Lyntech LY69-010-68 User manual

CONTENTS
Section Page No.
1.00
1.01
1.02
1.03
1.04
1.05
2.00
2.01
2.02
2.03
2.04
2.05
2.06
2.07
2.08
2.09
2.10
2.11
2.12
2.13
2.14
2.15
2.16
2.17
2.18
2.19
3.00
3.00
3.01
3.02
3.03
3.04
3.05
3.06
4.00
4.01
4.02
4.03
Introduction
ST5000 Control Panel
K6600 LCD Remote Keypad
K6550 LED Remote Keypad
SL6600 Sleep Watch Remote Keypad
AD1000 Voice Dialer
User Operation
Day (Off) Mode
Full Guard Arming
Part Guard Arming Option 1
Omitting Zones Full Guard
Omitting Zones Part Guard
Activating & Resetting Keypad Panic
Disarming System Using Keypad
Disarming System After Activation
Arming & Disarming Part Guard Option 2
Arming and Disarming Sleep Watch Zones
Activating Sleep Watch Panic Button
Silencing Panic Alarm Activation
Memory Recall
Displaying Faulted Zones
Intelligent Auto Reset
Mains Supply Failure Indication
Mains Supply Failure and Low Battery Indication
Low Battery Indication
Service Required
User Programming Section
Entering User Programming Mode
Changing Master User Code
Enable User Codes 2 - 5
Enable User Code 6
Setting Secure Zones
Setting Chime Zones
Exit User Programming
System Test
Quick User Reference Guide
User Programming Notes
Fault Indications
2
2
3
3
4
4
5
5
5
6
6
7
7
8
8
9
9
9
10
10
11
11
11
11
11
11
12
12
12
12
13
13
14
14
15
16
17
18
1

2.00 USER OPERATION
2.01 Day (Off) Mode
This is the normal (default) setting of the control panel. The alarm will sound if the following
types of zones are activated in Day Mode and also to indicate faults.
Type of Alarm or Fault Indication
Panic, Personal Alarm (PA) Full alarm, external and internal sirens sound.
Fire Detection Zones Full alarm, external and internal siren intermittent sound.
24 Hour Alarm Internal sirens only.
Tamper Fault Tamper LED On(ST5000)
LCDDisplay Fault Tamper (K6600)
Zone Fault Day LED flashing
2.02 Full Guard Arming
In FULL GUARD armed state, zones connected with intrusion detectors to the control
panel will detect any unauthorised entry and set off the internal and external alarm.
Make sure all zones and P.A. (Panic Alarm) loops are closed. The control panel will not
switch to the armed mode if they are open. Full Guard Arming is indicated by the internal
speaker beeping during exit time count down.
To arm the system enter a valid user code:
Example:
System Ready
Melcom
Enter: 1 2 43 System Arming
K6600 LCD Display
Note: System can be quick set by pressing Set key for 3 seconds if this feature is
enabled by the installation engineer.
System Armed
EXIT time is delayed whenever a zone is opened or in fault,
(e.g. a door contact on the front door is opened). Count down
will resume when the zone is closed, omitted or fault re-
moved.
5

2.03 Part Guard Arming Option 1
PART GUARD means that the system is only armed in pre-set zones, allowing you to oc-
cupy or pass through the unarmed zones. This is normally used for night-time setting of the
alarm system to isolate the bedrooms.
Enter a Valid User Code and press SET within 3seconds.
Example:
Enter:
System Ready
Melcom
? ? ?? Part Arming
System Armed
PART GUARD mode will become armed within 5 seconds (or
the time programmed by the engineer). You should leave or go
to a non-armed part of the building, zone LEDs, PA and Tam-
per will flash momentarily to indicate Part Guard Arming.
Note: If you have zones programmed as Sleep Watch zones, these can only be
armed after Part Guard arming and pressing the sleep button on the sleep watch
remote keypad.
2.04 Omitting Zones Full Guard
You might wish to omit zones in full guard before arming the system. For example, you can
omit the zone that protects the garage.
SET
Enter a valid user code and press OMIT, enter zone number to be omitted and press
OMIT.
Enter: 1
? ? ??
Press: OMIT 2
Press: OMIT
System Arming
Omit Zones
2
System Arming
Zones omitted will be reintroduced to the system once the system has been disarmed. If
you wish to have a zone disabled from the system, you must contact your installation
engineer.
Note: PA, Tamper, Fire Zones & 24 Hour Zones can not be omitted.
6
Example: Omitting zone 2

