Power source 220-240V~50Hz / 220V~60Hz
Operation data Cooling Heating
Nominal capacity kW 14.0 [ 5.0 (Min.) ~16.0 (Max.)] 16.0 [ 4.0 (Min.) ~18.0 (Max.)]
Power consumption kW 4.83 4.97
Running current A 21.4 / 22.4 22.0 / 23.1
Power factor %98 98
Inrush current A 5 < Max.running current 26 >
Sound Pressure Level dB(A)
P-Hi : 42 Hi : 39 Me : 35 Lo : 33
Cooling
:
49 Heating
:
52
Exterior dimensions
Height x Width x Depth
Exterior appearance Ceramic White Stucco White
(Munsell color) (N8.0) near equivalent (4.2Y7.5/1.1) near equivalent
Net weight kg 49 105
Refrigerant equipment
Compressor type & Q'ty —RMT5134MDE2 × 1
Starting method —Direct line start
Refrigerant oil ・—0.9 M-MA68
Heat exchanger
Louver fine & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control —Electronic expansion valve
Air handling equipment
Fan type & Q'ty Centrifugal fan × 1 Propeller fan × 2
Motor <Starting method> W 157 < Direct line start > 86 x 2 < Direct line start >
Air flow (Standard) CMM P-Hi
:
18 Hi
:
16 Me
:
14 Lo
:
12 100
External static pressure Pa 0
Outside air intake Not possible —
—
Air filter, Q'ty Plastic net × 1 (Washable) —
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber sleeve (for Compressor )
Insulation (noise & heat) Polyurethane form —
Electric heater W —20 (Crank case heater)
Remote controller RC-E4 Installed / wireless : RCN-KIT3-E (option)
Room temperature control Thermostat by electronics —
Safety equipment Overload protection for fan motor Internal thermostat for fan motor
Frost protection thermostat
Abnormal discharge temperature protection.
Installation data
Refrigerant piping size
Connecting method Flare piping Flare piping
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant Quantity
R410A 4.5kg (Pre-charged up to the piping length of 30m) Outdoor unit
Drain pump — —
Drain
Insulation for piping Necessary (both Liquid & Gas lines)
Standard Accessories Mounting kit Edging
Notes (1) The data are measured at the following conditions.
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation
these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
(5)
Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1" × 1 (option). ①
:
Pipe of O/U~Branch, ②
:
Pipe of Branch~I/U
(7) If wireless remote controller is used, only 3-speed fan setting (Hi-Me-Lo) is available.
mm 1,850 × 600 × 320 1,300 × 970 × 370
mm
Adapted to RoHS directive
FDF140VNXPVD
Indoor unit FDF71VD (2 units) Outdoor unit FDC140VNX
Indoor air temperature
Operation DB
27oC
20oC 7oC 6oC
19oC 35oC 24oC
WB DB WB
Cooling
Heating
Item
Outdoor air temperature
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
See page 43
Max.100m
Hose Connectable with VP20
Liquid line: I/Uφ9.52 (3/8") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8 O/Uφ9.52 (3/8")
Gas line: I/Uφ15.88 (5/8") ②φ15.88 (5/8") × 1.0 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Model
Item
Holes size φ20 × 3pcs