mercor mcr 0204 Operator's manual

Nr dok: HO.20.00601.docx rew.: BStatus: Wydany
Technical and Operating Documentation
User Instruction Manual
mcr 0204
Smoke and Heat Exhaust Control Unit
for Smoke Curtains
mcr PROSMOKE FS CE

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 2 z 15
Table of Contents
1. USER INFORMATION ............................................................................................................................................... 2
2. INTRODUCTION....................................................................................................................................................... 3
3. BASIC INFORMATION ABOUT THE UNIT.................................................................................................................. 4
4. OPERATION ............................................................................................................................................................. 6
5. ASSEMBLY AND START UP....................................................................................................................................... 8
6. INSTRUCTION MANUAL FOR CHECKING CONNECTION AND PERFORMANCE OF THE MCR 0204 CONTROL UNIT . 8
7. TYPICAL CONNECTION DIAGRAMS........................................................................................................................ 10
8. SERVICE AND MAINTENANCE ............................................................................................................................... 11
9. WARRANTY TERMS AND CONDITIONS.................................................................................................................. 11
10. TECHNICAL SPECIFICATIONS ............................................................................................................................ 13
11. DECLARATION OF PERFORMANCE ................................................................................................................... 14
12. CERTIFICATE OF CONSTANCY OF PERFORMANCE ............................................................................................ 15
We recommend keeping this Instruction Manual inside the control unit, so that the
information is always available when required!
1. USER INFORMATION
The mcr 0204 control unit meets the requirements of the National Technical Assessment
CNBOP-PIB-KOT-2017/0014-1009 issue 2 and the essential requirements of EU directives:
2014/35/EU (LVD) regarding electrical equipment provided for use within certain
voltage limits;
2014/30/EU (EMC) regarding electromagnetic compatibility.
RELATED DOCUMENTS:
-
European certification of constancy of performance of construction products
CNBOP-PIB No.1438-CPR-0583 and The Declaration of Performance
No. 092/HO/2018 of 07/03/2018 confirming the compliance of the power supply
with the requirements of EN 12101-10: 2007.
-
EU Declaration of Conformity No. 087/HO/2018 dated 07/03/2018.
The above documents can be downloaded from the „MERCOR” S.A company website -
www.mercor.com.pl
Thank you for choosing the mcr 0204 control unit. We recommend you to read this User Manual
with attention and to apply the recommendations therein. This will ensure smooth and reliable
operation of the equipment.
“MERCOR” S.A reserves the right to modify the product or documentation without notice.
We wish to ensure your full satisfaction with our products and we will be glad to provide
professional service and assistance to you, should such a need arise.
“MERCOR” S.A.
Electrical and electronic equipment should be disposed of and collected separately.
18
1438

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 3 z 15
2. INTRODUCTION
The mcr 0204 control unit is used in smoke exhaust systems to control the operation of electrical
actuators, in particular the actuators of smoke curtains mcr PROSMOKE FS CE.
The control panel mcr 0204 should be installed near a controllable smoke-exhausting device or in
the facility monitoring room. The control panel is supplied with 230V alternating voltage and working
voltage 24V constant voltage at output to which electrical devices controlling the fire-exhausting
system are connected. The control panel is fitted with the batteries which let the system work in the
case of mains power supply decay. The time of supporting the control panel operation with smoke
curtains PROSMOKE FS CE depends on the number of smoke curtains connected.
Control panel mcr 0204 has the following functions:
alarm triggering by hand from alarm pushbuttons,
automatic alarm triggering from smoke sensors,
automatic alarm triggering from fire-signaling control panel,
informing about alarm (NO/NC signal),
informing about system damage (NO/NC signal),
remote alarm reset and roll-up of curtains,
The mcr 0204 unit features visual indicators of its operating status, repeated on alarm
pushbuttons, which allows easy identification of alarm status or a system defect.
Connecting the fire-exhausting pushbutton mcr RPO-1 allows for remote operation of the control
panel (signaling damage or alarm, remote alarm reset or rolling-up curtains after alarm).

