Programmable Logic Controller Installation Guide
XB(E)C-DR28U/DR28UA/DR28UP
XB(E)C-DN32U/DN32UA/DN32UP
XB(E)C-DP32U/DP32UA/DP32UP
(Applied to /DC Power unit)
This installation guide provides simple function information of PLC control. Please carefully read
this data sheet and manuals before using products. Especially read safety precautions and
handle the products properly.
■ Meaning of warning and caution inscription
WARNING indicates a potentially hazardous situation which,
if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate injury.
It may also be used to alert against unsafe practices
①
Do not contact the terminals while the power is applied.
②Protect the product from being gone into by foreign metallic matter.
③Do not manipulate the battery (Charge, disassemble, hitting, short, soldering)
①
Be sure to check the rated voltage and terminal arrangement before wiring
②When wiring, Tighten the screw of terminal block with the specified torque range
③Do not install the flammable things on surroundings
④Do not use the PLC in the environment of direct vibration
⑤Except expert service staff, Do not disassemble or fix or modify the product
⑥Use the PLC in an environment that meets the general specifications contained
in this datasheet.
⑦Be sure that external load does not exceed the rating of output product.
⑧When disposing of PLC and battery, treat it as industrial waste.
To install, observe the below conditions.
℃
℃
5 ~ 95%RH, non-condensing
5 ~ 95%RH, non-condensing
5 Vibration
Resistance
Frequency Acceleration Amplitude Times
IEC 61131-2
each
direction
for
X, Y, Z
The following table shows the general specifications of the XGB. For more information, please
refer to user manual
■ General Specifications
Items Specifications
Operation method
Reiterative operation, fixed cycle operation,
Interrupt operation, constant period scan
I/O control method Batch processing by simultaneous scan (Refresh method),
Directed by program instruction
Basic instruction: 60ns/step
XBC:32Kstep, XEC:384KB
Main + Expansion 10slot (Communication 2slot)
Operation mode RUN, STOP, DEBUG
Delay of operation, abnormal memory, abnormal I/O
Data keeping method at
power failure
Latch (Retain) area setting in basic parameter
Built-in function
Cnet (RS-232C, RS-485), Enet, (IEEE802.3)
Datalog, Web Server,
PID, High speed counter, RTC
Positioning (UP Type available), Analog (UA Type available)
■Check the battery attached in the product
1)Rated Voltage/Current : DC 3.6V/800mAh
2)Warranty period : 3 year (at 25℃, Normal temperature)
3)Usage : Program/Data back-up, RTC driving when power-off
4)Specification : Lithium battery (φ14 X26mm)
■ Check the accessory (Order the cable if need)
1) USB-301A : USB connecting (download) cable.
2) C40HH-□PH-XBI : Cable for positioning (for UP type)
3) XTB-40H : I/O link(for UP type)
■ This is front part of the CPU. Refer to each name when driving the system. For more
information, refer to user manual.
①
②
③
④
⑤
⑥
⑦
⑧
Built-in Communication(For Ethernet)
⑨
⑩
24V Output(Sub-power, Not applied to /DC power unit)
⑪
Built-in Communication Terminal block(For RS232C/485 communication)
⑫
⑬
⑭
Analog input (UA type) / Positioning 3, 4axis
⑮
Analog output (UA type) / Positioning 1, 2axis
■ Dimension (mm)
Installing / Removing Modules
■ Here describes the method to install and remove each product.
1) Installing module
①Eliminate the Extension Cover at the
product.
②Push the product and connect it in
alignment with Hook for Fixation of four
edges and Hook for Connection at the
bottom.
③After connection, push down the Hook
for Fixation and fix it completely.
2) Removing module
①Push up the Hook for Disconnection, and then detach the product with two hands.
(Do not remove the product by force)
■ Power wiring
1) In case that the power is out of rated voltage, connect constant voltage transformer
2) Connect the power having the small noise between cables or between earths.
In case of having lots of noise, connect the isolating transformer or noise filter.
3) power for PLC, I/O device and other machines should be separate.
4) Use the dedicated earth if possible. In case of Earth works, use 3 class earth
(earth resistance 100 Ωor less) and Use more than 2㎟ cable for earth.
If the abnormal operation is found according to the earth, separate the earth
■ Warranty period
18 months after the production date.
■ Scope of Warranty
18-month warranty is available except:
1) The troubles caused by improper condition, environment, or treatment except the
instructions of LS ELETRIC.
2) The troubles caused by external devices
3) The troubles caused by remodeling or repairing based on the user’s own discretion.
4) The troubles caused by improper usage of the product
5) The troubles caused by thereason which exceeded the expectation fromscience and
technology level when LS ELETRIC manufactured the product
6) The troubles caused by natural disaster
■ Change in specifications
Product specifications are subject to change without notice due to continuous product
development and improvement.
LS ELECTRIC Co., Ltd. www.ls-electric.com 10310001354 V4.4 (2022.9)
•E-mail: automation@ls-electric.com
•Headquarter/Seoul Office
Tel: 82-2-2034-4033,4888,4703
•LS ELECTRIC Shanghai Office (China)
•LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China)
•LS-ELECTRIC Vietnam Co., Ltd. (Hanoi, Vietnam)
•LS ELECTRIC Middle East FZE (Dubai, U.A.E.)
•LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands)
•LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan)
•LS ELECTRIC America Inc. (Chicago, USA)
•Factory: 56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnam-
do, 31226, Korea
Power
PE
Supply
Noise
Filter
PLC
Input/Output
PLC Power
Performance Specifications
Applicable Support Software
■ For system configuration, the following version is necessary.
1) XG5000 Software : V4.04 or above
Accessories and Cable Specifications
Parts name and Dimension (mm)
1354
PWR
RUN
ERR
STATE
RD/WR A/D D/A
V0+
I0+
COM0
V1+
I1+
COM1
V2+
I2+
COM2
V3+
I3+
COM3
V0+
V0-
V1+
V1-
I0+
I0-
I1+
I1-
NC
NC
+
-
24Vd.c.
100-240Va.c.
N L
PE
24V 24G
OUTPUT
50/60 Hz 24Vd.c., 0.4 A
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
COM
+ -
- +
24Vd.c.24Vd.c.
220Va.c.
2 A
00
COM0
01
02
03
COM1
COM2
COM3
04
05
06
07
COM4
08
09
0A
COM5
0B
DR28UA
123 4
5 6
7
910 11 12 13 14 15
8
Hook for fixation
Extension cover
Boss for fixation
Boss for connection