2.05 Omitting Zones Part Guard
You might wish to Omit Zones in Part Guard before arming the system. For example, you
can omit the zone that protects the kitchen.
Enter a Valid User Code and press OMIT, enter zone number ,press OMIT and SET.
Example: Omit Zone 6 .
Enter: ?
Zones omitted will be reintroduced to the system once the system has been disarmed. If
you wish to have a zone disabled from the system you must contact your installation engi-
neer.
Note: PA, Tamper, Fire Zones & 24 Hour Zones can not be omitted.
System Arming
?? ?
Press: OMIT 6
Press: OMIT SET
Omit Zones
6
Part Arming
2.06 Activating & Resetting Keypad Panic
If the control panel is armed or in day mode, activating of the Keypad Panic will sound the
external and internal sirens. To silence the alarm, enter any USER CODE, day LED will
flash and press RESET.
Press: SET OMIT SET (S.O.S.) Alarm
Enter: Alarm
Personal Attack
? ? ? ? RESET
Example:
Silence alarm after keypad activation.
Note: If you do not press RESET after enter your code the control panel will not op-
erate until RESET has been pressed.
7

2.07 Disarming System Using Keypad
When returning to the premises, enter via the ENTRY/EXIT Zone. This will activate the en-
try tone for length of ENTRY time as programmed by your installation engineer. To prevent
the activation of the alarm before the elapse of the ENTRY time, you must enter any valid
user code. The keypad sounder will speed up when entry time has nearly timed out.
Example: disarming system.
Enter: ? System Ready
Melcom
? ? ?
NOTE: Entry tone will speed up before sounding the internal alarm. If after 30
seconds, still no valid user code has been entered, the external siren will sound. The
keypad will lock up for 2 minutes if after 15 key presses no valid code is recognised.
2.08 Disarming System After Activation
When returning to the premises, enter via the ENTRY/EXIT Zone. This will activate the en-
try tone for length of ENTRY time as programmed by your installation engineer.
Enter a valid user code to disarm the system and press RESET.
Example: disarming systemafter zone 3activation.
Enter: ? ? ? ? Alarm
Zone 3
The activated zones will be indicated by zone LED on the ST5000 and on the K6600 LCD
keypad date time and zone number or name. Note which zone or zones have activated.
Enter your user code and press the reset key. After resetting the system investigate those
zones which have been activated.
Any activation caused by a Tamper fault has to be cleared before the system can be reset.
System Ready
Melcom
Enter: RESET
Zone 5 LED illuminated.
Note: Failure to reset the control panel will cause the system to lock up, the system
will not function until the reset key has been pressed.
If your system has been programmed to be reset after an alarm activation by your
installer. After silencing the alarm, you will need to contact your installer to reset the
system.
8