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 4 z 15
3. BASIC INFORMATION ABOUT THE UNIT
Fig. 1 Front panel of the unit.
On the front panel there are diode indicators which inform the user about the unit's status.
No.
Description
Colour
Function
1
POWER
green
presence of both sources of supply
2
ALARM
red
visual alarm notification
3
FAIL
yellow
general system defect/failure signal
The FAIL diode is blinking when mains voltage 230 V is not present.
The front panel of unit is attached by means of six screws, which can be released using
a special screwdriver.
1
2
3

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 5 z 15
Fig. 2 View of the unit's interior.
On the unit module's PCB there is a RESET (1) pushbutton. It allows to cancel the alarm after the
original cause of the alarm has been eliminated. Press and hold down the button for at least one
second!
In the left part of the unit module's PCB there is a four-position switch SW1 (2), designed to set
the operation mode:
Switch position
Function
SW1-1
OFF –do not use
ON –FS curtains control mode
SW1-2
In the FS curtains control
mode:
OFF - Automatic reset of
control panel in the alarm
state
ON –Hand reset of control panel
in the alarm state
SW1-3
Do not use
SW1-4
Note: the default setting SW1-2 through SW1-4 —OFF position.
3
4
5
6
7
8
9
10
11
2
13
12
14
15
1
16

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 6 z 15
Along the top edge of the module's PCB there are terminal strips which are used for connecting
the elements of the system:
No.
Description
Function
3
P1
power input 230 V, 50 Hz
4
P2
output to actuators (-,+)
5
P3
ventilation input (G-top, D-bottom, ┴- joint, closing contacts)
6
P4
input for wind/rain controls (closing contact)
7
P5
sensors line (+,-)
8
P6
push-buttons line (+,-)
9
P7
auxiliary power/ alarm reset input (+,-, reset)
10
P8
defect indication output - relay contact
11
P9
alarm indication output - relay contact
15
P14
RPO-1 indication output (1, 2, 3)
Moreover, in the bottom part of the PCB:
12
P10
positive end of battery
13
P11
negative end of battery
Fuse on the PCB (14) FS1 - batteries protection (4 A quick).
Fuse on the PCB (16) FS2 - mains line 230 V protection (125 mA quick).
4. OPERATION
4.1 Normal operation
On the front panel (Fig. 1) the green diode indicator for POWER is on.
Description of diode indicators on the front panel:
POWER
ALARM
FAIL
UNIT STATUS
+
ALARM
□
ANY STATUS
+
-
-
NORMAL OPERATION
+
ON
-
+
BATTERY FAILURE
-
OFF
-
B
MAINS FAILURE
B
BLINKING
+
+
DEFECT
The mcr 0204 control unit is a maintenance-free device. It requires uninterrupted 230 V mains
power supply. In the case of main power supply shortage, the batteries provide emergency power
supply for the period depending on the number of curtains to roll-up (see: OMM for curtains mcr
PROSMOKE FS CE). Any power outage exceeding 72 hours can result in permanent damage to the
batteries.
4.2 Emergency alarm
If the status of the unit is ‘alarm’, the red ALARM diode on the front panel will light up.
Alarm release methods:
Manual - break the glass of the emergency pushbutton and press the button

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 7 z 15
Automatic –depending on the type of sensors, the sensors will be automatically activated when the
temperature rises or in smoke conditions.
Control panel mcr 0204 is also able to receive alarm signal from an external source, e.g. fire alarm
control panel through the RPO pushbuttons line.
In the alarm state, the control panel lowers down connected curtains FS CE to the operational
position.
4.3 Deleting the alarm
To delete the alarm status, determine the source of the alarm first. Then remove its cause and
reset the alarm:
Alarm indicated by the pushbutton (the RPO line) - open emergency pushbutton housing, unlock
the button using the lever and delete the alarm using RESET button inside the housing. The red ALARM
diode will go out. The glass also needs to be replaced.
Alarm indicated by a smoke sensor (the sensors line) - delete the alarm using the RESET button,
either in the RPO emergency pushbutton housing or in the control unit. The sensor will not activate
the alarm again if there’s no longer excessive smoke/temperature. The red ALARM diode will go out.
If the cause of the alarm can’t be removed (for example, when there’s an alarm source failure),
disconnect the line corresponding to a particular alarm source. Delete the alarm using the RESET
button. The red ALARM diode will go out. The FAULT diode will light up.
In this case CALL THE SERVICE!
4.4 Rolling-up curtains after alarm release
Resetting with the mcr RPO-1 casing button rolls-up the curtains automatically.
Alarm resetting depends on the settings of SW1-2. In the case the autoreset function is on, the alarm
is reset automatically; if the autoreset function is off, do as above.
4.5 Diagnosing defects
Visual signal (Fig. 1) on the unit’s front panel informs about a system defect. The signal is repeated
in mcr RPO-1 emergency pushbutton.
When only the FAIL diode is on, the batteries have failed. In this case you should check battery
connections and the condition of FS1 fuse (see page 6).
When the FAIL diode blinks, this means that there is no mains power supply. In this case you
should check the status of FS2 fuse (see page 6) and if the 230 V voltage is present on the unit’s
terminals.
The default factory settings for the battery voltage control potentiometer must not be changed!
In case of a system defect CALL THE SERVICE!
4.6 Curtain control –extra information.
The control panel mcr 0204 operating in the curtain automatics mode may have a service button
for temporary lowering of curtains connected to the P4 terminal.
The time of supporting the control panel operation with smoke curtains PROSMOKE FS CE
depends on the number of smoke curtains connected –more details in OMM of smoke curtains mcr
PROSMOKE FS CE.

