Maple Systems OMI6900BP Series User manual

Your Industrial Control Solutions Source
_____________________
www.maplesystems.com
Maple Systems, Inc. | 808 134th St. SW, Suite 120, Everett, WA 98204 | 425.745.3229
OMI Operations Manual
OMI6900BP Light Industrial Panel PC
Series
For use with the following:
•OMI6900BP Series

Operations Manual: OMI6900BP Series 2
Operations Manual: OMI6900BP Series 2
TABLE OF CONTENTS
COPYRIGHT NOTICE......................................................................................................3
WARRANTY.....................................................................................................................3
TECHNICAL SUPPORT...................................................................................................3
UNPACKING THE UNIT ..................................................................................................3
SAFETY PRECAUTIONS ................................................................................................4
OVERVIEW OF OMI6900BP SERIES .............................................................................5
SPECIFICATIONS AND DIMENSIONAL OUTLINES .....................................................6
SPECIFICATIONS........................................................................................................6
OMI6912 DIMENSIONS ...............................................................................................8
OMI6915 DIMENSIONS ...............................................................................................9
OMI6916 DIMENSIONS .............................................................................................10
OMI6918 DIMENSIONS .............................................................................................11
OMI6921 DIMENSIONS .............................................................................................12
I/O PORTS......................................................................................................................13
COM1 and COM2:......................................................................................................13
LINE OUT: ..................................................................................................................13
USB: ...........................................................................................................................13
LAN1 AND LAN2: .......................................................................................................13
REMOTE POWER SWITCH CONNECTOR: .............................................................13
REMOTE POWER SWITCH CONFIGURATION OPTION ........................................14
VESA MOUNTING .........................................................................................................15
PANEL MOUNTING .......................................................................................................15
DRIVER INSTALLATION...............................................................................................16
WINDOWS OPERATING SYSTEM REINSTALLATION ...............................................16
BIOS CONFIGURATION OPTIONS ..............................................................................17
INTRODUCTION ........................................................................................................17
ENTERING SETUP ....................................................................................................17
SETTING COM1 FUNCTION .....................................................................................18
WINDOWS 10 IoT ENTERPRISE 2019 LTSC...............................................................19
WONDERWARE / AVEVA™ EDGE ..............................................................................19

Operations Manual: OMI6900BP Series 3
Operations Manual: OMI6900BP Series 3
COPYRIGHT NOTICE
This manual is a publication of Maple Systems, Inc., and is provided for use by its customers only. The contents of
the manual are copyrighted by Maple Systems, Inc.; reproduction in whole or in part, for use other than in support of
Maple Systems equipment, is prohibited without the specific written permission of Maple Systems.
WARRANTY
Warranty Statements are included with each unit at the time of purchase and are available at
www.maplesystems.com.
TECHNICAL SUPPORT
This manual is designed to provide the necessary information for trouble-free installation and operation of your new
OMI. However, if you need assistance, please contact Maple Systems:
•Phone: 425-745-3229
•Email: [email protected]
•Web: http://www.maplesystems.com
UNPACKING THE UNIT
Carefully unpack the OMI6900BP. Check all material in the container against the packing list. Maple Systems will not
accept responsibility for shortages against the packing list unless notified within 30 days. The equipment and
accessories were inspected and tested by Maple Systems before shipment.
Examine the equipment carefully; if any shipping damage is evident, notify the carrier immediately. Maple Systems is
not responsible for claim negotiations with the carrier.
Save the shipping container and packing material in case the equipment needs to be stored, returned to Maple
Systems, or transported for any reason.
Packing List
OMI6900BP Series Light Industrial Panel PC
DC Power Connector (3 pin terminal block)
DC Power adapter with cord
Mounting Clamp Kit
2-Pin Remote Power Switch connector
Support Disc
Windows Recovery Disc (for non-embedded operating systems only)

