microSYST MS8111PWM3S User manual

COMPETENCE IN
MEASUREMENT
UNIVERSAL DUAL CHANNEL
PROGRAMMABLE CONTROLLER
WITH TIMER OR ALARM
MS8111PWM3S
v1.2
USER MANUAL
PLOVDIV 2018
Редакция документ 2018 11 02
1

Редакция документ 2018 11 02
2

• Difference from the previous version of the software :
0.1s format is added in timer modes.
The controller has 5 outputs / three discrete and two analog /
•Discrete outputs K1 and K2 are control outputs of temperature
controllers.
•The discrete output K3 output is programmed as a timer or alarm in the
System Parameters section
•Analog outputs are retransmitting input variables.
Timer has 2 main modes:
•as an independent from input variables. In this mode the timer is started
by front ;
•depending on whether the measured parameter has reached the
controller setting.In this mode, the timer starts and works until at the
control input has a active level.
Each of the main modes has two sub-modes of work which define timer output:
•The output is switched on during counting
•Output is activated after the expiry of the count.
Редакция документ 2018 11 02
3

СЪДЪРЖ НИЕ
1. DESIGNATION 3
2. ORDER CODE 4
3. TECHNICAL DATA 5
4. OPERATION 6
4.1 TEMPERATURE CONTROLLER SETTINGS 6
4.2 ALARM OUTPUT 6
4.3 TIMER - MODES OF OPERATION 7
4.4 TIMER - EDIT TIME 8
5. FRONT AND BACK PANEL. TERMINALS 8
6. ANALOG INPUTS CONNECTIONS 9
6.1 Resistive sensors connection (Pt100 or others) 9
6.2 Thermocouple connection 9
6.3 Transmitters connection 10
7. CONNECTION TO START THE TIMER 11
8. OUTPUTS CONNECTIONS 11
9. SYSTEM PARAMETERS 12
10. CONSUMER SETTING OF OFFSET ON ANALOG CHANNELS 13
11. RECOMMENDATION AGAINST EMI (Electromagnetic Interference) 13
12. HIDDEN SYSTEM PARAMETERS 14
Controls two processes simultaneously by proportional or ON-OFF mode
Programmable timer or alarm
Analog outputs
Display: 2 x4 digits ED
MS8111PWM3S is used for baked bread, bakery and confectionery, ceramics, rubber
production, hardening of metals, HVAC, greenhouses and others.
1. DESIGNATION
The Microprocessor Two Channel Controller MS8111PWM3S is designed to control
two processes simultaneously using a proportional or positional control law.
An option for user choice of an alarm output or a timer section is provided.
The outputs are controlled by ON / OFF logic or by pulse with variable duration
(PWM) respectively.
Редакция документ 2018 11 02
4

2. ORDER CODE
Редакция документ 2018 11 02
5
MS8111PWM3S - x.x.x.x.x.x.x.x.x.x
Input Channel 1(C1)
Pt1000 Pt100
J
K
Power supply or a transmitter
Transmitter
Housing
C1 C2
1 21
2
0.0 100,0 °C
22
4 24
5 25
6 26
7 27
8 28
9 29
10 30
11 31
13 33
15 35
16 36
17 37
9X 9Y
0.0 200.0 °C
0 250 °C
0 400 °C
0 600 °C
-50 400 °C
-50.0 50.0 °C
-50.0 100.0°C
-50 200 °C
0 600 °C
0 1200 °C
4 20 mA DC-2W
0 20 mA DC-3W
0 10 V DC-3W
other
code
Code
М1
- box Ip5496x48x125
horizo tal pa el
1М
- box Ip5496x48x125
vertical pa el
Input Channel 2(C2)
Code
- ot co ected
-
Т0
Т1
11...14V 150 mA
Supply voltage**
Code
PA
PF
PB
-
-
-
230 VAC
24 VAC
24 VDC
- 12 VDC
- 24 VDC
- other
/50Hz
±30% isolated
±30% isolated
±15% u isolated
±15% u isolated
PC
PD
PX
Code
D
N
S
- Alarm
- Timer
- ot co ected
! Decimal poi t, upper a d
lower limit of the desired
scope must be specified!
Code
K1 K2 K3
AA BA CA
AB BB CB
AD BD ---
-
- Relay
- Triac
ot co ected
5A/250V
2A / 250V
- OC NPN u iso
- OC NPN iso.
AE BE CD
AF BF CF
U =65V, I =100mA
U =80V, I =1A
CEmax Cmax
CEmax Cmax
Supply voltage -
230 VАС
MS8111PWM3S - M1.2.35.T0.PA.I0.AB.BA.CB.N
Example:
Power supplt or a transmitter -
ot co ected
Input C2 - transmitter
4-20mA DC 2W
Analog outputs
I0 - not connected
I1
- 1x4-20mA DC
1x0-20mA DC
- 1x0-1V DC
1x0-10V DC
- 2x4-20mA DC
- 2x0-20mA DC
- 2x0-1V DC
- 2x0-10V DC
I2 -
I3
I4 -
I5
I7
9I
I9
IX- other
Analog outputs -
ot co ected

