EM-5133-B Rev1 P. 9 / 18
[01] Lockout Setting
Set Lock / Unlock of lockout setting.
SETTING VALUE DESCRIPTION INITIAL VALUE
Lock Lockout setting enable Lock
Unlock Lockout setting disable
Even when setting is ‘Lock’, it is available to move on to
each setting mode and confirm the setting value of each
setting parameter. In each setting parameter display, when
‘Lock’, ‘DATA (Locked)’ is indicated, when ‘Unlock’, ‘DATA’
is indicated.
[11] Input range
Set the type of output signal
SETTING VALUE DESCRIPTION INITIAL VALUE
0 – 50 mA
Input: 0 – 50 mA DC
0 – 50 mA-1000 – +1000 mV
Input: -1000 – +1000 mV DC
-10 – +10 V
Input: -10 – +10 V DC
When input range is changed, turn the power off,and change
the connection to the input terminal of the unit. Input set-
ting value is changed to initial value.
[12] 0 % input setting
Set the 0 % input setting.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 50 mA 0.00 – 48.00 2.00 4.00
-1000 – +1000 mV -1000.0 – 900.0 100.0 -1000.0
-10 – +10 V -10.000 – 9.000 1.000 -10.000
Set as follows.
[12] 0 % input setting < [13] 100 % input setting
[13] 100 % input setting
Set the 100 % input setting.
Setting range differs according to input range.
INPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 50 mA 2.00 – 50.00 2.00 20.00
-1000 – +1000 mV -900.0 – 1000.0 100.0 1000.0
-10 – +10 V -9.000 – 10.000 1.000 10.000
Set as follows.
[12] 0 % input setting < [13] 100 % input setting
[14] 0 % input scaling
Set the display value of 0 % input setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 0.00
[15] 100 % input scaling
Set the display value of 100 % input setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 100.00
[16] Input decimal point
Set the decimal point position of [14] 0 % and [15] 100 %
input display scaling.
SETTING VALUE
DESCRIPTION INITIAL VALUE
oooooo Decimal point: None
2 places of
decimals
ooooo.o Number of decimal places: 1
oooo.oo Number of decimal places: 2
ooo.ooo Number of decimal places: 3
oo.oooo Number of decimal places: 4
o.ooooo Number of decimal places: 5
[17] Output range
Set the range of output signal of the unit.
SETTING VALUE DESCRIPTION INITIAL VALUE
0 – 20 mA Output: 0 – 20 mA DC
0 – 20 mA-5 – +5 V Output: -5 – +5 V DC
-10 – +10 V Output: -10 – +10 V DC
When output range is changed, turn the power off, and
then set the output setting DIP SW on the side of the unit.
Setting is as follows. Output setting value is changed to ini-
tial value.
OUTPUT
RANGE
SW1
12345678
0 – 20 mA OFF ON OFF OFF OFF OFF ON OFF
-5 – +5 V OFF OFF ON OFF ON OFF OFF ON
-10 – +10 V OFF OFF ON OFF OFF ON OFF ON
[18] 0 % output setting
Set the 0 % output setting.
OUTPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 20 mA 0.000 – 19.000 1.000 4.000
-5 – +5 V -5.000 – 4.750 0.250 -5.000
-10 – +10 V -10.000 – 9.000 1.000 -10.000
Set as follows.
[18] 0 % output setting < [19] 100 % output setting
The value is indicated by ‘OUTPUT’ at measuring mode.
[19] 100 % output setting
Set the 100 % output setting.
OUTPUT RANGE
SETTING RANGE
MIN. SPAN
INITIAL VALUE
0 – 20 mA 1.000 – 20.000 1.000 20.000
-5 – +5 V -4.750 – 5.000 0.250 5.000
-10 – +10 V -9.000 – 10.000 1.000 10.000
Set as follows.
[18] 0 % output setting < [19] 100 % output setting
The value is indicated by ‘OUTPUT’ at measuring mode.
[20] 0 % output scaling
Set the display value of [18] 0 % output setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 0.00
[21] 100 % output scaling
Set the display value of [19] 100 % output setting.
SETTING RANGE INITIAL VALUE
-99999 – 999999 100.00