2.09 Arming & Disarming Part Guard Option 2
If your system is fitted with a SL6600 sleep watch keypad, the system can be part guard
armed and disarmed by using this keypad providing that this function has been enabled by
your installer
Press:
SLEEP for 3 seconds key illuminates green and
gives 1 beep. Part guard is now armed.
System Armed
Press:
SLEEP
for 3 seconds key light extinguished and
gives 2 beeps. Part guard is now dis-
armed.
System Ready
Melcom
2.10 Arming & Disarming Sleep Watch Zones
Sleep Watch zones act in the following way. When the system is part guard armed, Sleep
Watch zones remain unarmed until the sleep button on the sleep watch has been pressed.
These zones can be disarmed by using the sleep watch button (either permanently or tem-
porary timed). This is useful should you need to go to the bathroom or kitchen at night .
If a Sleep Watch zone is activated ,it will not activate the alarm immediately but give a
timed delay to enable you to enter your user code into the system keypad. The sleep watch
keypad will a give corresponding number of beeps to indicate which zones has been acti-
vated.
Press:
SLEEP for 1 second key illuminates green.
Sleep watch zones are armed.
System Armed
Press:
SLEEP for 1 second key illuminates red. Sleep
watch zones are disarmed.
System Armed
Note: If sleep watch automatic rearm is programmed by your installer sleep watch
zones will rearm automatically after the time preprogrammed by your installer and
the sleep button illuminates green when zones are rearmed.
2.11 Activating Sleep Watch Panic Button
The sleep watch keypad has an integrated digital panic button, which can be activated by
pressing for 1 second. This will activate a full alarm I( ie: both internal and external sirens).
Press: for 1 second key flashes green.
Internal and external sirens activated.
Alarm
PANIC
9

If your system is fitted with sleep watch remote keypads , LCD remote keypad or push
panic button and has been activated by pressing the button or entering the panic keypad
alarm sequence, enter a valid user code and press reset to silence alarm.
Enter: ? ? ?? Alarm
Personal Attack
Press: System Ready
Melcom
RESET
2.12 Silencing Panic Alarm Activation
Note: If the is alarm activated by using a panic button, after entering your user code
you must reset the button using a reset key supplied with the unit.
If you do not reset the panic button, the alarm system will not function until the
panic button is reset and the reset key on the keypad.
2.13 Memory Recall
The control panel can recall the last 50 activations and can also give the date and time of
activation if fitted with K6600 LCD remote keypad, last activation is displayed first. Only the
master user code can recall the activation memory log.
To recall alarm activations.
Press: PROG
Enter: ? ? ?? User
Programming
Press: DD-MM-YY HH-MM
Personal Attack
MEM
Press: System Ready
Melcom
RESET
Keep pressing MEM to go through the activation log.
to exit memory recall, and return to day
mode.
Day LED
flashing
Master
User Code
zone LED flashes.
10

2.14 Displaying Faulted Zones
If a zone is found to be in fault, this is indicated by the day LED flashing. To check which
zone is in fault enter a valid user code and note which zone LED is illuminated. A tamper
fault is indicated immediately by the tamper zone LED illuminating.
Enter: Fault
Zone 3
? ? ??
Note: System can not be armed unless the zone fault is cleared or omitted from the
system when arming.
2.15 Intelligent Auto Reset
If the panel has activated whilst you are away, once the alarm time as timed out, the panel
will automatically reset. The alarm will activate once more should another zone be acti-
vated, or if the zone that originally activated, is closed. Upon entering the premises the
strobe will be flashing to indicate system has been activated.
Enter a valid user code and note which zones have activated then press RESET key.
2.16 Mains Supply Failure Indication
Mains LED illuminated RED = No mains supply Fault
Mains
2.17 Mains Supply Failure and Low Battery Indication
Mains LED illuminated RED and flashing = No Mains and
Low Battery
Fault
Mains / Battery
2.18 Low Battery Indication
Mains LED illuminated ORANGE and flashing = Low Battery Fault
Low Battery
2.19 Service Require
Day LED flashing and system arms = Service Required Service Required
11