3. TECHNICAL DATA
Analog inputs
Linear current 0 ÷ 20 mA DC; 4 ÷ 20 mA DC
Linear Voltage 0 ÷ 1 (10) V DC
Thermoresistor Pt 100, P1000 EN 60751
Thermocouple J, K, EN 60584
Other By order
Measurement accuracy 0.15% of the range
Digital inputs
Start / Stop timer Optically isolated active level GND ISO,
for NPN sensor
Discrete outputs
K1 ON/OFF or PWM
К2 ON/OFF or PWM
К3 Function
Options:
Relay 250 V / 5,10 A
Triac 250 V / 2 A
NPN OC uniso Ucemax=65V ,Icemax=100 mA
NPN OC iso Ucemax=80V ,Icemax=1A
Function К3 Alarm
Timer
Analog outputs, (optional ) optically isolated
АО1 – current or voltage
АО2 – current or voltage
0 ÷ 20 mA DC; 4 ÷ 20 mA
0 ÷ 1 (10) V DC
Power supplying a transmitter (11.5 ÷ 14.5) V DC 150 mA unstabilized
Indication and keyboard
Display 2 x 4 digits LED 10 mm
Display range 1999 … 9999
Display format X.XXX X X.XX XXX.X XXXX
Keyboard semi sensor
Power supply
Supply voltage ; frequency 230VАС / max 20mA; 50 Hz
Other Depending on order code
Operating conditions
Temperature and relative
humidity without condensation
Operating: 10 ÷ 70 °C / 10 ÷ 85 % rh
Storage : 20 ÷ 70 °C / 10 ÷ 90 % rh
Dimentions
Overall dimensions (WxHxL) 96 x 48 x 128 mm
Installation in hole 90 x 44 mm
Weight max 300 g
Protection class IP40
Редакция документ 2018 11 02
6

4. OPERATION
Display Basic parameters used in the device:
SP Set Point
Zоn Zone proportional zone or hysteresis in ON/OFF control
PV Process variable input parameter
Ahi Alarm Hi upper alarm limit
ALО Alarm Lo lower alarm limit
In operational mode, the upper display shows the value of Channel 1, while the
lower display shows the value of Channel 2. Green LED s indicate whether the
corresponding output is active, respectively, the top for Channel 1 and the bottom for
Channel 2.
4.1. TEMPERATURE CONTROLLER SET TINGS
To access programming mode, press and hold the SET button for more than 5 seconds (while
the button is pressed, the display shows the values of the two set points. If the button is
released before the time expires, the entry into the mode does not take place).
In programming mode, the lower display displays the parameter name and the upper
display its value. Editing the values is done with the DOWN and UP buttons, and passing
on to the next parameter with the SET button.
Name Description Values
SP 1 Channel 1 Set point Within the range of change
of the input parameter
SP 2 Channel 2 Set point Within the range of change
of the input parameter
4.2. ALARM OUTPUT
Permitted by the SrEG parameter from the Hidden System Parameters section.
When the value of PV for some channel goes over (falls below) the upper (lower) alarm
limit, it is triggered and "ALL" message appears periodically on the channel display.
The alarm output is common to both channels and it is triggered regardless of
which channel is in an alarm situation. On the corresponding display alternating "ALL" and
the measured value are displayed.
Редакция документ 2018 11 02
7

