1
08/03/2018
SafeAir CM (GP)
Installation Instructions
The SafeAir CM (GP) is a ventilation interlock and gas pressure proving system with gas detection
The system will ensure that any mechanical ventilation connected (supply and/or extract) is running before
the gas can be used, when installed with gas sensors it will also monitor the atmosphere for CO and/or CO2
It will then continually monitor for fan operation
The system will also ensure there are no gas leaks downstream of the control valve at switch on by way of a
downstream integrity check, it continually checks that the incoming gas pressure is sufficient
Before commencing installation please familiarise yourself to the equipment by reading the comprehensive
installation instructions If in doubt then please call 0161 233 0600 Out of hours please call 07894 684080 or
07843 355163
It is a statutory requirement that this safety system is installed and commissioned
to the satisfaction of the manufacturer.
A commissioning certificate must be issued to the end user along with instructions for the operation of the
equipment
As the Manufacturer Medem UK should commission this safety system whereupon a commissioning report
will be forwarded to the installing agent who should provide a copy to the end user
At the point of our commissioning an individual serial number will be attached to the system along with a 24
help line number Photos and all relevant information for the installation will then be stored on the Medem
site database to be accessed in the event of a call on the 24 hour help line The warranty period for the
panel and sender unit will then be extended to Ten years
• Gas Pressure proving
• Gas Detection (up to 4 detectors )
• Built in Fan Current Monitor for Fan interlocking
• 5 year warranty - 10 years when commissioned
SafeAir CM (GP) features
2
08/03/2018
System description
SafeAir CM (GP)
System On/Off
Gas Pressure Proving and Ventilation Interlock System For Kitchens
The SafeAir CM (GP) is a Ventilation Interlock and Gas Pressure Proving system with inbuilt two channel current monitor The
system will ensure that any mechanical ventilation connected (supply or extract) is running before the gas can be used When
installed with Medem gas detectors it will also monitor the atmosphere for CO (Carbon Monoxide) and/or CO2 (Carbon Dioxide)
The system will also ensure there are no gas leaks downstream of the control valve at switch on by way of a downstream
integrity check, It continually checks that the incoming gas pressure is sufficient
The system comprises of a mains powered panel capable of operating up to four sensors and internal two channel current
monitor for interlocking the mechanical ventilation with a monitoring range of 30 mAmps to 24 Amps
The ventilation can also be interlocked by mechanical air flow switches (DP) if required
Control Panel
The front of the panel has the following controls and indications:
Emergency stop button
System On/Off switch
Detectors button - For viewing detector status
Mute
LCD display:
For displaying system status during both installation and normal use, also for displaying diagnostics
Pressure sender unit transmits pressure information back to the main panel in order for it to preform its integrity test Its is not
optional and must be connected, the system will not work without it.
It is mounted to the gas solenoid valve inlet and outlet test ports using 8mm OD copper pipe Use the appropriate Medem fitting
kit to fit the control valve size (see page 7,8)
Incoming gas ressure: Min = 12 mbar, Max = 70mb
The pressure sender is connected to the control panel with low voltage two core cable using the terminal marked A & B
NOTE: This is low voltage and should be segregated from mains wiring.
Pressure Sender Unit
3
08/03/2018
Main features
SafeAir CM (GP)
Connections to panel: marked on board
1 Live & Neutral 230 volts supply from 3amp switched fuse spur
2 230 volts out to gas solenoid valve
3 Earth connection terminals
4 BMS to indicate, high alarm, gas on, EM stop, low alarm (Using No14 AX1 & 2 )
00 = Gas On
01 = Fan Fault
10 = EM Stop & High Alarm
11 = Unused
5 Remote emergency stop buttons SELV, connect in series multiple buttons (requires a N/C circuit)
6 Power connections for detectors, Methane, LPG, CO, CO2, Oxygen, Temperature
7 Comms connections for detectors, Methane, LPG, CO, CO2, Oxygen, Temperature
8 Pressure sender unit SELV and comm’s both through “A” & “B” terminals (2 wire) MUST BE FITTED
9 12 volt power
10 Fan A interlock for PD switches
11 Fan B interlock for PD switches
12 Fan A current monitor (CT) connection
13 Fan B current monitor (CT) connection