Operations Manual: OMI6900BP Series 4
Operations Manual: OMI6900BP Series 4
SAFETY PRECAUTIONS
Please observe the following precautions when installing the OMI6900BP Series Panel PCs. Failure to comply with
these restrictions could result in loss of life, serious personal injury, or equipment damage.
Warning: Disconnect this equipment from any power before cleaning. Do not use liquid or
spray detergents for cleaning. Use a damp cloth.
Warning: Keep this equipment away from humidity.
Warning: Before applying power to the unit make sure the voltage of the power source is
within the input voltage rating of the unit.
Warning: Position the power cord so that people cannot step on it. Do not place anything
over the power cord.
Warning: Never open the equipment and do not operate equipment with its back cover
removed- there are dangerous high voltages present inside. For safety reasons, the
equipment should be opened only by a qualified service technician.
Warning: This equipment generates, uses and can radiate radio frequency energy and if
not installed and used in accordance with the instruction manual, it may cause interference
to radio communications. It has been tested and found to comply with the limits for a Class
A computing device pursuant to FCC Rules, which are designed to provide reasonable
protection against such interference when operated in a commercial environment. Operation
of this equipment in a residential area is likely to cause interference in which case the user
at his own expense will be required to take whatever measures may be required to correct
the interference.
Warning: If any of the following situations arise, get the equipment checked by qualified
service personnel.
•The power cord or plug is damaged.
•Liquid has penetrated into the equipment.
•The equipment has been exposed to moisture.
•The equipment does not work well, or you cannot get it to work according to this manual.
•The equipment has been dropped and damaged.
•The equipment has obvious signs of breakage.
Warning: Do not leave this equipment in an uncontrolled environment where the storage
temperature is below -30°C (-22°F) or above 70°C (158°F). It may damage the equipment.

Operations Manual: OMI6900BP Series 5
Operations Manual: OMI6900BP Series 5
OVERVIEW OF OMI6900BP SERIES
The OMI6900BP Series is available in 12.1”, 15.1”, 15.6”, 18.5”, and 21.5” screen sizes. The OMI6900BP
is fanless and compact, and is powered by the 6th Generation Intel®Core™i5-6300U™2.4 GHz dual-core
processor with 1x 8GB DDR4 2133MHz SO-DIMM (Upgradable to 1x 16GB DDR4 2133MHz SO-DIMM)
The OMI6900BP series feature Projected Capacitive Touch Screens, which allow for a more natural,
intuitive user touch experience compared to traditional analog-resistive touch screen terminals. Benefits
of projected capacitive touchscreens include multi-touch response (pinch and zoom functionality) and
personal tablet-like operation. Finally, projected capacitive touchscreens do not require calibration.
Optional upgrades to the OMI6900BP Series (available at time of order) include 1x 16GB DDR4
2133MHz SO-DIMM RAM, as well as a wi-fi module. This module includes an internally mounted IEEE
802.11a/b/g/n/ac card as well as two antennas, allowing for wireless networking connectivity.
Front View of OMI6900BP Series
Rear View
(OMI6912BP shown)

