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � p�48
WH25
3/50
LINDAB SAFE
OVERVIEW
WH25
LINDAB SAFE
4/50
OVERVIEW
Description
Fire dampers WH25 are devices for use in heating, ventila-
tion and air-conditioning (HVAC) systems at re bounda-
ries to maintain compartmentation and protect means of
escape in case of re. They satisfy integrity, insulation and
smoke leakage criteria for the declared time of re resist-
ance.
Tested and classed in accordance with EN 1366-2 and EN
13501-3 regulations with 500 Pa depression.
Studied and optimized for small diameter ducts and re-
duced installation space focusing on aeraulic and acous-
tical performance.
Equipped with various dierent mechanisms completely
outside the wall, easily interchangeble even after installa-
tion.
General characteristics
• Casing made from galvanized carbon steel.
• Thermal labyrinth obtained from the casing.
• Air duct connection gasket.
Lindab Safe: The system is based on a double, factory-in-
stalled seal made of EPDM rubber. This seal makes the
system quick and easy to mount. Refer to Lindab web
site for further information.
Please note that casing painting (see table Accessories
and spare parts  p. 41) is not available for Lindab Safe
connectors.
• Intumescent sealing gasket.
• Opening/closing mechanism with IP42 protection box
(IP54 for motorized version).
• 25 mm thick closing blade made with refractory material.
• Lip seal on blade border for cold smoke seal.
• Internal intumescent gasket for hot smoke seal.
European Standards applied
CE certication EN 15650
Test EN 1366-2
Classication EN 13501-3
Thermal fuse reliability ISO 10294-4
Air tightness EN 1751
Resistance to corrosive environments EN 60068-2-52
Certications and approvals
CE Certicate of Constancy of Performance n° 1812-CPR-1023 Efectis
German approval n° Z-56.4212-987 DIBt
NF certication n° 09/04.02 AFNOR
Swiss approval n° 25971 VKF-AEAI
Swedish approval n° SC0195-16 SP
Components
1. Casing made from galvanized carbon steel.
2. Thermal labyrinth
3. Intumescent graphite gasket on the outside the casing
4. Damper blade made from refractoring material
5. Blade pivot
6. Cold smoke air seal gasket
7. Intumescent graphite gasket on inside of casing for the hot seal
of the blade once closed
8. Temperature controlled closing device (thermal fuse)
9. Blade actioning device
10. Manual closing device (Test button)
11. Manual reset lever
12. Closed blade stopper
13. Protection box
14. Inspection opening Ø 18mm for endoscope (available only for
non-motorized version)
WH25
LINDAB SAFE
4/50
OVERVIEW
WH25
LINDAB SAFE
5/50
Available dimensions
Ø mm 100 125 140 150 160 180 200 224 250 280 300 315
Performances
Performance Reference standard Class
Thermal fuse testing ISO 10294-4 Compliant
Open and Close cycle reliability EN 15650 Compliant
Resistance to corrosion in humid and saline environments EN 60068-2-52 Degree of severity 2
Casing tightness EN 1751 Class C
Blade seal EN 1751 Class 3 minimum
Fire resistance classication according to EN 13501-3-2009
EI 120 S
(500 Pa) EI 90 S
(500 Pa) EI 60 S
(500 Pa) EI 30 S
(500 Pa)
Rigid wall
EI 120 S Installation within vertical rigid wall p.19
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Mortar or plaster putty sealing
ve (i↔o)
WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 90 S Installation within vertical rigid wall p.19
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Plasterboard and rock wool 100 kg/m³ sealing
ve (i↔o)
D - Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Flexible wall
EI 60 S Installation within vertical light wall (plasterboard) p.21
Wall minimum thickness 100 mm
Wall rock wool density up tp 80 kg/m³ (optional)
Plasterboard and rock wool 80 kg/m³ density sealing
ve (i↔o)
D - - Ø
min 100
max 315
Ø
min 100
max 315
EI 90 S Installation within vertical light wall (plasterboard) p.21
Wall minimum thickness 100 mm
Wall rock wool density up to 80 kg/m³ (optional)
Plasterboard and rock wool 100 kg/m³ density sealing
ve (i↔o)
D - Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation within vertical light wall (plasterboard) p.21
Wall minimum thickness 100 mm
Wall rock wool density up to 80 kg/m³ (optional)
Mortar or plaster putty sealing
ve (i↔o)
WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 90 S Installation within vertical light wall (gypsum blocks wall) p.22
Wall minimum thickness 70 mm
Wall minimum density 995 kg/m³
Plaster putty sealing
