5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8207 Rev.3 P. 1 / 3
INSTRUCTION MANUAL
LIGHTNING SURGE PROTECTOR FOR
PROFIBUS-PA MODEL MDP-PA
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Surge protector....................................................................(1)
DIN rail mounting adaptor*...............................................(1)
Screws for DIN rail mounting (M4 × 8)* ...........................(2)
*Included with option code /A33
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
LIMITATION APPLICABLE TO M-RESTER
The M-RESTER will protect electronics equipment from
damage caused by lightning by absorbing most of the
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.
GENERAL
■FUNCTION & FEATURES
• Designed specifically for PROFIBUS-PA network
• No interruption of transmission signal by unplugging the
head element module
■SPECIFICATIONS
LINE TO
LINE
LINE TO
EARTH
SHLD TO
EARTH
Max. continuous
operating voltage Uc)
±27V ±160V ±160V
Voltage protection level
(Up) @2kV (1kA)
±60V ±600V ±600V
Leakage current ≤ 5µA
@±27V
≤ 5µA
@±160V
≤ 5µA
@±160V
Capacitance @1 MHz ≤ 1500 pF ≤ 100 pF ≤ 100 pF
Response time ≤ 4 nsec. ≤ 20 nsec. ≤ 20 nsec.
Max. discharge current
(Imax)
5000A (8 / 20 µs)
Nominal current (IN) 500mA
Internal series resistance
≤ 3.3 Ω including return
Max. line voltage ±27V
POINTS OF CAUTION
■ENVIRONMENT
• When heavy dust or metal particles are present in the
air, install the surge protector inside proper housing with
sufficient ventilation.
• Do not install the surge protector where it is subjected to
continuous vibration. Do not subject the unit to physical
impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■DIELECTRIC STRENGTH TEST
• Loosen the screw located at the left-center of the element
and remove the element module from the base before
conducting a dielectric strength testing. Otherwise the
element will start discharging at a voltage exceeding the
max. continuous operating voltage (Uc), which can cause
insulation failure of the module.
Be sure to return the element and fasten securely after
the test.
■AND ....
• We recommend that you keep spare surge protectors so
that you can replace them when necessary.
• Lightning surge can enter not only through signal lines
but also through power supply lines. We recommend that
you also use the surge protectors for power line for suffi-
cient protection.
COMPONENT IDENTIFICATION
Ground Terminal (G)
(used as mounting bracket)
Base
Element is secured to Base
with screw when M-RESTER is
shipped from Factory.
M•RESTER
MADE IN JAPAN N1430B
Lot.NO
MODEL
Head Element
Specifications
MDP-PA
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8207 Rev.3 P. 2 / 3
INSTALLATION
In order to separate the head element from the base, loosen the screw located at the left-center of the element.
■WALL MOUNTING
Refer to the drawings below.
• EXTERNAL DIMENSIONS unit: mm (inch)
B
C
23
A
1
31.5 (1.24)
2–5 (.20) dia.
MTG HOLE
6–M4 SCREW
GROUND TERMINAL (G)
(used as mounting bracket)
27 (1.06)53 (2.08)
80 (3.15)
45 (1.77)
HEAD ELEMENT
BASE
80 (3.15)
90 (3.54)
100 (3.94)
33 (1.30) min. 2–M4 SCREW
90 (3.54)
• MOUNTING REQUIREMENTS
unit: mm (inch)
■DIN RAIL MOUNTING (Only for /A33)
1. MOUNTING ONTO THE ADAPTOR
Before DIN rail mounting, secure the mounting bracket of
MDP to the mounting adaptor with a screw provided with
this product. In this step, secure at one point.
M•RESTER
2. DIN RAIL MOUNTING
Set the base socket so that its mounting slider is at the bot-
tom. Position the upper hook at the rear side of base socket
on the DIN rail and push in the lower. When removing the
socket, push down the mounting slider utilizing a minus
screwdriver and pull.
DIN Rail Mounting Slider
35 mm wide
DIN Rail
3. GROUNDING
Secure the mounting bracket at the other point with the
other screw. In this step, secure the grounding wire togeth-
er with the screw.
M•RESTER
Solderless Terminal
• MOUNTING REQUIREMENTS unit: mm (inch)
8.5
(.33)
[3.3 (.13)]
DIN RAIL
35mm wide
80 (3.15)
45 (1.77)
4
(.18)
2–M4 MOUNTING SCREW
(used as ground terminal (G))
MDP-PA
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8207 Rev.3 P. 3 / 3
TERMINAL CONNECTION
Connect the unit as in the diagram below.
Be sure to cross-wire between the Ground terminal (G) and that of the protected equipment. When the surge protector is con-
nected with a device which has no ground terminal such like M-System’s (See figure below), ground the M-RESTER Ground
terminal (G) only.
Protected DeviceMDP-PA
G
1
3
A
C
2
SHLD
G
+
–
B
PA
BUS
Grounding
≤100Ω
Cross wiring
*2
*1
*1. Cross wire to the surge protector’s G terminal when grounding the shield wire.
If the shield wire is not to be grounded, connect it to B terminal.
*2. Follow instructions provided with the protected device whether 2 terminal
should be connected or not. However, if the shield terminal of the protected
device is not isolated from PA BUS, DO NOT connect 2 terminal to the
protected device.
Protected
Devices
(Nodes)
MDP-PA
G G
G
G
MDP-PA
G G
G
Protected
Devices
(Nodes)
When the distance between nodes are relatively long (e.g. grouped and separated by cabinets),
install the MDP-PA by each group of devices. Insert the MDP-PA at the surge side of the network.
For detailed information on the network, refer to that provided by PROFIBUS International or
Fieldbus Foundation.
*1. Fieldbus devices complying with IEC 61158-2 operate by a supply voltage between
9V and 32V DC.
Take the MDP-PA’s internal series resistance into consideration when determining the
cable distance if there is a large current flow on the bus line.
Crossover Wire
Crossover Wire
*1
■GROUNDING
M-RESTER PROTECTED
EQUIPMENT
G
G
CROSSOVER WIRE
GROUNDING
(100 ohms or less)
A crossover wire between M-RESTER ground and the ground or
metallic housing of the equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
When the M-RESTER is mounted with DIN Rail Mounting Adapter,
connect the grounding wire to the mounting screw of the M-RESTER.
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
MAINTENANCE
Check surge protectors periodically. Many cases of light-
ning are ignored, and even lightning at a far distance often
causes inductive surges.
We recommend that you check your surge protector about
twice a year, before and after the rainy season. Check
whenever you experience a strong lightning occurrence.
Checking procedure is explained in the following:
■CHECKING
WIRING
1) Make sure that wiring is done as instructed in the con-
nection diagram.
2) Make sure that the Ground terminal (G) is connected to
the metallic housing of protected equipment.
3) Make sure that the Ground terminal (G) is grounded to
earth.
DISCHARGE FUNCTION
The M-RESTER Tester is available for a preliminary check-
ing of the surge protector’s head element.
Approximate testing procedure without using the Tester is
explained as below.
1) Remove all wiring connected to the surge protector when
you test the element module.
2) Check resistance across the following terminals on the
high resistance range of multimeter and confirm no con-
duction. The meter shows ≥10MΩ.
Terminals (A) – (G), (B) – (G), (C) – (G)
3) Check that discharging occurs across the same terminals
with a 500V DC 1000MΩ insulation tester (The tester
shows ≤ 20MΩ).
If any of the above tests shows negative, replace the pro-
tector.