14 Fill & prove time for gas pressure proving & AUX relay settings (see No4)
15 Set Fan A to use either PD switch (No10) or Current Monitor (CT) (No12)
16 Lift valve button, opens the gas valve only whilst the button is continuously pressed, for commissioning purposes
17 Display gas pressures on the LCD screen
18 Learn detectors button, press once only when all detectors are connected and powered Also “learn Trip Current” when
pressed in conjunction with “No 19 Fan Comm” see page 4 for more details
19 Fan comm button: Displays the “Fan Current Trip level” this is the minimum fan current draw allowed before the system
will indicate that the fans aren’t running (Default 35mA)
FAN A
FAN B
1 2
12
11
16 17
13
14
3 4 5 6 7 8 9 10
18 19
15
20
4
08/03/2018
Gas Detection
Gas Detectors
IMPORTANT - Gas Detectors should not be installed until all building, construction or painting work etc Is completed, as these
works can effect the sensitivity and longevity of the detectors
Ensure that the protective cover labels (RED) are removed only
after the completion of all building work and the system has
been commissioned by the Medem engineer
The labels are required to be removed for the detectors to
operate, but removal before the completion of works risks
contaminating the sensor element
The system is capable of operating a mix of up to 4 detectors of different types
Detector Alarm levels
Type Pre-Alarm High Alarm
CO: 80ppm 100ppm
CO2: 1800ppm 2800ppm
Pre-alarm will display a warning message and tone (3beeps) every 10mins
High-alarm will display a warning message, tone every one second and isolate the gas valve after 60seconds
Detector location will vary dependant on the individual characteristics of the target gas that is being monitored for See the gas
detectors own instructions for more guidance
Detector Information
Connection and addressing
+VE supply & Comm’s
From either the main panel or an
extender
Detectors are wired in parallel and can be
connected to one another daisy chain
Address Selector
Each detector must be set to its own
address (1-4) and then “learnt” using
button 18 (see page 3)
Status LED
SafeAir CM (GP)
All current wiring regulations must be followed with reference to running low and mains voltage cables together
The maximum cable length between a detector and the control panel should not exceed 100 metres, if the distance between
the main panel and the detectors is greater than 20metres a 1mm screened cable must be used on the +VE, 0v terminals
Gas detectors, require a four core screened Belden type security cable or 600v rated BMS cable (max cable length of
100meters )
Pressure sender unit, remote emergency stops, require a two core screened cable
Warranty will be void if Fire Protection Cable or cable over 1mm dia is used on the SELV side
5
08/03/2018
Detector Information
Detector location will vary dependant on the individual characteristics of the target gas that is being monitored for
The descriptions below describe the position for each detector after considering these characteristics
For proper function care must be taken not to site a detector in a “dead space” or in the flow of any ventilation
Natural Gas/Methane
Natural gas detectors should be mounted at high level on a wall approximately 150mm from the ceiling height and avoiding
corners and potential dead air areas
Natural gas detectors should not be mounted below the height of the top of a doorway for example This is because as the gas
is slightly lighter than air it will rise filling the room from the ceiling down and will spill through the top of a door opening into the
next room If the detectors are mounted below this height then it will take longer the gas to reach the detector
LPG /Pro ane
LPG gas is heavier than air so detectors need to be mounted at low level 100mm from the floor, consideration should be given
to any potential mopping or wet floor height
Carbon Monoxide
Carbon Monoxide is similarly weighted to air so detectors should be mounted between 1 to 2 meters from the floor
Carbon Dioxide
Carbon Dioxide detectors should be installed so they monitor the general level of CO2 within the area They should be mounted
above standing head height and between 1m and 3m from the potential source Care should be taken so they are not located
close to the edge of a canopy or in direct flow of the supply or extract ventilation
For additional information or guidance on site specific requirements please don’t hesitate to contact us
Each detector has its own Bi-Colour LED which is used to indicate the status of that detector
Not Lit: No power/comm’s These a four wire units and all connections are required, check the polarity of both the