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 8 z 15
5. ASSEMBLY AND START UP
1. Mount the unit near the devices which are meant to be controlled by the unit, using
appropriate metal connectors selected in accordance with the substrate material. Note: do not drill
through the unit's housing —in the case of damage to electronic components caused by dust/debris,
any complaint will be disregarded.
2. Sensors line - 2 leads (YnTKSY) from P5 terminals.
End resistor 10 kΩ in the base of the last sensor.
The maximum number of sensors in accordance with the technical parameters.
3. Emergency pushbuttons line (RPO) - 7 conductors from P6, P7 and P14 terminals.
End resistor 10 kΩ in the last pushbutton.
The maximum number of pushbuttons in accordance with the technical parameters.
4. Actuators line - 2 leads (feature PH30, for example HLGs), from P2 terminals. The end terminal
in the last assembly box. The maximum number of actuators in accordance with the technical
parameters.
5. Auxiliary voltage - P7 terminal. The auxiliary voltage output P7 is short-circuit resistant and
may carry a load of maximum two relays.
6. No-voltage output NC (or NO) for information about alarm –2 leads (YnTKSY) from P9
terminals. The jumper H1 allows to select NC output (default) or NO output.
7. No-voltage output NC (or NO) for information about defect –2 leads (YnTKSY) from P8
terminals. The jumper H2 allows to select NC output (default) or NO output.
8. Main supply 230 V, 50 Hz should be connected to the terminal strip P1 on the unit module's
PCB. The power supply for the unit should be separate (units only on the mains line), properly
protected by means of an overload circuit breaker in the switching station.
Do not protect the line by means of a GFCI (RCCB) circuit breaker.
9. 24 V power supply from batteries (P10, P11). The batteries should be connected in series,
taking polarity into account.
10. Start-up. Before switching on the power supply, check if the leads are connected properly.
Note: the leads should be placed and connected in accordance with relevant standards and basic
rules for wiring.
In a correctly operating unit the POWER diode indicator is on.
In order to check the operation of ventilation, the weather monitoring unit should be
disconnected. The weather monitoring unit blocks ventilation for several minutes after the wind has
ceased, and in the case of rain the sensor needs to get dry, which takes even more time.
Note: in order to connect the unit you should use leads which satisfy the requirements of current
regulations.
Note: conduct and connect the cables according to the binding standards and basic rules of
installation assembling.
6. INSTRUCTION MANUAL FOR CHECKING CONNECTION AND
PERFORMANCE OF THE MCR 0204 CONTROL UNIT
For reasons of operational safety and reliability of the fire protection system, after installing the
control panel, check the device by following instructions.
1. Check the correctness and reliability of connection of all cables (main power, input and
output lines, line continuity resistors) in accordance with Operation Manual and the
installation design.
2. Check the value of the power supply voltage of the control unit - it should be 230 V
%10%15
,
50 Hz.

