
User Guide
DigiFlex
Manage Your Energy
User area:
The DigiFlex is a portable tool to be used as a complement to xed
installed earth fault monitoring systems or ve wire earth fault systems
in an AC system.
When the supervising system alarms, the DigiFlex is able to show
in which group wire or burden the fault is to be found.
The exible current sensor allows metering during operation
even in places that are hard to reach in a distribution board
or switchroom. The meter accuracy is high (±10%) and is able
to recognize current faults down to 20mA.
How to use the DigiFlex:
Apply the exible current sensor around where you want to measure and start the instrument.
Upon current sum metering, which is the method used for measuring earth faults or ve wire faults, all wires that nor-
mally lead electricity (phases and neutral) must be covered by the current sensor. PE, the earth wire must pass outside
the sensor.
Metering tips:
1. Upon measuring parallell cables to the same burden, phase and earth in all wires must be inside the
current sensor.
2. The level of fault that is monitored in a xed mounted unit does not necessarily correspond to the value
on a portable instrument. This is caused by that several faults may be found on each group with dierent phase
angles.
3. Current faults measured in a earth wire (PE) may not be compared to sum current measuring. Earth fault cur
rents may choose several ways back to the supplying transformer, and split out over the total system as well as
other electrically lead objects in the facility.
4. The most frequent fault in a ve wire system is that the earht and PE are connected. This fault does not result in
fuses or current protectors to discharge.
5. In a ve wire system with three-pole fuses, current faults may be shown even if the current device is turned o.
This may be caused by faults according to point 4, circulating currents in the facility that are redirected through
the earth since this is not discharged at three-pole break.
NOTE!
As always when working in an electrical environment, caution must be taken.
In a ve wire system, the earth is always to be treated with as much respect as the phase leader. If the earth is connected
incorrectly between dierent groups, the earth may be fully electrically activated even if the current device is turned o
or if the fuses are removed.
Megacon AB
Ranhammarsvägen 20 - 168 67 Bromma - Tel 08-402 42 50 - Fax 08-26 80 50 - sales@megacon.se - www.megacon.se
2014-08-21