Megalarm wireless system
General points
The Megalarm wireless fire alarm system is designed for small offices, shops, workshops, site cabins and
temporary buildings. It can combine up to 10 units consisting of 1 master unit and 9 stave units, either
manual call points or smoke detectors. The system is powered by batteries and requires no mains voltage
supply.
The master P300W can be combined with either 9 more P300Ws, C300W radio manual call points
(MCP), radio smoke heads D300W or a combination of all 3 totalling no more than 9, plus the master. The
instructions in this manual will enable you to commission all devices together, which when activated will
register an alarm sound from all P300W units and D300W detectors.
Instructions for decommissioning can be found on the last page should you encounter any difficulties.
This is important should you encounter any set up issue, decommission and start the configuration process
again.
Technical Data
P300W master unit
Power Lithium 3V battery capacity: 1300mAh, IEC standard: CR17345 for the radio module & 6LR 61 Alkaline 9 volts battery
for sounder/beacon operation autonomy: 5 years with at least 5 minutes alarm
Installation Method Surface mounted
Sounder Integral 90db within 2 meters
Strobe Lights Integral high power LEDs
Dimensions 126(W)x242(H)x75(D)mm
Colour White ABS
Manual Call Point Integral/wireless complete with 3V lithium battery
Wireless Range 100m in open area conditions, 30-40m if being used inside a building
C300W manual call point
Power Integral lithium 3V battery, capacity: 1400mAh, IEC standard: CR17345
Range Maximum range between manual call point and base = 100m in open area conditions
Installation Mounting Surface mounted
Resetting Key Included
Wireless Range 100m in open area conditions, 30-40m if being used inside a building
D300W wireless smoke detector
Power Lithium sealed in battery (non-replaceable)
Sounder Integral 85db
Test Button Integral
Operating Temperature 0 ºC - 55 ºC
Radio Linking Frequency 868 Mhz
Wireless Range 100m in open area conditions, 30-40m if being used inside a building
Wireless interface (optional - not a stock item)
Power 12V via fire alarm panel
Operating Temperature 0 ºC - 55 ºC
Dimensions 83(W)x83(H)x46(D)mm
Interconnection Capacity Smoke detectors unlimited
Wireless Range 100m in open area conditions, 30-40m if being used inside a building