4.3. TIMER - MODES OF OPERATION
Permitted by the SrEG parameter from the Hidden System Parameters section.
The timer section can work independently of the rest of the controller (from the
measured value) by starting / stopping with buttons or on the pulse front at the "Start timer"
input or it works depending on the measured value as the timer starts when the assigned
value is reached(selected by the SrEG parameter).
●MODE 1 - The timer works independently of the controller
Starting from digital input Start timer / start on front /
A button is used to manually start.
MODE 1.1: The timer is started by activating the GND level at the Start timer input
( pressing an external button,for example), with which the timer output is activated and
begins to decrease the set time. The timer output is active until the time has elapsed or the
external button is pressed again.
The red LED blinks until the time has elapsed.
MODE 1. 2 : ТThe timer is started by pressing an external button. The red LED flashes
until the set time elapses. After that, the output activates (indicated by a permanently
illuminated red LED) and remains active until pressing the external button or by a power
failure.
●MODE 2 - The timer starts depending on whether the measured value (PV) has
reached the controller (SP) setting .
The Start timer input must have a GND-level enable.
A switch is used for manual permission.
MODE 2 .1: The timer starts when the starting conditions are reached and an active
level at Start timer (permission from an external switch), which activates the timer output
and the set time starts to count down. The timer output is active until the time elapses or until
disabled by the external key. The red LED flashes until the time runs out. A new start is only
possible afterwards prohibition and re authorization by the external switch.
MODE 2 . 2 : The timer starts when the starting conditions are reached and an active
level at Start timer (permission from an external switch). The red LED flashes until the set
time elapses. After that, the output activates (indicated by a permanently illuminated red
LED) and remains active until disabled by the external key or by a power failure. A new start
is only possible afterwards prohibition and re authorization by the external switch .
In the above two modes, when feeding the supply voltage, if enabled from the external switch
and the startup conditions are present, the timer restarts!
Редакция документ 2018 11 02
8

4.4. TIMER - EDIT TIME
When the timer is started, the remaining time is displayed.
Display of the remaining or set time
on the timer display
by pressing and holding the SET and UP
buttons in the indicated sequence
Change the set time
by pressing and holding the SET and UP
buttons in the indicated sequence for more
than 5 seconds (until SP t shows on the lower
display).
Editing the value is done vie the DOWN
and UP buttons, while confirmation with
the SET button.
5. FRONT AND BACK PANEL. TERMINALS
Редакция документ 2018 11 02
9
Multyfunctional process controller
set
MS8111
+12V
ISO
AO1 GND
ISO
AO2 DIG1
Pt100
J
K
IN
+12V
IN
+12V
Start timer
CH1 CH2
microsyst

6. ANALOG INPUTS CONNECTIONS
For the sake of good functioning, it's important that the probes are located on a
suitable place in the environment, in which the temperature regulation will take place.
6.1 Resistive sensors connection (Pt100 or others)
The sensors can be connected via a two wire or three wire line. The connection of
two wire sensors to a three wire line follows the diagram shown in FIG. 6, while between
terminals 1 and 2 and terminals 5 and 6 of the controller, cable bridges are placed (short
circuited).
At longer distances between sensor and controller, it's recommended to use a three
wire line because it compensates the measurement error of the temperature due to the
additional resistance introduced by the connecting wires. Connecting three wire sensors to
the controller is done according to the scheme shown on FIG. 2 as to terminals 1 and 2 and
terminals 5 and 6 of the controller connect the cables connected to the short circuit in the
sensor.
Figure 1 Figure 2
6.2 Thermocouple connection
When connecting a sensor type thermocouple, care must be taken about the polarity
of the sensor. If polarity is inverthed, the device's readings will be incorrect.
When working with thermocouples, it is necessary to use a compensation cable,
corresponding to the type of thermocouple used (Figure 3).
Figure 3
Редакция документ 2018 11 02
10
Thermocouple Compenasation
cable
16
2 3 45
SHORT SHORT
16
5
4
32
16
2 3 45

6.3 Transmitters connection
6.3.1. Transmitters with two-wire connection
The power to the transmitters is provided by the unit.
Fig. 4 * The device provides unstable voltage from 11.5V to 14.5V / max 50mA
6.3.2. Transmitter with own power supply
Fig. 5
6.3.3. Three-wire transmitter powered by the device
Fig. * The device provides unstable voltage from 11.5V to 14.5V / max 50mA
Редакция документ 2018 11 02
11
I
+
Out
Out
+
16
2 3 45
I
U power
U захр.
+
+
16
2 3 45
I
+
16
2 3 45