3.00 User Programming Section
You can adjust several control panel settings by entering User Programming MODE. To
enter user programming from Day Mode press PROG and enter your Master User Code:
Press:
User
Programming
PROG
Enter: 1 2 3 4
All Red LEDs illuminate.
Zones LEDs extinguish, except Tamper
You are now in user programming mode, follow the instructions to make any changes
allowable under user programming.
Note: Only the master user code can make any changes in user programming mode.
3.01 Changing Master User Code
It is advisable to change your master code from the factory default setting 1 2 3 4. It is
important that you do not forget this code as no programming changes can be made in ei-
ther user or engineer programming without entering this code.
Press: 8 Zone 1-4 LEDs illuminate Enter New Code
Master
Enter a new 4 digit number do not use 0 0 0 0. After acceptance a double beep is given
and unit returns to user programming.
3.02 Enable User Codes 2 - 5
User Codes 2 – 5 are disabled and can be enabled by entering the following programming
locations:
Press: Enter New Code
User 2
Enter a 4 digit number. Do not use 0 0 0 0 as this will disable that user code. After accep-
tance of code a double beep is given and the system returns to user programming.
Press:
Press:
Enter New Code
User 3
Enter New Code
User 4
Enter New Code
User 5
Press:
2
3
4
5
Zone 1-4 LEDs illuminate
Zone 1-4 LEDs illuminate
Zone 1-4 LEDs illuminate
Zone 1-4 LEDs illuminate
12

3.03 Enable User Code 6
User code 6 is unable to disarm secure zones. This is useful if you have a cleaner , whom
you do not want to enter any particular zones.
To enable user code 6 from user programming mode:
Press: 6 Zone 1-4 LEDs illuminate Enter New Code
User 6
Enter a 4 digit number. Do Not use 0 0 0 0 as this will disable the user code. After accep-
tance of each code a double beep is given and the system returns to user programming.
3.04 Setting Secure Zones
Secure Zones act as normal zones except if the system is disarmed by user code 6 where-
upon those zones programmed as secure zones, remain armed.
If a Secure Zone is activated after the system has been disarmed by user code 6, internal
sirens will sound only. User code 6 can silence the alarm and arm the system again, but
can not reset the secure zones.
Upon enter user code master or user codes 2-5 the secure zone or zones will flash indicat-
ing activation. After entering your user code press RESET to reset the system.
To set secure zones from user programming mode:
Press: 7
Enter zone numbers to set as secure zones, (zone LED will flash if set as secure zone).
Toggle corresponding zone key number to enable or disable secure zones.
Secure Zones
None
Example: Programming zone 2 as secure zones from user programming mode:
Press: 7
Tamper LED illuminated.
Tamper LED illuminated.
Press: 2 zone 2 illuminated.
Press: RESET
Secure Zones
None
Secure Zones
Zone 2
User
Programming
Tamper LED illuminated
13

3.05 Setting Chime Zones
If a zone programmed as a chime is activated in day mode, the internal siren and K6600
LCD remote keypad will beep to indicate activation of that zone. This allows you to monitor
children or people in your premises or home.
To set chime zones from user programming mode:
Press: 9 LED illuminated.
Enter zone numbers to set as chime zones, zone LED will flash if set as chime zone. Tog-
gle corresponding zone key number to enable or disable chime zones.
Chime Zone
None
Example: Programming zone 1 as a chime zone from user programming mode:
Press: 9 PA LED illuminated. Chime Zone
None
Press: 1 Zone 1 LED illuminated. Chime Zone
1
User
Programming
Press: RESET Tamper LED illuminated.
3.16 Exit User Programming
To exit user programming and return to day Mode:
Press: System Ready
Melcom
Tamper LED extinguished.RESET
14

4.00 System Test
It is recommended that you test the system once a week to ensure that it is working
correctly.
To test the system:
Press: PROG All Red LEDs illuminate.
7
Enter: ? ? ?? User
Programming
Press: 0 Tamper and PA LED illuminate. System Test
System Test
Strobe
System Test
Volume High
System Ready
Melcom
System Test
Volume Low
System Test
Zone Test
System Test
External Siren
System Test
Press:
Press:
Press:
Press:
Press:
Press:
Press:
1
3
2
4
5
0
RESET
Tests strobe.
Tests external siren.
Tests high volume internal alarm
Tests low volume internal alarm
Testing sensors and detectors, follow
Manufacturer’s instructions supplied with
units on how to test in this manner.
Exits system test and returns to user pro-
gramming.
Exits user programming and
returns to Day Mode.
Master
User Code
K6600 LCD DISPLAY
15
RESET