ve (i↔o)
W - Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation within vertical light wall (gypsum blocks wall) p.22
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Plaster putty sealing
ve (i↔o)
WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
WH25
5/50
LINDAB SAFE
OVERVIEW
WH25
LINDAB SAFE
6/50
EI 120 S
(500 Pa) EI 90 S
(500 Pa) EI 60 S
(500 Pa) EI 30 S
(500 Pa)
Floor
EI 90 S Installation within oor p.23
Floor minimum thickness 100 mm
Floor minimum density 650 kg/m³
Mortar sealing
ho (i↔o)
W - Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation within oor p.23
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Mortar sealing
ho (i↔o)
WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø is the minimum and maximum nominal diameter of re dampers in mm
ve Vertical installation
ho Horizontal installation
(i↔o) Origin of re irrelevant
Pa Pascal of depression
E Integrity
I Thermal insulation
S Smoke seal
W Wet method sealing
D Dry method sealing
Cert. N° 1812-CPR-1023
Fire Batt (Weichschott) sealings
EI 120 S
(300 Pa) EI 90 S
(300 Pa) EI 60 S
(300 Pa) EI 30 S
(300 Pa)
Rigid wall
EI 120 S Installation within vertical rigid wall with Fire Batt (Weichschott) sealing p.24
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Minimum distance allowed between 2 dampers 200 mm 50 mm 50 mm 50 mm
Flexible wall
EI 120 S Installation within vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing p.24
Wall minimum thickness 100 mm
Wall rock wool density up to 80 kg/m³ (optional)
Rock wool density 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Minimum distance allowed between 2 dampers 200 mm 50 mm 50 mm 50 mm
EI 120 S Installation within vertical light wall (gypsum blocks wall) with Fire Batt (Weichschott) sealing p.24
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Minimum distance allowed between 2 dampers 200 mm 50 mm 50 mm 50 mm
Floor
EI 90 S Installation within oor and Fire Batt (Weichschott) sealing p.25
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ho (i↔o)
W - Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Minimum distance allowed between 2 dampers - 200 mm 200 mm 200 mm
Installation remote from construction support
EI 120 S
(300 Pa) EI 90 S
(300 Pa) EI 60 S
(500 Pa) EI 30 S
(500 Pa)
Rigid wall
EI 120 S Installation remote from the vertical rigid wall p.26
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Mortar or plaster putty sealing
ve (i↔o)
WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation remote from the vertical rigid wall with Fire Batt (Weichschott) sealing p.30
Wall minimum thickness 100 mm
Wall minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
DØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
WH25
LINDAB SAFE
6/50
OVERVIEW
WH25
LINDAB SAFE
7/50
EI 120 S
(300 Pa) EI 90 S
(300 Pa) EI 60 S
(500 Pa) EI 30 S
(500 Pa)
Flexible wall
EI 120 S Installation remote from the vertical light wall (plasterboard) p.28
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Plasterboard and rock wool 100 kg/m³ or mortar or plaster putty sealing
ve (i↔o)
D/W Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation remote from the vertical light wall (plasterboard) with Fire Batt (Weichschott) sealing p.30
Wall minimum thickness 100 mm
Wall rock wool density up to 100 kg/m³ (optional)
Rock wool density 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
DØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation remote from the vertical light wall (gypsum blocks wall) p.26
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Mortar or plaster putty sealing
ve (i↔o)
WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 120 S Installation remote from the vertical light wall (gypsum blocks wall) with Fire Batt (Weichschott) sealing p.30
Wall minimum thickness 100 mm
Wall minimum density 995 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ve (i↔o)
DØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Floor
EI 120 S Installation remote from the oor p.32
Floor minimum thickness 150 mm
Floor minimum density 650 kg/m³
Mortar or plaster putty sealing
ho (i↔o)
WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
EI 90 S Installation remote from the oor p.32
Floor minimum thickness 100 mm
Floor minimum density 650 kg/m³
Mortar or plaster putty sealing
ho (i↔o)
W - Ø
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
Installations within vertical light wall (Shaft wall)
EI 90 S
