Matelec FSA-60000 User manual

MATELEC AUSTRALIA. P 1800 281 282. F 1300 281 282
INFO@MATELECAUSTRALIA.COM.AU. WWW.MATELECAUSTRALIA.COM.AU
• This product must only be used for the purpose described in these instructions and must be installed in
accordance with local wiring rules and regulations.
Main Power Source 220-240 V AC/50 Hz
Secondary Power Source DC 3V battery: CR17450
AC Operating Current <100mA
Interconnecting Max. 24 alarms (wired 150m maximum)
Operating Temperature 0 °C to 40 °C
Ambient Humidity ≤ 93%
Alarm Sensitivity 0.118-0.169 dB/m
Alarm Volume ≥ 85dB(A) @ 3m
Sound Pattern ISO8201(BI 0.5s - pause 0.5s- BI 0.5s - pause
0.5s - BI 0.5s - pause 1.5s, with the RED LED
ashing, repeat this alarm pattern)
Complies with AS3786:2014
THIS SMOKE ALARM MUST BE INSTALLED BY A LICENSED ELECTRICIAN IN ACCORDANCE
WITH AUSTRALIAN WIRING RULES
SMOKE ALARM FSA-60000
240Vac c/w 3V DC Battery Backup Photoelectric Smoke Alarm
TM
A
C
T
I
V
F
I
R
E
D
E
T
S
I
L
Compatible
with the FSA-50000
Wireless Interconnect
module
*Sold Separately.

MATELEC AUSTRALIA. P 1800 281 282. F 1300 281 282
INFO@MATELECAUSTRALIA.COM.AU. WWW.MATELECAUSTRALIA.COM.AU
1. Kitchens or garages
2. Any area subjected to relative humidity outside the range of 10%-93%, for example bathrooms
3. Any area where the temperature may fall below 0°C or exceed 40°C.
4. Within 1m of any heating or cooling vents
5. In any bug or insect infested area
6. In areas of excess dust
7. Near uorescent lights – electronic ‘noise’ may cause nuisance alarming
AVOID THESE LOCATIONS
4”
(10cm)
Minimum
20”
(50cm)
Minimum
12”
(30.5cm)
Minimum
CEILING
SIDE
WALL
NOT IN
THIS AREA
ACCEPTABLE HERE
BEST HERE
DIAGRAM 1
50cm NOT
IN THIS
AREA
DIAGRAM 2
DO NOT INSTALL
100cm
ANYWHERE IN
THIS AREA
DEAD AIR
1. Smoke alarms must be installed in accordance with local and national regulations.
Please check your State Fire Department requirements prior to installation.
2. As a minimum, smoke alarms should be located between sleeping areas and potential
sources of re such as a kitchen, heater or basement. In single story homes with one sleeping
area, an alarm should be installed in the hallway outside the room. In single story homes with two
or more sleeping areas, a minimum one alarm for each area is required. In multilevel dwellings,
an alarm should be installed outside and inside each sleeping area, in the basement, and on
every level of the home.
3. Smoke alarms are best installed as close to the centre of the ceiling as possible. As a minimum,
the alarms should be located at least 30cm from walls. If wall mounted, it should be at least 30cm
from the ceiling. (Diagram 1.)
4. Larger rooms, in excess of 10m in length, should have multiple alarms installed.
5. For buildings with a peaked, or cathedral type ceiling, the alarm musty be installed at least 50cm
from the apex. (Diagram 2.)
6. Do not mount the alarm on an external wall of a mobile home, as they may be subjected to
excessive heat.
RECOMMENDED LOCATIONS FOR SMOKE ALARMS
SUGGESTED SMOKE ALARM LOCATIONS

MATELEC AUSTRALIA. P 1800 281 282. F 1300 281 282
INFO@MATELECAUSTRALIA.COM.AU. WWW.MATELECAUSTRALIA.COM.AU
1. Isolate Mains/AC power.
2. Select optimum location for your smoke alarm/s as per earlier details.
3. Press the base on the installation position, mark installation holes of the bracket.
4. Bore two 5mm holes on the markings and install mounting plugs. (See Diagram A)
5. Follow wiring details as per Diagram D.
6. Attach the base to the mounting plugs and x screws into the plugs.(See Diagram B)
7. Close the alarm body. (See Diagram C)
MOUNTING INSTRUCTIONS
Plastic plugs
Holes
Screws
Diagram A
Diagram B
Diagram DDiagram C
Installation sketch
Wiring Instructions:
TERMINAL:
L : Active wire
N : Neutral wire
I/O : Interconnect wire
(when applicable)
E/LOOP : No wire
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
220-240V a.c.
Active (A)
Neutral (N)
TERMINAL
I-Connect : Interconnection
N : Neutral
E-Loop : No wiring
A : Active