4.01 QUICK USER REFERENCE GUIDE
Full Guard Arming Option 1 Enter User Code Leave premises via
exit route
# Full Arming Guard Option 2 Press: SET 3 seconds Leave premises via
exit route
Part Guard Arming Option 1 Enter User Code Press: SET Leave to none pro-
tected area of building
# Part Guard Arming Option 2 Sleep Watch Keypad
Press: SLEEP for 3 seconds
Sleep Button illumi-
nates Red
Silent Set Press: PROG during exit time Keypad no beeps
Omit Zones Full Guard Press: OMIT after entering
user code, enter zone number
Press: OMIT
Omit LED illuminates
Omit Zones Part Guard Press: OMIT after entering
user code, enter zone number
Press: OMIT, SET
Omit LED illuminates
Full Guard Disarming Enter User Code Day LED illuminates
Part Guard Disarming Option 1 Enter User Code Day LED illuminates
# Part Guard Disarming Option 2 Sleep Watch Keypad
Press: SLEEP for 3 seconds
Sleep LED
extinguishes
Disarming After Alarm Activation Enter User Code
Press: RESET
Day LED illuminates
Panic Keypad Press: SET, OMIT, SET SOS) Day LED flashes
Memory Recall Press: PROG, Enter Master
User Code Press: MEM
Last Activation Display
First
Note:
To use those options marked with “# “, ask your installation engineer to program
them.
Important:
If after 14 key presses a valid code has not been entered the keypad will not accept
any entries for 2 minutes. You must wait then re-enter your user code.
Do not leave this quick reference guide with your user codes near the control panel.
16

17
Note:
The alarm system can provide valuable protection for your home and property if
used properly. However, the system can not guarantee complete protection against
burglary or robbery. Therefore, the manufacturer, distributor or supplier will not be
held responsible for any loss or damage that may occur. Every effort has been made
to provide accurate information, however, slight variations can occur. We reserve
the right to make changes for product improvement at anytime.
Function Factory Settings User Settings
Master User Code 1 2 3 4
User Code 2 Disabled
User Code 3 Disabled
User Code 4 Disabled
User Code 5 Disabled
User Code 6 Disabled
Secure Zones
Zone 1 Clear
Zone 2 Clear
Zone 3 Clear
Zone 4 Clear
Zone 5 Clear
Zone 6 Clear
Chime Zones
Zone 1 Clear
Zone 2 Clear
Zone 3 Clear
Zone 4 Clear
Zone 5 Clear
Zone 6 Clear
4.02 USER PROGRAMMING NOTES

4.03 PROBLEM AND FAULT INDICATION
18
LED Indication Fault Action
Mains LED
RED
Mains Supply Failure Call installer if you do not have a
general mains power failure.
Mains LED
Flashing RED
Mains Supply Failure and Low
Battery.
Call installer to check the battery if
LED remains on.
Mains LED
Flashing Orange
Low Battery Call installer to check the battery if
LED remains on
Day LED
Flashing
Enter user code if Zone LED illu-
minates Zone Fault.
Check the zone for faults. Call In-
staller if you cannot clear.
Day LED
Flashing
Enter User Code if no Zone LED
illuminates, and Day LED still
Flashing.
System Requires Service, call in-
staller.
Tamper LED
Illuminated
In Day Mode Tamper LED illu-
minated, Tamper Fault.
Call installer.
PA LED
Illuminated
Can Not Arm System. Panic button not reset, also press
RESET.
Zone LED
Illuminated
When arming system it will not
arm.
Check zone to see if you can clear
the fault, if not OMIT that zone
from system and call installer to
check that zone.
Keypad Accepts
No Presses
Keypad Tamper Activated Wait 2 minutes and try again. If no
correct code entered after 4 at-
tempts the keypad stops working
for 2 minutes.
Note: There are no user serviceable parts contained within this control panel.
DO NOT attempt to interfere with, or alter any of the electronic components. To do
so may damage the electronic circuitry and will invalidate your warranty.
Table of contents