Operations Manual: OMI6900BP Series 6
Operations Manual: OMI6900BP Series 6
SPECIFICATIONS AND DIMENSIONAL OUTLINES
The following section contains the Specifications and Dimensional Outlines for the OMI6900BP Series
Light Industrial Panel PCs.
SPECIFICATIONS
CPU
Intel®6th Gen Core™i5-6300U CPU processor
System Chipset
SoC
System
System Memory*
1x DDR4 260-pin SO-DIMM 8 GB 2133MHz
USB
2 x USB 3.0 type A
Serial
COM1: RS-232/422/485 DE-9P (default RS-232)
COM2: RS-232 DE-9P
Audio
1 x 3.5 mm line out
LAN
2 x GbE RJ-45
Power
3-pin connector header, DC power input
I/O Ports
Remote Power Switch
2-pin connector header
Expansion
Expansion Slot
Optional Wi-Fi kit (IEEE 802.11a/b/g/n/ac card and antenna)
Type
Projected Capacitive Touch
Interface
USB
Touch Screen
Light Transmission
80+%
Display Type
12.1” SVGA TFT LCD
15” XGA TFT LCD
15.6” HD TFT LCD
Max. Resolution
800 x 600
1024 x 768
1366 x 768
Max. Color
16.2 M
16.2 M
16.7 M
Luminance (cd/m²)
450
300
400
View Angle (H°/V°)
178/178
176/176
170/160
Contrast Ratio
1500:1
2000:1
500:1
Display
Backlight Lifetime
(hours)
50,000+
70,000+
50,000+
Solid State Drive Type
1 x 2.5” SATA 3, MLC
Solid State Drive
Capacity Options **
64, 128, 256, 512 GB SSD
Storage
SD Card Slot
N/A
Input Voltage
9~36 VDC
9~36 VDC
9~36 VDC
Input Current
1.31 ~ 5.22 A
1.14 ~ 4.56 A
1.25 ~ 5.0 A
Electrical
Input Power (max.)
47 W
41 W
45 W
Dimensions
(W x H x D)
12.56 x 9.65 x 2.04 inches
[319 x 245 x 51.7 mm]
16.14 x 12.20 x 2.15 inches
[410 x 310 x 54.7 mm]
16.22 x 10.94 x 2.32 inches
[412 x 278 x 59 mm]
Net Weight
~ 6.17 lbs [2.8 kg]
~ 9.70 lbs [4.4 kg]
~ 9.92 lbs [4.5 kg]
Panel Cutout
Dimensions (W x H)
11.93 x 9.02”
[303 x 229 mm]
15.43 x 11.50”
[392 x 292 mm]
15.51 x 10.24”
[394 x 260 mm]
Mounting
Panel mounting, VESA 100 x 100
Mechanical
Construction
Silver aluminum front bezel and chassis
Operating Temperature
32~122°F [0~50°C]
Storage Temperature
-22~158°F [-30~70°C]
Relative Humidity
10 to 90% @ 40°C, non-condensing
Rating
IP66 / NEMA 4 when panel mounted
Environmental
Certification
CE / FCC Class A / cULus / RoHS
Operating
System
Microsoft Windows
Options
Microsoft Windows© 10 IoT Enterprise Embedded 2019 LTSC 64-bit (EPKEA)
Microsoft Windows© 10 IoT Enterprise 2019 LTSC 64-bit (PKEA)
Notes
* 8GB RAM Standard; 16GB RAM option available; contact Maple Systems for details
** Additional SSD options available; contact Maple Systems for details.
Specifications subject to change without notice.

Operations Manual: OMI6900BP Series 7
Operations Manual: OMI6900BP Series 7
CPU
Intel®6th Gen Core™i5-6300U CPU processor
System Chipset
SoC
System
System Memory*
1x DDR4 260-pin SO-DIMM 8 GB 2133MHz
USB
2 x USB 3.0 type A
Serial
COM1: RS-232/422/485 DE-9P (default RS-232)
COM2: RS-232 DE-9P
Audio
1 x 3.5 mm line out
LAN
2 x GbE RJ-45
Power
3-pin connector header, DC power input
I/O Ports
Remote Power Switch
2-pin connector header
Expansion
Expansion Slot
Optional Wi-Fi kit (IEEE 802.11a/b/g/n/ac card and antenna)
Type
Projected Capacitive Touch
Interface
USB
Touch Screen
Light Transmission
80+%
Display Type
18.5” HD TFT LCD
21.5” FHD TFT LCD
Max. Resolution
1366 x 768
1920 x 1080
Max. Color
16.7 M
16.7 M
Luminance (cd/m²)
300
250
View Angle (H°/V°)
170/160
178/178
Contrast Ratio
1000:1
3000:1
Display
Backlight Lifetime
(hours)
50,000+
50,000+
Solid State Drive Type
1 x 2.5” SATA 3, MLC
Solid State Drive
Capacity Options **
64, 128, 256, 512 GB SSD
Storage
SD Card Slot
N/A
Input Voltage
9~36 VDC
9~36 VDC
Input Current
1.53 ~ 6.11 A
1.50 ~ 6.0 A
Electrical
Input Power (max.)
55 W
54 W
Dimensions
(W x H x D)
19.67 x 12.39 x 2.57 inches
[499.6 x 314.6 x 65.4 mm]
21.94 x 14.26 x 2.56 inches
[557.3 x 362.3 x 64.8 mm]
Net Weight
~ 13.23 lbs. [6 kg]
~ 16.53 lbs. [7.5 kg]
Panel Cutout
Dimensions (W x H)
18.98 x 11.69”
[482 x 297 mm]
21.22 x 13.54”
[539 x 344 mm]
Mounting
Panel mounting, VESA 100 x 100
Mechanical
Construction
Silver aluminum front bezel and chassis
Operating Temperature
32~122°F [0~50°C]
Storage Temperature
-22~158°F [-30~70°C]
Relative Humidity
10 to 90% @ 40°C, non-condensing
Rating
IP66 / NEMA 4 when panel mounted
Environmental
Certification
CE / FCC Class A / cULus / RoHS
Operating
System
Microsoft Windows
Options
Microsoft Windows© 10 IoT Enterprise Embedded 2019 LTSC 64-bit (EPKEA)
Microsoft Windows© 10 IoT Enterprise 2019 LTSC 64-bit (PKEA)
Notes
* 8GB RAM Standard; 16GB DDR4 RAM option available; contact Maple Systems for details
** Additional SSD options available; contact Maple Systems for details.
Specifications subject to change without notice.