7. CONNECTION TO START THE TIMER
external button
(start by front)
Used when the timer operates
independently of the
measured input variables Start Timer – кл.26
GND ISO – кл.23
external switch
(start by level)
Used when the timer operates
depending of the measured
input variables
8. OUTPUTS CONNECTIONS
Depending on the option of executing the corresponding digital output in the order
code, the connections to load is made according the schemes on fig.7
fig.7
Редакция документ 2018 11 02
12
U U
U internal
11-14V
+
-
U
+
-
RELAY TRIAC NPN OC
non isolated
NPN OC
isolated
26 23
26 23

9. SYSTEM PARAMETERS
The system parameter programming mode is accessed by pressing buttons UP and DOWN
simultaneously for more than 5 seconds.
In the mode, the parameter's name is shown on the lower display. With buttons DOWN
and UP the desired parameter is selected, and with SET button, on the upper display, the
parameter's value is displayed.
Editing the values is done with the DOWN and UP buttons and the switching to the next
parameter with the SET button.
Name Description Values
t 1 Channel 1 period
0 128 seconds
When the value is zero, the regulation becomes
positional, with parameter Zon1 assuming the role
of hysteresis
Zon1 Zone of proportionality
for Channel 1 Within the range of change of the input parameter
t 2 Channel 2 period
0 128 seconds
When the value is zero, the regulation becomes
positional, with parameter Zon2 assuming the role
of hysteresis
Zon2 Zone of proportionality
for Channel 2 Within the range of change of the input parameter
ALO1 Channel 1
low level alarm Within the range of change of the input parameter
ALO2 Channel 2
low level alarm Within the range of change of the input parameter
Ahi1 Channel 1 high level
alarm Within the range of change of the input parameter
Ahi2 Channel 2 high level
alarm Within the range of change of the input parameter
End Exit system parameters
mode
Pressing SET while selected exits system
parameters mode.
Changes in parameters should to be made with extreme caution, due to
potential incorrect function of the device.
Редакция документ 2018 11 02
13

10. CONSUMER SETTING OF OFFSET ON ANALOG CHANNELS
In this mode, users can freely enter a programmable value, which will always be added to
the measurement ("offset"). This is used when there's a discrepancy between the value
displayed by the device and measured with another reference instrument.
To authorize the user offset of the readings of both channels, it is necessary to power on
the device while the DOWN button is pressed.
In this case, values are added (subtracted when with minus sign) to channel readings.
Assigning each separate offset is done the way, as is setting the setpoint SP of each
channel in normal work mode.
Caution – the device does not display previously made changes!
Changing with extreme caution can lead to incorrect operation of the unit!
Offset mode is available only until the next shut down.
11. RECOMMENDATION AGAINST EMI (Electromagnetic Interference)
•Recommendations for use of connecting wires
- Wires that carry a similar type of signals can be packed together, but if the signals
are different, the wires must be separated to prevent electromagnetic interaction.
When there have to be crossed wires with different signal types this must be done at
an angle of 90 degrees and a long distance.
Wires, which carry weak signals and wires connecting the sensors to the controller
must not be near contactors, motors, generators, radios and wires, which carry large currents.
•Noise suppression using the built-in in the controller filter
If the input parameter fluctuates and is not stable it is necessary to reduce the filter
coefficient Fr 1 or Fr2. As lower the value, the heavier the filter and slowly change the input
parameter.
If the process variable on the display jumps periodically for short intervals, it is
necessary to increase the parameter tJ 1 ot tJ2. When increasing this parameter, the device
reacts slower at an unexpected “jump’’ in the input, but ignores the short term interference.
Редакция документ 2018 11 02
14

12. HIDDEN SYSTEM PARAMETERS
USED ONLY BY SERVICE SPECIALIST
WRONG SETTINGS MAY LEAD TO THE INCORRECT FUNCTION OF THE DEVICE
Hidden system parameters are “visible’’ only until the next shut down.
To access hidden system parameters, it’s needed to feed the power supply while holding
and pressing the UP button. In this case, in the list of system parameters, after End, the
following ones appear:
Name Description Values
Fr 1 Filter coefficient for Channel 1
0 128 units
A lower value corresponds to a
“heavier” filter of the input variable
tJ 1 Waiting time before a filter jump for
Channel 1 0 128 seconds
JP 1 Filter rebound threshold of Channel 1
0 .. 255 units of input
When changing the input variable to a
value greater than the preset and
maintaining the new state for a time
greater than tJ 1, the filter bounces
and takes the new value directly.
Fr 2 Filter coefficient for Channel 2
0 128 units
A lower value corresponds to a
“heavier” filter of the input variable
tJ 2
Waiting time before a filter jump for
Channel 2 when changing the input
variable with a value greater than JP 2.
0 128 seconds
JP 2 Filter rebound threshold of Channel 2
0 .. 255 units of input
When changing the input variable
to a value greater than the preset and
maintaining the new state for a time
greater than tJ 2, the filter bounces
and takes the new value directly.
Редакция документ 2018 11 02
15