power and the comm’s (MA/MB) terminals are correct
Flashing Green: Detector is warming up, the detectors will flash green on power up for 90 seconds while the sensor
elements stabilize The system will ignore any detectors while flashing
Solid Green: Detector is powered and active Note: The detectors will still require correctly addressing (using the address
selector pot) and learning by the system using button 16 (see page 3)
Flashing Red: Low level alarm All detectors have both a low and high level alarm, low level alarms serve as a warning
that an unsafe condition maybe building and gives chance to intervene before loss of gas service
Solid Red High level alarm An unsafe level of the target gas have been reached and the system will isolate the
gas supply The cause of the alarm will require identifying and resolving before the gas supply can be re-
established
After installation a simple bump test can be performed by using an appropriate level test gas in order to check operation Full
testing and calibration checking takes place during a Medem commissioning
Detector Location
Detector Indications
SafeAir CM (GP)
6
08/03/2018
Basic Connections
Pressure Sender
unit
mounts on to the
body of the gas
valve
(Required)
230v Supply
3Amp Fused Spur Medem
Gas detectors
Multiple,
connect in
parrallel
Earth Connections not shown
Two core low voltage connection
EM Stop Buttons,
Thermal links
(Normally closed)
For multiple, connect in
series
Set a minimum fan running s eed by setting a minimum allowed fan current load.
SafeAir CM (GP)
Fan speed
controls fans
12
13
15
11 10
Earth Connections not shown
Fan Supply
230 v
Where using 3 phase fans
interlock on a single phase
16 17 18 19
If you wish to set a minimum fan running speed, adjust the fans to the desired speed settings and then press buttons 19 & 18 together
This will change the “minimum trip current” setting from the default 35mA to be that being used by the fans at your set speed
Pressing button 19 (Fan comm) alone will display the new “minimum trip current” value If the fan load drops below that level for more
than 10 seconds the system will give an alert and isolate the gas supply There is a 20% allowance for fluctuations in fan load due to
temperature etc
Fan A CT/PD to select between using CT 12 or Terminal 10 for PD switch
Fan B CT/PD to select between using CT 13 or Terminal 11 for PD switch
Fan B can be disabled/enabled using the Fan B DIS/EN selector
Note: Fan A cannot be disabled, Fan A DIS/EN has no function
Mains rating: 240/440 VAC 50HZ Monitoring range - Min: 35 mAmps to Max: 24 Amps Continuous
Current Monitoring or PD Switch
No15
7
08/03/2018
Pressure Sender & Valve connection
Incorrect
Ensure that the valve is correctly installed with regard to the direction of the flow of gas and that the Sender Unit is fitted the
correct way round (Note: there is no flow “through” the pressure sender unit, it is purely reading the pressures either side of the
valve
Correct
Pressur
e
Solenoid
Never mount the valve such that the Solenoid or Sender Unit are below the horizontal
Inlet Side/Upstream Outlet Side/Downstream
Direction of flow
Gas Solenoid and Sender Unit Mounting
Pressure sender unit
SafeAir CM (GP)
8
08/03/2018
Fitting Kit
OUTLET PORT
Note: If this port is blanked off,
use port on base of valve
WALL MOUNTING STRAP
NOTES:
Solenoid coil of the valve should never be mounted below the horizontal
Pressure sender unit should never be mounted upside down (to protect from water ingress)
Approx 400mm length
INLET PORT & OUTLET PORT
Note: These ports could be
side by side
Mounting details - Fitting kit
PRESSURE SENDER UNIT
INLET PORT
Fitting kit - Contents
SafeAir CM (GP)
9
08/03/2018
Remote stop buttons
To EM Stop connections in the
panel
Use terminals TB2 A & C Use terminals TB2 A & C
Remote stop buttons can be connected to the panel terminal
marked as “EM STOP” (number 6 )
The remote buttons must be wired as shown in order to provide a
“closed contact” for the control panel
If thermal links are to be installed these should be wired
in series with the EM sto buttons
To EM Stop connections in the
panel
Indicator bar shows when
pressed
Normal EM-Stop Activated
Multi le Sto Buttons
Single Sto Buttons
Resetting (indicator bar)
The stop buttons supplied by Medem are of a “Push Glass, key resettable” style, when activated a yellow indicator bar will
show and the unit will require resetting using the key provided
Multiple stop buttons are wired in series
If thermal links are to be installed these too should
be wired in series with the EM stop buttons
Use terminal TB2 A & C
SafeAir CM (GP)
10
08/03/2018
Warranty
Medem (UK) Limited
Project House