Operations Manual: OMI6900BP Series 8
Operations Manual: OMI6900BP Series 8
OMI6912 DIMENSIONS
A
Power Connector
B
VESA 100 x 100 mm Screw Holes
C
Line Out
D
Remote Power Switch Connector
E
USB 3.0 Host Ports
F
Gigabit Ethernet Ports
G
DE9P COM Ports

Operations Manual: OMI6900BP Series 9
Operations Manual: OMI6900BP Series 9
OMI6915 DIMENSIONS
A
Power Connector
B
VESA 100 x 100 mm Screw Holes
C
Line Out
D
Remote Power Switch Connector
E
USB 3.0 Host Ports
F
Gigabit Ethernet Ports
G
DE9P COM Ports

Operations Manual: OMI6900BP Series 10
Operations Manual: OMI6900BP Series 10
OMI6916 DIMENSIONS
A
Power Connector
B
VESA 100 x 100 mm Screw Holes
C
Line Out
D
Remote Power Switch Connector
E
USB 3.0 Host Ports
F
Gigabit Ethernet Ports
G
DE9P COM Ports

Operations Manual: OMI6900BP Series 11
Operations Manual: OMI6900BP Series 11
OMI6918 DIMENSIONS
A
Power Connector
B
VESA 100 x 100 mm Screw Holes
C
Line Out
D
Remote Power Switch Connector
E
USB 3.0 Host Ports
F
Gigabit Ethernet Ports
G
DE9P COM Ports

Operations Manual: OMI6900BP Series 12
Operations Manual: OMI6900BP Series 12
OMI6921 DIMENSIONS
A
Power Connector
B
VESA 100 x 100 mm Screw Holes
C
Line Out
D
Remote Power Switch Connector
E
USB 3.0 Host Ports
F
Gigabit Ethernet Ports
G
DE9P COM Ports

Operations Manual: OMI6900BP Series 13
Operations Manual: OMI6900BP Series 13
I/O PORTS
COM1 and COM2:
Connector Type: DE9P male serial ports.
COM1*
COM2
Pin #
(RS-232 Default)
(RS422)
(RS485)
(RS232)
1
DCD
422_TX-
485-
DCD
2
RXD
422_TX+
485+
RXD
3
TXD
422_RX+
NC
TXD
4
DTR
422_RX-
NC
DTR
5
GND
GND
GND
GND
6
DSR
NC
NC
DSR
7
RTS
NC
NC
RTS
8
CTS
NC
NC
CTS
9
RI
NC
NC
RI
* Refer to “Setting COM1 Function” section to set the communication mode.
LINE OUT:
Connector Type: 3.5mm audio jack.
Line out HD Audio port can be connected to a speaker or headphones.
USB:
OMI6900BP models have 2 ea. USB 3.0 type A ports.
Note: USB 3.0 allows data transfers up to 5000 Mb/s,
full-speed, and low-speed signaling. The total USB current limit is 2.0A.
LAN1 AND LAN2:
Standard 10/100/1000M (Gigabit) RJ-45 Ethernet ports
LINK LED (green) and ACTIVE LED (green or orange)
located at the left-hand and right-hand side of the Ethernet port indicate the activity and
transmission state of the network.
REMOTE POWER SWITCH CONNECTOR:
Two-Position Connector Header, 2.5mm pitch.
OMI6900BP Series units include the matching connector plug.

