
Installation Instructions Continued
10) Place the mounting bracket over the pipework.
11) Place the olive over onto the exposed pipe.
12) Take one of the threaded connectors, slide the connector over the pipework
and loosely t the threaded connector into the mounting bracket.
13) Screw the mounting bracket to the wall.
14) Using two spanners, one to be located on the mounting bracket and the
other to be located on the threaded adaptor then tighten the thread adaptor
to the mounting bracket. Note: Ensure that two spanners are used to ensure
that you do not tighten the assemble against the mounting bracket screws.
Failure to do so may result in the mounting becoming loose.
15) Repeat steps 4 – 14 for the second tting, ensuring that the bar is level
on the wall.
16) To t the trim plates, screw on the threaded insert until it reaches the
nished wall lining and align accordingly. At this stage the pipe should
be ushed of any debris. Failure to do so may result in the lter of the bar
valve becoming prematurely blocked and reduce its performance.
17) Ensuring seals and lters are correctly located in the inlet unions of
the bar valve, screw the unions of the bar valve to the easy x connections
and tighten.
18) Turn on the hot and cold water supplies and check for leaks.
Commissioning and Testing
The valve should be tested to ensure correct operation at commissioning and
thereafter at stated intervals decided by the user but never greater than a 12
Monthly period.
The testing will only require a normal thermometer with a scale greater than
65⁰C. The temperature sensitive element of the thermometer should always be
fully inserted into the water flow.
Measure the mixed water temperature.
Carry out a cold fail/safe shut off test by using the isolation valve to shut off the
water to the cold supply.
Wait 5 seconds, if the water is still flowing check that the water temperature is
below 46⁰C. the flow of water should reduce to a trickle or stop completely.
Open the cold water isolation valve and measure mixed water temperature.
If there is no significant change from the original settings and the fail/safe shut
off is functioning the valve is working correctly and no further service is re-
quired.
If the outlet temperature has drifted by more than 2⁰C, or if the fail/safe func-
tion does not work, a full service or re-commissioning is required.
The manufacturer of the valve recommends that in these circumstances you
contact a competent person for servicing or ring 0800 195 1602 for further
advice.
e thermostatic mixing valve is factory set to the indicated temperature.
Check the product aer installation to ensure that it operates at the correct
outlet temperature.
A temperature dierence of at least 10⁰C should be maintained between the
mixed and system hot water.
Aer commissioning carry out a cold water failure test to ensure the valve is
operating correctly.
If some adjustment is required to the temperature, this should only be carried
out when necessary, by a competent person.
Temperature Adjustment/Commissioning
1) Turn the temperature control to the mixed position (marked 38⁰C on the
handle).
2) Turn on the water to the bath ller and using a thermometer take a tem-
perature reading.
3) If the temperature requires adjustment prise the cap out of the centre of
the temperature control handle.
4) Remove the handle screw and pull the handle o the top of the thermo-
static cartridge.
5) With the handle removed rotate the spindle, anti-clockwise to increase
clockwise to decrease.
6) Once the desired temperature is achieved re-t the handle in the mixed
position, so that the handle cannot be rotated any further clockwise without
depressing the override button.
45