  9. M-system W5PA User manual

M-system W5PA User manual

Other M-system Transmitter manuals

M-system Mini-M M2EXR User manual

M-system

M-system Mini-M M2EXR User manual

M-system W5MS User manual

M-system

M-system W5MS User manual

M-system M5PT User manual

M-system

M-system M5PT User manual

M-system W2CA User manual

M-system

M-system W2CA User manual

M-system 10JM User manual

M-system

M-system 10JM User manual

M-system M3LR User manual

M-system

M-system M3LR User manual

M-system 10TS User manual

M-system

M-system 10TS User manual

M-system M5XTR User manual

M-system

M-system M5XTR User manual

M-system M5VF User manual

M-system

M-system M5VF User manual

M-system 10TG User manual

M-system

M-system 10TG User manual

M-system Mini-M M2VF User manual

M-system

M-system Mini-M M2VF User manual

M-system 10VS4 User manual

M-system

M-system 10VS4 User manual

M-system F2RS User manual

M-system

M-system F2RS User manual

M-system LC2 User manual

M-system

M-system LC2 User manual

M-system JR User manual

M-system

M-system JR User manual

M-system W2AC User manual

M-system

M-system W2AC User manual

M-system M2EXV User manual

M-system

M-system M2EXV User manual

M-system M5PA-CA-R User manual

M-system

M-system M5PA-CA-R User manual

M-system MLV User manual

M-system

M-system MLV User manual

M-system Mini-M M2SP User manual

M-system

M-system Mini-M M2SP User manual

M-system M6DXU User manual

M-system

M-system M6DXU User manual

M-system M2EXV User manual

M-system

M-system M2EXV User manual

M-system Mini-M M2XR2 User manual

M-system

M-system Mini-M M2XR2 User manual

M-system M5XV User manual

M-system

M-system M5XV User manual

Popular Transmitter manuals by other brands

NIVELCO EasyTREK SCA-300 Series Programming manual

NIVELCO

NIVELCO EasyTREK SCA-300 Series Programming manual

Honeywell 5816WMBR installation instructions

Honeywell

Honeywell 5816WMBR installation instructions

Kamstrup READy MTU Installation and operation guide

Kamstrup

Kamstrup READy MTU Installation and operation guide

Omega ZW Series user guide

Omega

Omega ZW Series user guide

ABB Field 264H Instructions for installation

ABB

ABB Field 264H Instructions for installation

Alinco DJ-V17T Service manual

Alinco

Alinco DJ-V17T Service manual

Dejero EnGo 3x manual

Dejero

Dejero EnGo 3x manual

Rosemount 4600 Reference manual

Rosemount

Rosemount 4600 Reference manual

Speaka Professional 2342740 operating instructions

Speaka Professional

Speaka Professional 2342740 operating instructions

trubomat GAB 1000 instruction manual

trubomat

trubomat GAB 1000 instruction manual

Teledyne Analytical Instruments LXT-380 instructions

Teledyne Analytical Instruments

Teledyne Analytical Instruments LXT-380 instructions

Rondish UT-11 quick start guide

Rondish

Rondish UT-11 quick start guide

MG 10JRE instruction manual

MG

MG 10JRE instruction manual

Burkert 8177 operating instructions

Burkert

Burkert 8177 operating instructions

Firetide HotPort 3203 Hardware installation guide

Firetide

Firetide HotPort 3203 Hardware installation guide

Tele Radio T9-02 User instructions

Tele Radio

Tele Radio T9-02 User instructions

Rotronic HygroFlex HF3 Series user guide

Rotronic

Rotronic HygroFlex HF3 Series user guide

Jamara FCX6 Pro Tel Instruction

Jamara

Jamara FCX6 Pro Tel Instruction

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8533 Rev.4 P. 1 / 3
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Signal conditioner ...............................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside a panel.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may affect
the protection level of this unit when it is integrated in a
panel system. The user may have to review the CE re-
quirements in regard to the whole system and employ ad-
ditional protective measures* to ensure the CE conformity.
* For example, installation of noise filters and clamp fil-
ters for the power source, input and output connected
to the unit, etc.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
85 – 264V AC rating: 85 – 264V, 47 – 66 Hz, approx. 6 – 8VA
24V DC rating: 24V ±10%, approx. 3W
11 – 27V DC rating: 11 – 27V, approx. 3W
110V DC rating: 85 – 150V, approx. 3W
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 0 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
• Install lightning surge protectors for those wires connect-
ed to remote locations. For 24V DC power supply line,
choose a surge protector with its maximum surge voltage
40V or less between lines. Recommended M-System mod-
el: MDP-D24.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
• Output 2
Span Adj.
Zero Adj.
• Output 1
Span Adj.
Zero Adj.
Body
Specifications
INSTALLATION
Set the unit so that its DIN rail adapter is at the bottom.
■MOUNTING THE UNIT ON A DIN RAIL
A)Hang the upper hook at the rear side of unit on the DIN
rail.
B)Push in the lower in keeping pressing the unit to the DIN
rail.
A
B
DIN Rail
■REMOVING THE UNIT
A)Push down the DIN rail adaptor using a minus screw-
driver.
B)Pull out the lower part of the unit.
C)Remove the upper part from the DIN rail.
C
A
B
Spring Loaded
DIN Rail Adaptor
FREQUENCY TRANSMITTER MODEL W5PA
W5PA
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8533 Rev.4 P. 2 / 3
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the front of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
54321
1110
9876
94 (3.70)
45 (1.77) 41 (1.61) [3.3 (.13)]
• When mounting, no extra space is needed between units.
DIN RAIL
35mm wide
5–M3.5 SCREW
7.4 (.29)
6–M3 SCREW
6 (.24)
3 (.12)
■CONNECTION DIAGRAM
Vsns
4
5
+
2.5kΩ
3
–
+5V
U(+)
V(–)
POWER
10
11
+
–
OUTPUT 1
6
7
+
–
8
9
OUTPUT 2
The section enclosed by broken line is only with
2nd output option.
DO NOT connect to the terminals 1 and 2.
4
5
3
+
–
+
SENSOR EXCITATION
INPUT
■ Open Collector or
Mechanical Contact
Input Connection Examples
■ Voltage Pulse
4
5
+
–
Vsns
3
WIRING INSTRUCTIONS
■M3 Screw (output, power input)
Torque: 0.8 N∙m
■M3.5 Screw (input)
Torque: 0.8 N∙m
W5PA
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8533 Rev.4 P. 3 / 3
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
10 – 11 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
5) Go through the same procedure for the output 2.
Calibration for the output 1 affects the output 2. Check
the output 2 whenever the output 1 is adjusted.
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.