(300 Pa) EI 60 S
(300 Pa) EI 30 S
(300 Pa)
Flexible
wall
EI 90 S Installation within vertical light wall (Shaft wall) p.34
Wall minimum thickness 90 mm
Plasterboard and mortar or plaster putty sealing
ve (i↔o) WØ
min 100
max 315
Ø
min 100
max 315
Ø
min 100
max 315
WH25
7/50
LINDAB SAFE
OVERVIEW
WH25
LINDAB SAFE
8/50
Mechanism type
Manual and compact manual
Manual
Compact manual
1. Manual opening lever
2. Manual closing button
3. Lever position when the blade is open
4. Lever position when the blade is closed
Blade closing mode
Automatic closing with thermal fuse.
The control mechanism has a thermosensitive element
that automatically closes the blade when the temperature
in the duct exceeds 70°C (or 95°C for the re damper with
95°C thermal fuse).
It is possible to close the damper by pressing the indicated
button.
Blade opening mode
The damper must be opened when the ventilation system
if switched o.
It is possible to open the damper blade by rotating the le-
ver anticlockwise.
In case of closed damper as a result of the action of the
thermosensitive element, it is possible to manually reopen
the damper by rotating the lever counterclockwise once
the element has been replaced.
Position indication microswitches
On request, the re damper can be supplied with position
microswitches (S2 optional) that signal the blade position
(open or closed). Refer to the section Electrical connec-
tions p.35 for more details.
Closing by remote control
Not available
Temperature calibration of thermosensitive element for
automatic damper closing
70 °C±7 °C (Standard)
95 °C±9 °C (On request).
CAUTION:The compact mechanism is not interchangeable
with other types of manual mechanism�
Manual with magnet
1. Manual opening lever
2. Manual closing button
3. Lever position when the blade is open
4. Lever position when the blade is closed
Blade closing mode
Automatic closing with thermal fuse.
The control mechanism has a thermosensitive element
that automatically closes the blade when the temperature
in the duct exceeds 70°C (or 95°C for the re damper with
95°C thermal fuse).
It is possible to close the damper by pressing the indicated
button.
It is possible to remotely close the re damper.
The manual command mechanism with magnet is
equipped with an electromagnet which, in case power is
interrupted (interuption magnet version) or when power
is supplied (input magnet version), comands the closing of
the damper.
Blade opening mode
The damper must be opened when the ventilation system
if switched o.
In case of closed damper by pressing the closing button or
remotely by electromagnet, it is possible to manually open
the re damper blade by rotating the lever antyclockwise.
WH25
LINDAB SAFE
8/50
OVERVIEW
WH25
LINDAB SAFE
9/50
In case of closed damper as a result of the action of the
thermosensitive element, it is possible to manually reopen
the damper by rotating the lever counterclockwise once
the element has been replaced.
Position indication microswitches
It is advisable to install the re damper with position mi-
croswitches (S2 optional) which signal the position of the
blade (open or closed). Refer to the section Electrical con-
nections p.35 for more details.
Closing by remote control
With power supply input or interruption magnet.
Temperature calibration of thermosensitive element for
automatic damper closing
70 °C±7 °C (Standard)
95 °C±9 °C (On request).
Belimo motorized version
1. Manual closing switch
2. Manual opening lever
3. Position indicator
4. Blade locking lever
Blade closing mode
Automatic closing with thermal fuse.
The control mechanism has a thermosensitive element
that automatically closes the blade when the temperature
in the duct or in the room exceeds 72°C (or 95°C for the
95°C version).
To close the damper when the motor is connected, press
the switch on the temperature sensor or cut o the power
supply.
Blade opening mode
The damper must be opened when the ventilation system
if switched o.
To open the damper with the electric motor driven actua-
tor, provide power supply to the motor. Refer to the section
Electrical connections p.35 for further information.
To manually open the damper, use the handle supplied
and carefully rotate clockwise to the 90° indicator. To hold
the damper in open position operate on the lever indicat-
ed in gure.
During the manual opening of the damper, power must
not be supplied to the motor.
Position indication microswitches