MATELEC AUSTRALIA. P 1800 281 282. F 1300 281 282
INFO@MATELECAUSTRALIA.COM.AU. WWW.MATELECAUSTRALIA.COM.AU
• All interconnected alarms must be connected to the same sub/circuit
• A common Neutral must be used for interconnect to function
• Do not connect the interconnect wires to Active or Neutral
Status Description
Status Indication Description
Standby status The Red LED ashes every 40
seconds, with no Green LED.
Operating under battery power
only.
AC power indication The Green LED is continuously
illuminated
The unit is operating under AC
power.
Low battery warning The unit chirps, with Red LED ash-
ing every 40 seconds.
Battery voltage is low – replace
battery
Self-test fault warning The Red LED ashes twice every
40 seconds.
The buzzer fault or buzzer
detection circuit fault.
End-of-life warning The unit chirps between the Red
LED ashing twice
The unit will send end-of-life warn-
ing after 10 years of operation.
Alarm must be replaced.
Test function The Red LED ashes once every
second, with alarm sounding until
the TEST button is released.
• Test by pressing the TEST button
on the smoke alarm for at least 5
seconds.
• The alarm will sound if all elec-
tronic circuitry, buzzer and battery
are working properly.
Silence function The Red LED ashes every 8
seconds.
• This smoke alarm has a built-in
Silence feature.
• If cooking or other
non-hazardous sources cause
the alarm to sound, it can be
temporarily silenced by pressing
the HUSH button for a minimum 2
seconds.
• The alarm enters silence mode
for 10 minutes.
• After the 10-minute dormant
period, the smoke alarm will
resume normal operation
Interconnection alarm Alarm sounds without Red LED
ashing.
Occurs when another
interconnected alarm is triggered.

MATELEC AUSTRALIA. P 1800 281 282. F 1300 281 282
INFO@MATELECAUSTRALIA.COM.AU. WWW.MATELECAUSTRALIA.COM.AU
Trouble Shooting
Problem Cause and Remedy
The Green LED does not light
when AC power supplied
• Check the AC line is properly connected to the smoke alarm.
• Ensure that the AC power is turned on.
The Red LED does not ash every
40s
• Ensure that the battery and the AC power are properly connected.
Smoke alarm does not sound
when tested
• Ensure that the battery and the AC power are properly connected.
• Clean the smoke alarm.Then take out the battery and turn off the
AC power. Install battery and turn on the AC power after 3 minutes.
Low battery warning • Ensure that the battery is properly connected.
• Replace a ash battery, refer to “Replace Battery” section.
Fault warning • Clean smoke alarm.Take out the battery and turn off the AC power.
Wait 3 minutes, then install battery and turn on the AC power.
Self-test fault warning • Press the TEST button at least 15s, then release.
False alarm • Press the HUSH button to silence it.
• Clean smoke alarm device.
• Move the smoke alarm device to new location.
The alarm sounds different from it
is used to
• Ensure that the battery is not low voltage.
• Clean smoke alarm.Take out the battery and turn off the AC power.
Wait for 3 minutes, then install battery and turn on the AC power.
The alarm can’t interconnection
alarm
• Check the Active, Neutral, Interconnection wires are properly
connected.
• Check the interconnected smoke alarm are supplied from the same
circuit.
If the problem still exists, please return to your retailers.
If the unit is out of warranty, please replace another new alarm.
Note: If self-test fault warning is existing, but the product can sound alarm when press
test button.The product can continue to be used. Need to test weekly by press the test
button instead of self-test weekly.