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 9 z 15
3. Perform the control panel start-up in accordance with the Operation Manual
(chapter 4.6).
4. Check whether the control panel remains in the normal operating state (chapter 4.1).
5. After min. 12 hours of charging the batteries, check the voltage at the battery terminals.
The measurement must be carried out in the normal operating state (chapter 4.1). The
voltage at the battery terminals should be in the range of 26.5 ÷ 28 V =.
6. Check the correctness of fault detection by the control unit (paragraph 0): damage to the
detector line (e.g. take out the last detector from the socket), damage to the RPO button
line (e.g. to open the RPO line, P6 terminal), damage to the actuator lines (e.g. open the
actuators line, the control panel in mode smoke exhaust), power supply damage (e.g. 230
V disconnect), battery detection (e.g. disconnect the batteries). Tests should be
performed in a normal operating state for any potential damage. In each test case, the
fault condition should be detected and signalled on the front panel of the control unit, on
the service panel for selected faults, by means of the mcr RPO-1 emergency pushbutton
(if connected) and on the fault indication output (by ohmmeter control).
7. Check whether the control panel is correctly detecting alarms. Check all connected alarm
sources:
a) alarm from the RPO line (press the mcr RPO-1 emergency pushbutton),
b) alarm from the detector line (activate the detector),
c) alarm from the external alarm line (activate external device or open the line).
Tests should be performed in the normal operating state independently for each
connected alarm source. In any case, the alarm condition should be detected and signaled
by the control unit (chapter 4.2) on the front panel, on the service panel with the diode
of the proper alarm source, with the diode of the mcr RPO-1 (if connected) and on the
alarm signal output (ohmmeter control), and all connected fire devices controlled by the
control panel should be controlled.
8. Check whether the control unit remains in the normal operating state after all tests have
been performed (chapter 4.1).
9. The control panel can be put into operation if all tests have been completed correctly.
Only an efficient and properly connected control unit can work in fire protection systems.
In the event that at least one result of the above tests is not correct, the control panel
cannot be used in security systems and should be restored for proper operation.
After checking the above points, make a record in all fields of the table below.
Date of
control
Result:
Working/not working
Name and
surname
Name of
enterprise:
“MERCOR” S.A’s
authorization no:

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 10 z 15
7. TYPICAL CONNECTION DIAGRAMS
Fig. 3 Typical configuration of smoke exhaust system with mcr 0204 unit.
FP CU - fire protection control unit
OCD - optical smoke sensor (KL731)
RPO - mcr RPO-1 emergency pushbutton
PM - assembly box
MECU XL - controller of mcr PROSMOKE FS CE smoke curtain
P - service button
Note: Not all the elements of the system (in particular the connection with fire protection control
unit and weather monitoring unit) must be present in the smoke exhaust system.
Fig. 4 Alternative connection diagram with mcr RPO-1 emergency pushbuttons and optical smoke sensors.

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 11 z 15
8. SERVICE AND MAINTENANCE
The technical condition of fire protection devices installed in the facility is of key importance to ensure
the safety of users of this facility. The guarantee of reliable operation of the devices can only be
obtained by providing regular and professional service care.
Devices produced by "MERCOR” S.A. should be subjected to periodical technical inspections and
maintenance operations every six months during the entire period of operation, i.e. during the
warranty period, as well as after the warranty period. Inspections and maintenance should be carried
out by the manufacturer or by companies having valid authorization for the service of devices
"MERCOR” S.A.
The service carried out in accordance with the above recommendations is one of the basic conditions
of preservation of rights arising from the guarantee and the obligation of the users / owners or
managers of the resulting facilities from the law.
In order to be able to perform activities included in the scope of service inspections, as well as service
and warranty activities such as visual inspection or repair, it is necessary to provide physical access to
the devices.
It is recommended to perform those check-ups in between of inspections:
1. Checking the status of signaling of control diodes.
2. Checking the condition of electrical connections paying special attention to looseness and
mechanical damage.
In matters related to technical inspections, maintenance and repairs of devices, you can contact
representatives of “MERCOR”S.A., tel. 58/341 42 45 during operating hours 8 - 16 (Mon-Fri), e-mail:
[email protected]om.pl.
9. WARRANTY TERMS AND CONDITIONS
1. “MERCOR” S.A. grants a 12-month quality guarantee for equipment, starting from the date of
purchase, unless the agreement provides otherwise.
2. If during the term of guarantee any physical defects of the equipment become evident,
“MERCOR” S.A. shall remove them within 21 days of the written notification, subject to
paragraph 6.
3. “MERCOR” S.A. reserves the right to lengthen the repair time in the event of complicated
repairs or those that require non-standard sub-assemblies [elements] or spare parts to be
purchased.
4. Liability under the Guarantee covers only defects resulting from causes inherent in the
equipment sold.
5. In the event of defects resulting from inappropriate operation of the equipment or due to
other reasons stated in par. 6, the Buyer/Guarantee Holder shall bear the costs of their
removal.
6. The guarantee does not cover:
damages and breakdowns of the equipment due to inappropriate operation, user’s
interference, lack of maintenance or periodic servicing;
equipment damages resulting from causes other than those that “MERCOR” S.A. is
responsible for, in particular: acts of God such as torrential rainfall, flood, hurricane,
flooding, stroke of thunder, overvoltage in the mains, explosion, hail, fall of aircraft, fire,
avalanche, landslide and secondary damages due to the above-listed causes. Torrential
rain is defined as rain with an efficiency index of at least 4 (or 5 in Chomicz scale or