Operations Manual: OMI6900BP Series 14
Operations Manual: OMI6900BP Series 14
REMOTE POWER SWITCH CONFIGURATION OPTION
By default, your OMI6900BP Series unit is configured to boot up automatically upon application of power,
with no configuration changes necessary. In the event that DC power is lost, the unit will automatically
boot up again once DC power is restored.
If you wish to control the unit’s on/off status via a Remote Power Switch, simply connect a normally open
momentary-type switch wired to the included 2-pin connector. The connector plug accepts min. 28AWG
and max. 20AWG solid or stranded wire connection, with push-type insertion.
When the unit is powered, pressing the switch will perform a proper Windows shut down. If the DC power
supply to the OMI6900BP Series is still providing power, simply press your power switch again to boot your
OMI6900BP Series unit. When the unit is properly shut down, then it is safe to remove DC power. When
DC power is provided to the OMI6900BP Series once again, the unit will automatically boot.
Warning: Maple Systems does not recommend shutting down the
OMI6900BP Series by cutting DC power to the unit.
Always perform a Windows Shut Down procedure when you wish to turn the unit off.
Cutting DC power to the OMI6900BP Series can corrupt the Windows Operating System,
or other software or hardware components of your OMI. Damage caused by improper
application or removal of power may not be covered under the OMI6900BP Series
Warranty.

Operations Manual: OMI6900BP Series 15
Operations Manual: OMI6900BP Series 15
VESA MOUNTING
The OMI6900BP Series offer VESA mounting as an option. VESA 100 x 100mm threaded inserts are
located on the rear of the unit. Use the M4 threaded mounting screws included with the VESA mounting
hardware to mount the OMI6900BP as illustrated in the figure below.
Use VESA mounting hardware suitable for your intended application; Maple Systems is not responsible
for damage to unit, mounting surface, or to other components, caused by improper mounting.
PANEL MOUNTING
In addition to VESA mounting, your OMI6900BP Series can be mounted in a panel using the mounting
holes located on the sides and top of the unit. Use the included clamps to fasten your OMI6900BP Series
unit to a panel, cut out to the proper dimensions on the datasheet corresponding to your display size.
Tighten the panel bolts with a torque force between 7 ~ 8.5 inch/lbs. to ensure an adequate seal. Torque
values outside this range may negate NEMA or IP rating, or cause damage to the unit or panel.
Maple Systems is not responsible for damage to unit, mounting surface, or to other components caused
by improper mounting.
Note: The image above is a representative image of the panel mounting process; your specific
OMI6900BP Series unit may differ in appearance, but mounting is functionally similar.

Operations Manual: OMI6900BP Series 16
Operations Manual: OMI6900BP Series 16
DRIVER INSTALLATION
Your OMI6900BP series comes with all necessary drivers pre-installed. As such, driver installation is not
normally needed. However, there may be times when a driver requires re-installation. Use the Support
DVD that came with your unit to install all non-Windows Operating System Drivers. If you no longer have
your Support DVD, visit the Support Center of the Maple Systems website for driver download.
Equipment required:
•OMI6000 Support DVD
•USB External DVD drive
Instructions:
•Plug in the USB external DVD drive into one of the USB ports.
•Load the support DVD into the external drive.
•Access the OMI6000 support DVD and open the OMI6900BP folder.
•Open the folder corresponding to the driver you want to install / reinstall.
•Double-click the application (setup.exe) file to begin driver installation.
•Follow the instructional prompts on the screen.
•We recommend that you restart your computer when prompted, and after completion of all driver
installations.
WINDOWS OPERATING SYSTEM REINSTALLATION
In the unlikely event of a system failure requiring reinstallation of the Windows Operating System, use the
OS Recovery DVD (enclosed with Non-Embedded Operating Systems only) to reinstall Windows as it
arrived to you from Maple Systems. You will need to re-activate Windows using the Product Key located
on the rear panel of your unit, adjacent to the product label.
In the event that you wish to update your Windows Operating System (Non-Embedded Operating
Systems only), simply connect the OMI6900BP Series unit to the Internet and run the Windows Update
utility.
Embedded Operating Systems do not come with an OS Recovery DVD. In the extremely unlikely event
the Windows OS needs to be reinstalled, contact your Maple Systems Sales Engineer for instructions.