Other M-system Surge Protector manuals

M-system MDA-TL User manual

M-system

M-system MDA-TL User manual

M-system MD7G User manual

M-system

M-system MD7G User manual

M-system MDCAT 5E User manual

M-system

M-system MDCAT 5E User manual

M-system MDP-SP User manual

M-system

M-system MDP-SP User manual

M-system MD-LC2 Service manual

M-system

M-system MD-LC2 Service manual

M-system MDP-D Series User manual

M-system

M-system MDP-D Series User manual

M-system MMAH Series User manual

M-system

M-system MMAH Series User manual

M-system MD74R User manual

M-system

M-system MD74R User manual

M-system MDCAT-SPE-A User manual

M-system

M-system MDCAT-SPE-A User manual

M-system MMA User manual

M-system

M-system MMA User manual

M-system MDP-100T User manual

M-system

M-system MDP-100T User manual

M-system MDP-RB User manual

M-system

M-system MDP-RB User manual

M-system MDP-24-1 User manual

M-system

M-system MDP-24-1 User manual

M-system MD73W User manual

M-system

M-system MD73W User manual

M-system MD6 24 Series User manual

M-system

M-system MD6 24 Series User manual

M-system MDK-24 User manual

M-system

M-system MDK-24 User manual

M-system MA-100 User manual

M-system

M-system MA-100 User manual

M-system MMAJ User manual

M-system

M-system MMAJ User manual

M-system MDP-65T User manual

M-system

M-system MDP-65T User manual

M-system MD7JS User manual

M-system

M-system MD7JS User manual

M-system MDP-JS User manual

M-system

M-system MDP-JS User manual

M-system MD7FB User manual

M-system

M-system MD7FB User manual

M-system MATP User manual

M-system

M-system MATP User manual

M-system MD7LWA User manual

M-system

M-system MD7LWA User manual

Popular Surge Protector manuals by other brands

ENFORCER IPV-P188Q manual

ENFORCER

ENFORCER IPV-P188Q manual

RCA SCP60 Specifications

RCA

RCA SCP60 Specifications

TRC Surge Guard 34850 troubleshooting guide

TRC

TRC Surge Guard 34850 troubleshooting guide

CyberPower 649532010301 Specification sheet

CyberPower

CyberPower 649532010301 Specification sheet

Patton electronics 501LC user manual

Patton electronics

Patton electronics 501LC user manual

Rocket Fish RF-PCS12ES13 Guía De Instalación Rápida

Rocket Fish

Rocket Fish RF-PCS12ES13 Guía De Instalación Rápida

ABB OVRHT3D Installation, operation and maintenance manual

ABB

ABB OVRHT3D Installation, operation and maintenance manual

Speco SPTVIVP user manual

Speco

Speco SPTVIVP user manual

Davis Instruments Surge Protector install guide

Davis Instruments

Davis Instruments Surge Protector install guide

Davis Instruments Surge Protector install guide

Davis Instruments

Davis Instruments Surge Protector install guide

Mersen Surge-Trap ST-50 Series installation instructions

Mersen

Mersen Surge-Trap ST-50 Series installation instructions

Eufficio Innera Molla installation instructions

Eufficio

Eufficio Innera Molla installation instructions

Panamax SP8 installation instructions

Panamax

Panamax SP8 installation instructions

CyberPower B602RC1 user manual

CyberPower

CyberPower B602RC1 user manual

Tyco Frostex 9800 Installation instructions and user guide

Tyco

Tyco Frostex 9800 Installation instructions and user guide

Real-El RS-8F USB Charge user manual

Real-El

Real-El RS-8F USB Charge user manual

360 electrical Revolve45 user guide

360 electrical

360 electrical Revolve45 user guide

ATOMI AT1089 user manual

ATOMI

ATOMI AT1089 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.