Detector Information
Detector location will vary dependant on the individ al characteristics of the target gas that is being monitored for.
The descriptions below describe the position for each detector after considering these characteristics.
For proper f nction care m st be taken not to site a detector in a “dead space” or in the flow of any ventilation.
Natural Gas/Methane
Nat ral gas detectors sho ld be mo nted at high level on a wall approximately 150mm from the ceiling height and avoiding
corners and potential dead air areas.
Nat ral gas detectors sho ld not be mo nted below the height of the top of a doorway for example. This is beca se as the gas
is slightly lighter than air it will rise filling the room from the ceiling down and will spill thro gh the top of a door opening into the
next room. If the detectors are mo nted below this height then it will take longer the gas to reach the detector.
LPG /Propane
LPG gas is heavier than air so detectors need to be mo nted at low level 100mm from the floor, consideration sho ld be given
to any potential mopping or wet floor height.
Carbon Monoxide
Carbon Monoxide is similarly weighted to air so detectors sho ld be mo nted between 1 to 2 meters from the floor.
Carbon Dioxide
Carbon Dioxide detectors sho ld be installed so they monitor the general level of CO2 within the area. They sho ld be mo nted
above standing head height and between 1m and 3m from the potential so rce. Care sho ld be taken so they are not located
close to the edge of a canopy or in direct flow of the s pply or extract ventilation.
For additional information or g idance on site specific req irements please don’t hesitate to contact s.
Each detector has its own Bi-Colo r LED which is sed to indicate the stat s of that detector.
Not Lit: No power/comm’s. These a fo r wire nits and all connections are req ired, check the polarity of both the
power and the comm’s (MA/MB) terminals are correct.
Flashing Green: Detector is warming p, the detectors will flash green on power p for 90 seconds while the sensor
elements stabilize. The system will ignore any detectors while flashing.
Solid Green: Detector is powered and active. Note: The detectors will still req ire correctly addressing ( sing the address
selector pot) and learning by the system sing b tton 16 (see page 3).
Flashing Red: Low level alarm. All detectors have both a low and high level alarm, low level alarms serve as a warning
that an nsafe condition maybe b ilding and gives chance to intervene before loss of gas service.
Solid Red High level alarm. An nsafe level of the target gas have been reached and the system will isolate the
gas s pply. The ca se of the alarm will req ire identifying and resolving before the gas s pply can be re-
established.
After installation a simple b mp test can be performed by sing an appropriate level test gas in order to check operation. F ll
testing and calibration checking takes place d ring a Medem commissioning.