Operations Manual: OMI6900BP Series 17
Operations Manual: OMI6900BP Series 17
BIOS CONFIGURATION OPTIONS
INTRODUCTION
The BIOS (Basic Input/Output System) installed in the ROM of your OMI6900BP Series supports Intel®
processors. The BIOS provides critical low-level support for standard devices such as disk drives and
serial ports. The BIOS also provides a Setup utility program that allows the user to specify system
configuration and setting options.
Warning: Changing settings or configurations within the BIOS of your
OMI6900BP can adversely impact the operation of your unit if incorrectly
performed.
Maple Systems provides the below instructions solely for the operations specified, and
is not responsible for improper unit operation caused by changing settings or entries
other than those explicitly listed below.
ENTERING SETUP
When the system is powered on, the BIOS will enter the Power-On Self Test (POST) routines
and the following message will appear on the screen:
Example of initial POST screen. Your POST screen may appear different.
Press the <Delete> key immediately during the POST portion of your PC’s bootup sequence to enter the
BIOS. The Main Menu containing the system summary information will appear.

Operations Manual: OMI6900BP Series 18
Operations Manual: OMI6900BP Series 18
SETTING COM1 FUNCTION
The OMI6900BP Series Serial Ports are configured by default as RS232, but COM1 can be configured for
RS422 (4-wire) or RS485 (2-wire) operation if so desired. Port configuration is managed through the
BIOS; see the below table for instructions on changing COM1 port mode.
Note: COM1 is the only port that can be configured for RS422 or RS485 operation; COM2 is
exclusively configured for RS232 operation.
BIOS COM1 Configuration
1. Enter the BIOS Setup Utility
by pressing [Delete] key
during POST.
The Main menu containing
the system summary
information will appear.
2. Set COM1 communication
mode as follows:
•Advanced Tab
•NCT6106D Super IO
Configuration
•Serial Port 1 Configuration
•F75111 COM1 Config:
oRS-232 mode
oRS-485 mode
oRS-422 mode
➢Save and Exit to restart

Operations Manual: OMI6900BP Series 19
Operations Manual: OMI6900BP Series 19
WINDOWS 10 IoT ENTERPRISE 2019 LTSC
Windows 10 IoT Enterprise LTSC is a full Professional version of Windows 10, available on all
OMI6900BP models. This powerful operating system delivers enterprise manageability and security to
IoT solutions. Additionally, all the features and functionality that customers expect to find on their desktop
PC are available in this version. The Long Term Servicing Channel (LTSC) version ensures long term
stability that critical production systems require by updating only necessary operating system
components, with significantly fewer update interruptions.
Included Apps:
•Microsoft Edge Web Browser
•LibreOffice Suite (Compatible with the following document types:)
oMS Word
oMS Excel
oMS PowerPoint
oAdobe PDF
•Media Player
WONDERWARE / AVEVA™ EDGE
All the OMI6900BP series Panel PCs are compatible with Wonderware / AVEVA™ Edge SCADA
software package. The choice of operating system will determine the target platform and runtime license
required as shown in the chart below:
Operating System
Runtime License*
Target Platform
Windows 10 IoT Enterprise
…for Embedded view..for Windows Embedded
Windows
* There are multiple options for each operating system indicated by “…” in the chart above. Refer to the
AVEVA™Edge price list for details.
For Windows 10 IoT Enterprise LTSC, install the Embedded View runtime by copying CEServer.exe from
your C:\Program Files (x86)\InduSoft Web Studio v8.1\Redist\WinEmbedded\Bin to the PC system files.

1010-1115 Rev 00
Maple Systems, Inc. | 808 134th St. SW, Suite 120, Everett, WA 98204 | 425.745.3229
Your Industrial Control Solutions Source
_____________________
www.maplesystems.com
Table of contents
Other Maple Systems Touch Panel manuals

Maple Systems
Maple Systems PC100 Series User manual

Maple Systems
Maple Systems Silver Plus Series User manual

Maple Systems
Maple Systems HMC7070A-M User manual

Maple Systems
Maple Systems OMI6912A User manual

Maple Systems
Maple Systems HMC7043A-M User manual

Maple Systems
Maple Systems Ivory Series User manual

Maple Systems
Maple Systems OMI6800 Series User manual

Maple Systems
Maple Systems PC2315A User manual

Maple Systems
Maple Systems HMC4101A-M Series User manual