The motorized versions are supplied with two microswitch-
es to show the blade's position (open or closed). Refer to
the section Electrical connections  p. 35 for further in-
formation.
Closing by remote control
If power to the motor is cut o, the blade will close.
Temperature calibration of thermosensitive element for
automatic damper closing
72 °C±7 °C (Standard)
95 °C±9 °C (On request).
Siemens motorized version
1. Manual closing switch
2. Manual opening lever
3. Screwdriver
4. Position indicator
Blade closing mode
Automatic closing with thermal fuse.
The control mechanism has a thermosensitive element
that automatically closes the blade when the temperature
in the duct or in the room exceeds 72°C (or 95°C for the
95°C version).
To close the damper when the motor is connected, press
the switch on the temperature sensor or cut o the power
supply.
Blade opening mode
The damper must be opened when the ventilation system
if switched o.
To open the damper with the electric motor driven actua-
tor, provide power supply to the motor. Refer to the section
Electrical connections p.35 for further information.
To manually open the damper, use the handle supplied
and carefully rotate counterclockwise to the 90 °C indica-
tor. To hold the damper in open position, rotate the screw
anticlockwise as shown in the picture.
During the manual opening of the damper, power must
not be supplied to the motor.
WH25
9/50
LINDAB SAFE
OVERVIEW
WH25
LINDAB SAFE
10/50
Position indication microswitches
The motorized versions are supplied with two microswitch-
es to show the blade's position (open or closed). Refer to
the section Electrical connections  p. 35 for further in-
formation.
Closing by remote control
If power to the motor is cut o, the blade will close.
Temperature calibration of thermosensitive element for
automatic damper closing
72 °C±7 °C (Standard)
95 °C±9 °C (On request).
WH25
LINDAB SAFE
10/50
TECHNICAL DATA
WH25
LINDAB SAFE
11/50
TECHNICAL DATA
The sizes shown are in mm.
Dimension
Ø mm 100 125 140 150 160 180
S blade
exposition mm000000
Lp mm 38 38 38 38 38 38
Ø mm 200 224 250 280 300 315
S blade
exposition mm 0 1 0 10 20 28
Lp mm 38 38 57 57 57 57
Lp Overlap length between re damper and duct
Manual
Manual with magnet
Siemens motorized version
Belimo motorized version
Weights
Ø mm 100 125 140 150 160 180 200 224 250 280 300 315
Weight kg 2,6 2,7 2,8 2,9 3,0 3,2 3,5 4,0 4,5 5,0 5,6 5,9
Manual version. Motorized version: +1 kg
WH25
11/50
LINDAB SAFE
INSTALLATION
WH25
LINDAB SAFE
12/50
INSTALLATION
The sizes shown are in mm.
Intended use
The MP3 re dampers are “Devices for use in heating, ven-
tilation and air conditioning (HVAC) systems at re bound-
aries to mantain compartmentation and protect means of
escape in case of re” according to the 3.1 paragraph of EN
15650:2010 standard.
It is compulsory to install the re damper according to the
instructions indicated in the technical data sheet and man-
ual to maintain the declared performances and, in particu-
lar, the re classes.
The double test (with the mechanism inside and outside
the re area) demonstrated that there is no preferred direc-
tion for the position of the damper, both in relation to air
ow and the side with the higher probability of exposure
to re, as indicated in standard EN1366-2:2015 (paragraph
6.2).
Use permitted in any civil and industrial building.
Use permitted in saline atmosphere, for example:
• maritime and port enviroments;
• sh markets;
• slaughterhouses;
• cheese makers.
Not allowed uses
• Use with installations dierent to those described in the
technical data sheet and manual;
• use as smoke control damper;
• use as shut o damper;
• use in external environments without adequate protec-
tion from atmospheric conditions;
• use in explosive environments;
• use on board of ships;
• use in cooker extraction hoods;
• use in pneumatic conveying systems of dust or corn;
• use in ventilation systems within locations subject to
chemical contamination;
• use in non inspectable enviroments.
• Installation in suspended ceilings.
Positioning brackets before xing
1. Positioning brackets
Blade rotation axis positioning
The re damper can be installed with the blade axis posi-
tioned vertically or horizontally or tilted at any angle.
Installation of exible connectors in order
to balance out the ventilation ducts
expansion
CAUTION: Refer anyway to law and national standardiza-
tion�
Flexible connectors compensate any duct thermal expan-