19 Dallimore Road
Manchester
M23 9NX
Tel: (0) 161 233 0600
Fax: (0) 161 233 0601
Web: www medem co uk
E-mail: sales@medem co uk
Medem UK Warranty
Terms & Conditions
1 The warranty is a parts warranty and Medem UK Ltd will not cover or accept any labour or
other expenses that may be incurred in the process of changing faulty product
2 All panels and sender units are covered by a five year warranty
3 Gas detector units and other remote detectors carry a two year warranty Installation of the
detectors should not be undertaken until all building and construction work is completed
4 Gas solenoid valves carry the original manufacturers warranty, though as the supplier
Medem UK will exchange faulty valves for return to the manufacturer
5 Where a Medem UK engineer (or another company appointed by Medem UK) commission
and installed system then that system will carry a ten year warranty This applies to the
main panel and the sender unit At the time of commissioning a security label with a serial
number will be attached to the main panel box photographs and a comprehensive record
of the installation will be held by Medem UK
6 Where a warranty claim is made then, where appropriate, a written order to attend site
must be provided to Medem UK A cost for labour and travel to site will be prepared as a
quote The cost must be included in the order
7 Where it is found that the installation and/or the quality of workmanship has contributed to
or wholly caused the failure of the product then we reserve the right to charge the whole or
a proportion of the cost of the faulty item
SafeAir CM (GP)
11
08/03/2018
messages
Test fail check all a liances are off and retest:
The system has found an escape of gas, the most common cause is an open appliance Check all appliances are off and restart
the pressure test If the system still reports test fail then a leak will be on the pipe work Using “Blind button A” (see page 2) you
can view the gas pressures at the valve, the outlet pressure must remain at least 90% of the value of the inlet pressure or a leak
will be declared
Sender error, call engineer
System is not receiving data from the sender unit The pressure sender is a required part of the system and cannot be “linked
out” Verify the sender is correctly wired and that you have a green flashing LED on the sender unit
Detector fault, DXX lost comms
The system believes it has lost connection to a detector on address XX, verify detector addresses and press the “learn
button” (16) Verify all connected detectors are being registered by pressing “blind button B” (see page 2) If you have no
detectors connected to the system pressing the learn button will clear the error message
Gas Off, Switch On Fan X.
The system can monitor the fan status via a current monitor or air pressure switches These provide a closed contact to
terminals Fan A and Fan B, it is a requirement when using fan interlocking that the fans be running (and therefore the A and B1
receiving a closed contact) before the system can begin a gas pressure test If at any point the fans stop running (opening the A
or B contact) the system will isolate the gas and report fans not running Check that the fans are not only switched on, but
actually running and moving air
Prs X.XMbar, Check Inlet Gas
The system requires a minimum of 13 mBar of pressure at the inlet side of the gas valve, this is to ensure a correct strength
flame If at any time the incoming pressure drops below 13mBar for more than 10 seconds the system will isolate the gas and
report “low incoming gas pressure”
Note: if this occurs during installation check the sender unit direction of flow, if the sender is installed backwards the system will
believe the “outlet” to be the “inlet” and therefore see an open end as being low incoming gas pressure
Gas Off, Reset Em Sto s & Switch On/Off
The system has an panel mounted emergency stop and connection inside for remote buttons First check the panel button (once
pressed some require resetting by twisting and releasing) Clear the message by turning the main system switch off and then
back on, if the message remains check any remote buttons and their connections The terminal for the remote buttons requires
a volt free normally closed contact, ensure all remote stop buttons, thermal links any another connected systems (BMS/Fire
panels) are reset and the contacts are closed
In the event of any alert the system will always give a reason on screen as to the cause
Common messages you may receive are shown below with further explanation
If you require any help or if anything is unclear then please contact technical support on 0161 233 0600
SafeAir CM (GP)