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 12 z 15
torrential rain grade IV (A4)). Should it be impossible to determine the index mentioned in
the previous sentence, the actual condition and the degree of damage at the place of its
origin proving that it is the consequence of torrential rain will be considered. Hurricane is
defined as wind blowing at the speed of at least 17.5 m/s (damages are deemed to have
been caused by hurricane if the effects of hurricane have been found in the immediate
neighborhood);
damages due to failure to immediately report the defect discovered;
worsened quality of coating due to the natural ageing process (fading, oxidation);
defects due to using abrasive or aggressive cleaning products;
parts liable to natural wear and tear during operation (e.g. seals) unless a manufacturing
fault has occurred;
damages due to aggressive external factors, especially chemical and biological ones.
7. Each defect under guarantee should be reported to a local representative of “MERCOR” S.A.
immediately, i.e. within 7 days of its discovery.
8. Applications can be made by phone at +48/ 58 341 42 45, by email to [email protected]om.pl
or by sending a letter to: “MERCOR” S.A. 80-408 Gdańsk, Grzegorza z Sanoka 2.
9. The Buyer/Guarantee Holder is responsible for proper operation and maintenance of the
equipment and for regular (min. twice a year) servicing.
10. The Guarantee shall expire forthwith if:
The Buyer/Guarantee Holder makes design modifications on his own without consulting
“MERCOR” S.A.,
Maintenance or periodic servicing are not done in due time or are performed by
unauthorized persons or a service center not authorized by “MERCOR” S.A., or the
equipment is operated in the wrong way,
Any interference of unauthorized persons –except activities connected with normal
operation of the equipment.
11. Moreover, in the cases specified in par. 10, “MERCOR” S.A. has no warranty obligations.

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 13 z 15
10.TECHNICAL SPECIFICATIONS
Item
Value
Central type
conventional
Power supply voltage - basic
230 V (-15%, +10%) 50 Hz
Rated power
100 VA
Output voltage (power supply for actuators)
24 V=, max. 4 A
Stand-by power supply
2 batteries HP2-12 (12 V, 2
Ah) or similar connected in
series max. 2,3 Ah
Charging voltage for set of batteries
27.5 V ± 0.2 V at 20ºC
Working temperature range
-5ºC ÷ 40ºC
Maximum number of sensors in line:
15 pcs*
Maximum number of push-buttons of type:
mcr RPO-1
ROP
4 pcs.
10 pcs.
Maximum number of modules (curtain units)
Mcr PROSMOKE FS CE
8 pcs.
Maximum wire size
2.5 mm2**
Operation time without mains voltage, in READY mode
minimum 72 hours
Load for relay outputs
max. 100 mA, 24 V
Environmental class acc. to KOT
I
Environmental class acc. to EN 12101-10
I
Functionality class
A
Protection level for housing
IP 54
Insulation grade
II
Dimensions (H x W x D)
230 x 300 x 86 mm
* In standby mode, the current consumption of 1 sensor cannot exceed 80 μA!
** Larger diameters are permissible for the actuators line, provided that the cable ends with pin with
the diameter of that pin up to 2.5 mm2.

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 14 z 15
11.DECLARATION OF PERFORMANCE

Smoke and Heat Exhaust Control Unit mcr 0204 for Smoke Curtains mcr PROSMOKE FS CE. User
Instruction Manual.
Strona 15 z 15
12.CERTIFICATE OF CONSTANCY OF PERFORMANCE
Other manuals for mcr 0204
1
Table of contents
Other mercor Control Unit manuals