sion and wall bending in case of re.
Flexible connectors are used to limit re damper stresses
due to external forces in case of re and to preserve re
resistance class.
In general it is always appropriate the use of exible con-
nectors for the followings installations:
– light walls;
– Plasterboard and rock wool or Fire Batt (Weichschott)
sealing;
– Applique xing system.
Flexible connector must be normal ammability and in
case of re the grounding bonding should disconnet to
guarantee the complete separation between re damper
and connected air duct.
When exible connectors made of conductive material
(e.g. aluminum) are used, no additional grounding bond-
ing is required.
Despite exible connector installation, the re damper
must be installed in the construction support so that its
weight does not aect damper’s installation position both
during normal operation and in case of re.
It is recommended not to compress exible connectors in
the installation phase.
Flexible connector must be at least 100mm long and in
order that possible duct thermal expansions are balanced.
Take care that the exible connector does not interfer with
opening / closing movement of the blade.
Refer to the section Technical data p.11 for blade expo-
sition values.
WH25
LINDAB SAFE
12/50
INSTALLATION
WH25
LINDAB SAFE
13/50
Transfer Application (application not connected to air ducts on one or both sides)
Following tests performed as per EN 1366-2, section 6.3.6 Standard, it is possible to install the re damper free from air duct
from one or both sides.
• Attention: re resistance classication for transfer appli-
cation is conform to section Fire resistance classication
according to EN 13501-3-2009  p. 5limited to EI 120S
if the ducted classication is higher.
• End cap with mesh shall be mounted on the side not
connected to air duct.
• End cap with mesh is made from galvanized steel sheet.
• End cap with mesh is supplied loose from the re damp-
er.
• Refer to the section How to order (transfer Applica-
tion) p.14 for codes to use.
Components (Transfer Application)
1. End cap with mesh (to x to re damper with steel screws) 2. Fire damper
WH25
13/50
LINDAB SAFE
INSTALLATION
WH25
LINDAB SAFE
14/50
Technical data (Transfer Application)
1. Mechanism side
2. Mechanism opposite side
3. End cap with mesh
L1 End cap length mechanism side
L2 End cap length mechanism opposite side
Ø Fire damper nominal diameter
Length of end cap with mesh depending on re damper diameter Ø.
Ø L1 L2
100 40 40
125 40 40
140 40 40
150 40 40
160 40 40
180 40 40
200 40 60
224 40 40
250 60 80
280 60 100
300 60 100
315 60 120
Ø Fire damper nominal diameter
L1 End cap length mechanism side
L2 End cap length mechanism opposite side
How to order (transfer Application)
Code
Type EPNF End cap with mesh
Diameter XYZ Nominal diameter dimension (mm)
Length XYZ Length dimension (mm)
Examples Code
End cap with mesh length 80 mm for re damper Ø100 not connected to air ducts on mechanism side EPNF10040
End cap with mesh length 60 mm for re damper Ø200 not connected to air ducts on mechanism opposite side EPNF20060
End caps with mesh length 60 mm (mechanism side) and length 120 mm (mechanism opposite side) with mesh for re damper
Ø315 not connected to air ducts on both sides EPNF31560
EPNF315120
WH25
LINDAB SAFE
14/50
INSTALLATION
WH25
LINDAB SAFE
15/50
Minimum distances
It is recommended to keep enough space for using the
control mechanism or for maintenance.
In accordance with Articles 7 and 13 of EN 1366-2 respect
the minimum distances indicated below.
Minimum distances
1. Side vertical wall
2. Floor
a. Distance between re dampers installed within vertical wall
b. Distance between re damper and vertical lateral wall / oor
c. Distance between re dampers installed within oor
d. Distance between re damper and vertical lateral wall
Fire dampers installed within vertical
wall Fire dampers installed within oor
Installation a [mm] b [mm] c [mm] d [mm]
Rigid wall
EI 120 S Installation within vertical rigid wall p.19
Mortar or plaster putty sealing 50 75 - -
EI 90 S Installation within vertical rigid wall p.19
Plasterboard and rock wool 100 kg/m³ sealing 50 75 - -
Flexible wall
EI 120 S Installation within vertical light wall
(plasterboard) p.21
Mortar or plaster putty sealing 50 75 - -
EI 90 S Installation within vertical light wall
(plasterboard) p.21
Plasterboard and rock wool 100 kg/m³ sealing 50 75 - -