Other manuals for SafeAir CM

1

This manual suits for next models

1

Other Medem Gas Detector manuals

Medem AGDS-2em User manual

Medem

Medem AGDS-2em User manual

Medem AGDS-2em User manual

Medem

Medem AGDS-2em User manual

Medem SEC-K V4 User manual

Medem

Medem SEC-K V4 User manual

Medem SEC-B User manual

Medem

Medem SEC-B User manual

Medem AGDS-V User manual

Medem

Medem AGDS-V User manual

Medem AGDS-MC User manual

Medem

Medem AGDS-MC User manual

Medem AGDS-2em v2 User manual

Medem

Medem AGDS-2em v2 User manual

Medem AGDS-MC v2 User manual

Medem

Medem AGDS-MC v2 User manual

Medem AGDS-4 User manual

Medem

Medem AGDS-4 User manual

Medem AGDS-MCM v2 User manual

Medem

Medem AGDS-MCM v2 User manual

Medem SEC-L v4 User manual

Medem

Medem SEC-L v4 User manual

Medem AGDS-2 User manual

Medem

Medem AGDS-2 User manual

Medem SafeAir User manual

Medem

Medem SafeAir User manual

Medem SafeAir User manual

Medem

Medem SafeAir User manual

Medem AGDS-M User manual

Medem

Medem AGDS-M User manual

Popular Gas Detector manuals by other brands

mPower Electronics UNI MP100 user guide

mPower Electronics

mPower Electronics UNI MP100 user guide

Dräger Polytron Pulsar 2 Instuctions for use

Dräger

Dräger Polytron Pulsar 2 Instuctions for use

GASTRON GTC-550 instruction manual

GASTRON

GASTRON GTC-550 instruction manual

Helio SL Series operating manual

Helio

Helio SL Series operating manual

Sensitron SMART3 NC user manual

Sensitron

Sensitron SMART3 NC user manual

Consilium Salwico GD Technical manual

Consilium

Consilium Salwico GD Technical manual

Riken Keiki GD-F88Ai operating manual

Riken Keiki

Riken Keiki GD-F88Ai operating manual

GDS 404 Series Operating handbook

GDS

GDS 404 Series Operating handbook

BEINAT GS920 quick start guide

BEINAT

BEINAT GS920 quick start guide

Samon GD instructions

Samon

Samon GD instructions

GEV FlammEx FMG 3255 manual

GEV

GEV FlammEx FMG 3255 manual

AGS Mini Merlin LPGCO v2 TX Installation, operation & maintenance manual

AGS

AGS Mini Merlin LPGCO v2 TX Installation, operation & maintenance manual

Henan Oceanus Import & Export OC-F08 operating manual

Henan Oceanus Import & Export

Henan Oceanus Import & Export OC-F08 operating manual

Levenhuk ERMENRICH NG20 user manual

Levenhuk

Levenhuk ERMENRICH NG20 user manual

GasTech Cannonball 3 Dilution Manual

GasTech

GasTech Cannonball 3 Dilution Manual

Heiman HEIEHS1CG-P quick start

Heiman

Heiman HEIEHS1CG-P quick start

Oldham CTX 300 CO2 user manual

Oldham

Oldham CTX 300 CO2 user manual

olympia electronics BS-377/WP/A manual

olympia electronics

olympia electronics BS-377/WP/A manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.