MATELEC AUSTRALIA. P 1800 281 282. F 1300 281 282
INFO@MATELECAUSTRALIA.COM.AU. WWW.MATELECAUSTRALIA.COM.AU
INSTALLING THE FSA-50000 MODULE AND UTILISING WIRELESS INTERCONNECT
(If applicable)
The FSA-50000 Wireless Module has been developed exclusively for the MATelec FSA-60000 and FSA-30000
Smoke Alarms.This enables both wired and wireless smoke detectors to be utilised in one installation.The
FSA-60000 Smoke Detector is supplied separate to the FSA-50000 Module. Please contact your dealer for all
enquiries.The FSA-60000 comes without the module installed. Only install the module if the alarm is being
interconnected. If multiple units are being wire interconnected, then only 1 module per group of wired
alarms should be installed.
1. Isolate Mains/AC power.
2. Select optimum location for your smoke alarm as per earlier details.
3. Remove the ‘blank module’ from the smoke alarm.
4. Insert the FSA-50000 Wireless Module in slot provided.
5. Insert the battery and close the alarm.The alarm will automatically search for the module after
being closed.The red LED ashes continuously while the unit checks if the module is installed.
6. If no other alarms are found to pair with, the red LED will extinguish after 8 seconds, and unit
will beep 3 times in quick succession.The red LED will then ash twice quickly, every 8 seconds.This
indicates that while the module has been recognized, the unit is not yet paired.
7. If module was not installed correctly, or otherwise not recognized by the alarm, the red LED will
extinguish after 8 seconds, no beeps will be heard, and the red LED will not ash twice every 8
seconds.
8. Repeat these steps with all alarms to be interconnected.
PAIRING THE ALARM
9. Press the TEST button of the rst alarm 3 times in the space of 2 seconds.The Red LED should re
main illuminated.This alarm remains the Master.
10. Move to the next alarm and press the TEST button of this alarm 3 times in the space of 2 seconds.
The red LED will illuminate briey, and the unit will give one loud 0.5 second beep.The unit is now
paired.
11. Repeat this process with all remaining alarms to be paired.
12. Return to the Master (rst) alarm.The Red LED should still be illuminated. Press the TEST button for 1
second, to complete pairing.
13. All paired units will have the red light ashing once every 40 seconds.
14. Turn ON Main power
15. To test the alarms, press the TEST button for at least 2 seconds.The unit will alarm, and the light will
ash as long as TEST button is pressed.
16. All other interconnected alarms should go through their test cycle, with a series of beeps, within a
few seconds
DFSA-50000 module

MATELEC AUSTRALIA. P 1800 281 282. F 1300 281 282
INFO@MATELECAUSTRALIA.COM.AU. WWW.MATELECAUSTRALIA.COM.AU
The battery of alarms wirelessly interconnected should be replaced at a maximum, every 10 years.
CLEAR NETWORK
If it becomes necessary to unpair an alarm from a network, the following steps should be undertaken:
1. Isolate Power and Remove the battery from the alarm.
2. Press and hold the TEST button and reinsert the battery while the button is still pressed.The red LED
will illuminate for 3 seconds.
3. Release the TEST button, after Red LED goes off.
4. The Red LED should light up again.
5. Press the TEST button again, within 2 seconds, while the Red LED is illuminated, and release
6. The alarm will beep once, and the red LED goes out.The alarm is now unpaired.
DEVELOP AN ESCAPE PLAN
As part of your plan, all family members should know and/or practice:
1. The two quickest ways out of each room
2. How to exit from upstairs, for homes with a second story. A rope or chain may be required.
3. An agreed upon meeting place outside, such as the letterbox
4. The sound of the smoke alarm and practice leaving your home when they hear it.
5. A re drill at least every six months including drills at nights. Practice allows you to test your plan
before an emergency.You may not be able to reach your children. It is important that they know
what to do!
WHAT TO DO IF THE ALARM SOUNDS
1. Alert any small children and elderly persons.
2. Leave immediately by your plan of escape. Every second counts, so don’t waste time getting
dressed or picking up valuables.
3. In leaving, don’t open any inside door without rst feeling its surface. If hot, or if you see smoke
seeping through cracks, don’t open that door! Instead, use your alternate exit. If inside door is cool,
place your shoulder against it, open it slightly and be ready to slam it shut if heat and smoke
rush in.
4. Stay close to the oor if air is smoky. Breathe shallowly through a wet cloth if possible.
5. Once outside, go to your selected meeting place and make sure everyone is there.
6. Call the Fire Brigade on 000.
7. Don’t return to your home until ofcials say that it is safe to do so. For further information on re
safety contact your local Fire Brigade.
SERVICE AND WARRANTY
• The FSA-60000 smoke alarm is warranted for a period of 5 years, to be free of defects in materials
or workmanship, under normal use. In the event of a warranty issue, please contact your place of
purchase.
Please see the warranty card included with the smoke alarm package, for full details of the
warranty.
Table of contents
Other Matelec Smoke Alarm manuals
Popular Smoke Alarm manuals by other brands

Polon-Alfa
Polon-Alfa DOT?4046 Installation and maintenance manual

Dometic
Dometic FA25 Installation and operating manual

bolid
bolid S2000-IPDL installation manual

Safetec
Safetec SDS-2/6 Additional Fault Finding Instructions

Firex
Firex I240C user manual

Autronica
Autronica AutroSense Micra 25 Installation handbook