EI 60 S Installation within vertical light wall
(plasterboard) p.21
Plasterboard and rock wool 80 kg/m³ sealing 50 75 - -
EI 120 S Installation within vertical light wall (gypsum blocks
wall) p.22
Plaster putty sealing 50 75 - -
EI 90 S Installation within vertical light wall (gypsum blocks
wall) p.22
Plaster putty sealing 50 75 - -
Floor
EI 120 S Installation within oor p.23
Mortar sealing - - 50 75
EI 90 S Installation within oor p.23
Mortar sealing - - 50 75
WH25
15/50
LINDAB SAFE
INSTALLATION
WH25
LINDAB SAFE
16/50
Fire Batt (Weichschott) sealings
Fire dampers installed within vertical
wall Fire dampers installed within oor
Installation a [mm] b [mm] c [mm] d [mm]
Rigid
wall
EI 120 S Installation within vertical rigid wall with Fire Batt
(Weichschott) sealing p.24
Rock wool 140 kg/m³ and endothermic varnish sealing 50 * 50 - -
Flexible wall
EI 120 S Installation within vertical light wall (plasterboard) with
Fire Batt (Weichschott) sealing p.24
Rock wool 140 kg/m³ and endothermic varnish sealing 50 * 50 - -
EI 120 S Installation within vertical light wall (gypsum blocks
wall) with Fire Batt (Weichschott) sealing p.24
Rock wool 140 kg/m³ and endothermic varnish sealing 50 * 50 - -
Floor
EI 90 S Installation within oor and Fire Batt (Weichschott)
sealing p.25
Rock wool 140 kg/m³ and endothermic varnish sealing - - 200 75
* For the distance aincluding between 50 mm and 200 mm the re resistance class is reduced to EI 90 S
Installation remote from construction support
Fire dampers installed within vertical
wall Fire dampers installed within oor
Installation a [mm] b [mm] c [mm] d [mm]
Rigid wall
Installation remote from the vertical rigid wall p.26
Mortar or plaster putty sealing 200 110 * - -
Installation remote from the vertical rigid wall with Fire Batt
(Weichschott) sealing p.30
Rock wool 140 kg/m³ and endothermic varnish sealing 200 110 * - -
Flexible wall
Installation remote from vertical light wall
(plasterboard) p.28
Plasterboard and rock wool 100 kg/m³ or mortar or plaster putty
sealing
200 110 * - -
Installation remote from the vertical light wall (plasterboard)
with Fire Batt (Weichschott) sealing p.30
Rock wool 140 kg/m³ and endothermic varnish sealing 200 110 * - -
Installation remote from the vertical light wall (gypsum blocks
wall) p.26
Mortar or plaster putty sealing 200 110 * - -
Installation remote from the vertical light wall (gypsum blocks
wall) with Fire Batt (Weichschott) sealing p.30
Rock wool 140 kg/m³ and endothermic varnish sealing 200 110 * - -
Floor
EI 120 S Installation remote from the oor p.32
Mortar or plaster putty sealing - - 200 110 *
EI 90 S Installation remote from the oor p.32
Mortar or plaster putty sealing - - 200 110 *
* Due to rock wool panels thickness. See installation details.
Installations within vertical light wall (Shaft wall)
Fire dampers installed within
vertical wall Fire dampers installed within oor
Installation a [mm] b [mm] c [mm] d [mm]
EI 90 S Installation within vertical light wall (Shaft wall) p.34
Plasterboard and mortar or plaster putty sealing 50 75 - -
WH25
LINDAB SAFE
16/50
INSTALLATION
WH25
LINDAB SAFE
17/50
Construction supports characteristics
The European standard for re dampers foresees a precise
correlation between the wall/oor characteristics and the
re resistance class obtained, as well as the correlation be-
tween wall/oor used for the test and wall/oor used for
the actual installation.
The test results obtained on a type of wall/oor are valid
also for walls/oor of the same type but with greater thick-
ness and/or density than those used in the test.
For plasterboard walls, the test results are also valid for walls
with a greater number of plasterboard layers on each side.
As a result, the indicated thickness and density characteris-
tics are to be considered as minimum values.
The wall/oor in which the re dampers are installed must
be re class certied according to the standards foreseen
for the structure.
Rigid walls
Can be made with aerated concrete blocks, poured con-
crete, concrete panels, perforated cell elements in concrete
or brick in accordance with the following characteristics:
• minimum thickness 100 mm;
• minimum density 550 kg/m³.
The use of a reinforcing beam above the opening is recom-
mended for walls made from concrete blocks, bricks or in
concrete cell elements.
For walls built with perforated elements, it is also recom-
mended that the area of the opening be made from full