SrEG
0 - K3 - ALARM
К3 – TIMER – timer operates independently of the measured input variables
129 – mode 1 in seconds
130 – mode 1 in minutes
131 – mode 2 in seconds
132 – mode 2 in minutes
133 mode 1 in seconds x 0.1
134 mode 2 in seconds x 0.1
•The modes in seconds are indicated with a decimal point
K3 – TIMER- is started
depending of the measured input
variables
1 – mode 1 in seconds
2 – mode 1 in minutes
3 – mode 2 in seconds
4 – mode 2 in minutes
5 – mode 1 in seconds x 0.1
6 – mode 2 in seconds x 0.1
The modes in seconds are
indicated with a decimal point
To start when the set point is reached,
add to the value of parameter :
32 – start at PV1>SP1 & PV2>SP2
40 – start at PV1<SP1 & PV2>SP2
48 – start at PV1>SP1 & PV2<SP2
56 – start at PV1<SP1 & PV2<SP2
64 – start at PV1>SP1 or PV2>SP2
72 – start at PV1<SP1 or PV2>SP2
80 – start at PV1>SP1 or PV2<SP2
88 – start at PV1<SP1 or PV2<SP2
96 – start at PV1>SP1
104 – start at PV1<SP1
dPnt
Decimal points of the channels
(MEANINGFUL, ONLY IF IT’S
SCALING!)
ONLY FOR SERVICE
SPECIALISTS
0 ... 255
X . X . X . X .
X . X . X . X .
PA 1 Division coefficient of analog output1*
1999 ... 9999
PA 0 Offset of analog output 1*
PB 1 Division coefficient of analog output2*
PB 0 Offset of analog output 2*
rs__ Initialize communication through serial
channel Do not press SET
*The calculation of the analog output is done by the following formula:
0
1
1023* PX
PX
PV
Aout
, where PV is the value of the measured parameter, and PX1 and PX0
are PA1 and PA0 or PB1 and PB0 respectively.
Редакция документ 2018 11 02
16
32
64
128 16
1
2
4
8

WARRANTY CARD
Warranty card №:.................................................
Warranty term:................................................. months
Factory number:.................................................
The items were purchased from :..................................................................
Invoice number:............................../............. 20........ year .
GUARANTEE CONDITIONS
The guaranty consists in free repairs of all the factory defects which can occur during
the guarantee period. The repair is performed as in the repair base is being presented
the current guarantee card with which the device is bought. The warranty does notrefer
to issue caused by a bad transport, bad conservation, wrong exploitation, naturedisasters, not
following the instructions and the cases when there is an attempt to fix anydefects by other
people. In those cases the issue is being fixed only against payment.
The maintenance during the guarantee period and doing the claims happens according to the
valid legislation.
PERFORMED REPAIRS IN THE SERVICE
Service Date of
receipt
Order
number Type of repairs done
Date of
transmiss
ion
Carried
out the
repair
Seller:................... Buyer:.................
4, Murgash str., Plovdiv city, Bulgaria, 4000
Тел.: (+359 32) 642 519, 640 446 факс: (+359 32) 640 446
Редакция документ 2018 11 02
17
Table of contents
Other microSYST Controllers manuals
Popular Controllers manuals by other brands

Extron electronics
Extron electronics MEDIALINK MLC 52 Series user manual

Barco
Barco TransForm A Brochure & specs

gefran
gefran GF_LOOPER 3.5” quick start guide

Velleman
Velleman E305DC user manual

Bartels Mikrotechnik
Bartels Mikrotechnik microComponents mp6-XOEM operating manual

Panasonic
Panasonic FP7 Series user manual

Morningstar
Morningstar SUNSAVER DUO Installation and operation manual

Mitsubishi Electric
Mitsubishi Electric FX3U-ENET user manual

Ruckus Wireless
Ruckus Wireless SmartZone 100 Quick setup guide

ROMANOFF
ROMANOFF W13 operating instructions

Griffin Technology
Griffin Technology PowerMate quick start guide

Allen-Bradley
Allen-Bradley PowerFlex 70 user manual