elements (for example aerated concrete blocks) to guaran-
tee the correct adhesion of the mortar.
1. Reinforcing beam
Light plasterboard vertical walls
During testing, light plasterboard walls have been used
with the following characteristics:
• U-shaped horizontal metal frame (50 mm) and C-shaped
vertical frame (49 mm) made from 0,6 mm thick sheet
metal;
• Vertical proles placed with a maximum spacing of 625
mm between each other;
• Rock wool lling which has density 80 kg/m³;
• Each side is made from two plasterboard layers 12,5 mm
thick, unalinged to avoid alignment between the joints
of the layer above and below.
The following indications are given for the installation walls:
• metal proles minimum width: 49 mm;
• metal proles minimum thickness: 0,6 mm;
• vertical proles placed with a maximum spacing of 625
mm between each other;
• vertical prole xing with selfthreading screws or by
clinching to the bottom horizontal prole and insertion
in the top horizontal prole;
• proles xed using self-threading screws or by clinching
on every intersection.
• installation of a frame around the damper with base and
height where shown in the installation instructions;
• rock wool lling which has minimum density 80 kg/m³:
• each side is made from two plasterboard layers 12,5 mm
minumum thick, unalinged to avoid alignment between
the joints of the layer above and below.
• the front plasterboards layers are xed using long
enough screws to pass through the lower plasterboard
and attach to the steel prole underneath.
1. Plasterboard thickness 12,5 mm
2. Rock wool density up to 80 kg/m³ (optional)
3. Horizontal U-shaped prole
4. Vertical C-shaped prole
5. Self-drilling screw Ø 3,5 X 25 mm
6. Self-drilling screw Ø 3,5 X 35 mm
WH25
17/50
LINDAB SAFE
INSTALLATION
WH25
LINDAB SAFE
18/50
Gypsum blocks light walls
Gypsum blocks wall can be built with special solid gypsum
blocks with interlocking shaped edges as indicated in the
supplier's instructions and according to the following char-
acteristics:
• minimum thickness 70 or 100 mm according to the type
and resistance class required;
• minimum density 995 kg/m³.
It is generally advisable to rst build the wall and then pro-
vide the opening for the re damper.
Aerated concrete oors
Aerated concrete oors can be built during installation or
with preformed slabs with interlocking shaped edges ac-
cording to the following characteristics:
• minimum thickness 100 or 150 mm according to the
type and resistance class required;
• minimum density 650 kg/m³
Poured concrete oors
Poured concrete oors can be built during installation or
with preformed slabs with interlocking shaped edges ac-
cording to the following characteristics:
• minimum thickness 100 or 150 mm according to the re-
sistance class required;
• minimum density 2200 kg/m³.
WH25
LINDAB SAFE
18/50
INSTALLATION
WH25
LINDAB SAFE
19/50
Installations within vertical rigid wall
Refer to the section Construction supports characteris-
tics p.17 for further information.
Comply with the minimum distances indicated on section
Minimum distances p.15.
Wall opening
A opening must be provided in the wall as indicated in the
table and in the drawing
Damper positioning
Position the damper in the opening so that the side of the
closing mechanism extends as indicated in the drawing.
Filling
Fill the space between the wall and the damper as indicat-
ed in the table and in the drawing.
Fire resistance classi-
cation “D” hole size
[mm]
Wall minimum thickness
“S”
[mm] Sealing
EI 120 S Installation within vertical rigid wall
Wall minimum density 550 kg/m³ EI 120 S
(500 Pa)
From Ø + 25
to Ø + 440
(circular hole) 100 Mortar or plaster putty sealing
EI 90 S Installation within vertical rigid wall
Wall minimum density 550 kg/m³ EI 90 S
(500 Pa)
From (Ø + 50) x (Ø + 50)
To (Ø + 70) x (Ø + 70)
(square hole) 100 Rock wool 100 kg/m³ with
inll plasterboard (thickness
12.5 mm)
WH25
19/50
LINDAB SAFE
INSTALLATION
WH25
LINDAB SAFE
20/50
EI 120 S Installation within vertical rigid wall
1. Mortar M-10, EN998-2 or plaster putty
Lp Overlap length between re damper and duct: see section
Dimension p.11
D Hole size: see table above
EI 90 S Installation within vertical rigid wall
1. Plasterboard inll panel, thickness 12,5 mm
2. Rock wool, 100 kg/m³
3. Self-drilling screw Ø 3,5 X 45 mm
Lp Overlap length between re damper and duct: see section
Dimension p.11
D Hole size: see table above
WH25
LINDAB SAFE
20/50

Other manuals for WH25

1

Other Lindab Fire And Smoke Damper manuals

Lindab FBC1 User manual

Lindab

Lindab FBC1 User manual

Lindab CFDM Manual

Lindab

Lindab CFDM Manual

Lindab DRU User guide

Lindab

Lindab DRU User guide

Lindab SDR2-M Manual

Lindab

Lindab SDR2-M Manual

Lindab SDJR-S User manual

Lindab

Lindab SDJR-S User manual

Lindab WK45 Series Installation and operation manual

Lindab

Lindab WK45 Series Installation and operation manual

Lindab WK45 Series User manual

Lindab

Lindab WK45 Series User manual

Lindab FDS-M User manual

Lindab

Lindab FDS-M User manual

Lindab FBC2 Installation and operation manual

Lindab

Lindab FBC2 Installation and operation manual

Lindab LFD Quick start guide

Lindab

Lindab LFD Quick start guide

Lindab SKMTR User guide

Lindab

Lindab SKMTR User guide

Lindab FNC1 Installation and operation manual

Lindab

Lindab FNC1 Installation and operation manual

Lindab SDR-S User manual

Lindab

Lindab SDR-S User manual

Lindab WH45 Series Installation and operation manual

Lindab

Lindab WH45 Series Installation and operation manual

Lindab RECTANGULAR Series Installation and operation manual

Lindab

Lindab RECTANGULAR Series Installation and operation manual

Lindab CIRCULAR Series Installation and operation manual

Lindab

Lindab CIRCULAR Series Installation and operation manual

Lindab WH25 Installation and operation manual

Lindab

Lindab WH25 Installation and operation manual

Lindab WH45P Installation and operation manual

Lindab

Lindab WH45P Installation and operation manual

Lindab RECTANGULAR Series User manual

Lindab

Lindab RECTANGULAR Series User manual

Lindab RECTANGULAR Series Installation and operation manual

Lindab

Lindab RECTANGULAR Series Installation and operation manual

Popular Fire And Smoke Damper manuals by other brands

Greenheck FSD Series Installation, operation and maintenance instructions

Greenheck

Greenheck FSD Series Installation, operation and maintenance instructions

Price FD-RD installation instructions

Price

Price FD-RD installation instructions

Carrier 48DK024 installation instructions

Carrier

Carrier 48DK024 installation instructions

aldes Minisone Assembly instructions

aldes

aldes Minisone Assembly instructions

Mandik FDMR installation instructions

Mandik

Mandik FDMR installation instructions

K-VENTIL FD-10 quick start guide

K-VENTIL

K-VENTIL FD-10 quick start guide

Mandik SEDM-L manual

Mandik

Mandik SEDM-L manual

Swegon SIRI a Installation, commissioning maintenance

Swegon

Swegon SIRI a Installation, commissioning maintenance

Mandik FDMB Technical documentation

Mandik

Mandik FDMB Technical documentation

Trox Technik EK-JZ manual

Trox Technik

Trox Technik EK-JZ manual

Mandik MSD manual

Mandik

Mandik MSD manual

actionair DWFX-F installation guide

actionair

actionair DWFX-F installation guide

Wildeboer FR90 manual

Wildeboer

Wildeboer FR90 manual

Mandik FDMD installation instructions

Mandik

Mandik FDMD installation instructions

Swegon Actionair A60 manual

Swegon

Swegon Actionair A60 manual

Schako BSK-RPR Additional operating instructions

Schako

Schako BSK-RPR Additional operating instructions

Trox Technik FKR-EU Installation and operating manual

Trox Technik

Trox Technik FKR-EU Installation and operating manual

Trox Technik FKRS-EU Installation and operating manual

Trox Technik

Trox Technik FKRS-EU Installation and operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.