1. BEFORE INSTALLATION
Required Tools for Installation
ENGLISH
CONTENTS
1. BEFORE INSTALLATION ............................................................1
2. OUTDOOR UNIT INSTALLATION ...............................................7
3. FLARING WORK AND PIPE CONNECTION............................... 8
4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN.........9
5. PUMPING DOWN......................................................................12
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.
• Besuretoobservethewarningsandcautionsspeciedhereastheyincludeimportantitemsrelatedtosafety.
• Afterreadingthismanual,besuretokeepittogetherwiththeOPERATINGINSTRUCTIONSforfuturereference.
• EquipmentcomplyingwithIEC/EN61000-3-12.
nDo not install the unit by yourself (user).
Incompleteinstallationcouldcausereorelectricshock,injuryduetotheunit
falling,orleakageofwater.Consultthedealerfromwhomyoupurchasedtheunit
oraqualiedinstaller.
nPerform the installation securely referring to the installation manual.
Incompleteinstallationcouldcausere,electricshock,injuryduetotheunitfalling,
orleakageofwater.
nWhen installing the unit, use appropriate protective equipment and tools
for safety.
Failuretodosocouldcauseinjury.
nInstall the unit securely in a place which can bear the weight of the unit.
If the installation location cannot bear the weight of the unit, the unit could fall
causinginjury.
n Electricalworkshouldbeperformedbyaqualied,experiencedelectrician,
accordingtotheinstallationmanual.Besuretouseanexclusivecircuit.Do
not connect other electrical appliances to the circuit.
Ifthecapacityofthepowercircuitisinsufcientorthereisincompleteelectrical
work,itcouldresultinareoranelectricshock.
n Do not damage the wires by applying excessive pressure with parts or
screws.
Damagedwirescouldcausereorelectricshock.
nBe sure to cut off the main power in case of setting up the indoor P.C. board
or wiring works.
Failuretodosocouldcauseelectricshock.
n Usethespeciedwirestoconnecttheindoorandoutdoorunitssecurely
andattachthewiresrmlytotheterminalblockconnectingsectionssothe
stressofthewiresisnotappliedtothesections.Donotextendthewires,
or use intermediate connection.
Incompleteconnectingandsecuringcouldcausere.
n Donotinstalltheunitinaplacewhereinammablegasmayleak.
Ifgasleaksandaccumulatesintheareaaroundtheunit,itcouldcauseanexplo-
sion.
n Donotuseintermediateconnectionofthepowercordortheextensioncord
and do not connect many devices to one AC outlet.
Itcouldcauseareoranelectricshockduetodefectivecontact,defectiveinsula-
tion,exceedingthepermissiblecurrent,etc.
n Besuretousethepartsprovidedorspeciedpartsfortheinstallationwork.
Theuseofdefectivepartscouldcauseaninjuryorleakageofwaterduetoare,
anelectricshock,theunitfalling,etc.
nWhen plugging the power supply plug into the outlet, make sure that there
is no dust, clogging, or loose parts in both the outlet and the plug. Make
sure that the power supply plug is pushed completely into the outlet.
Ifthereisdust,clogging,orloosepartsonthepowersupplyplugortheoutlet,it
couldcauseelectricshockorre.Ifloosepartsarefoundonthepowersupply
plug, replace it.
nAttach the electrical cover to the indoor unit and the service panel to the
outdoor unit securely.
Iftheelectricalcoveroftheindoorunitand/ortheservicepaneloftheoutdoor
unitarenotattachedsecurely,itcouldresultinareoranelectricshockdueto
dust, water, etc.
nWhen installing, relocating, or servicing the unit, make sure that no sub-
stanceotherthanthespeciedrefrigerant(R32)enterstherefrigerantcircuit.
Anypresenceof foreignsubstancesuchasair cancauseabnormalpressure
riseandmayresultinexplosionorinjury.Theuseofanyrefrigerantotherthan
thatspeciedforthesystemwillcausemechanicalfailure,systemmalfunction,
orunitbreakdown.Intheworstcase,thiscouldleadtoaseriousimpedimentto
securingproductsafety.
nDo not discharge the refrigerant into the atmosphere. If refrigerant leaks
during installation, ventilate the room. Check that the refrigerant does not
leak after installation has been completed.
Ifrefrigerantleaksandcomesincontactwithreorheatingpartofsuchafan
heater,kerosene heater, orcooking stove, itwill create harmfulgas. Provide
ventilationinaccordancewithEN378-1.
nCheck that the refrigerant gas does not leak after installation has been
completed.
Ifrefrigerantgasleaksindoors,andcomesintocontactwiththeameofafan
heater,spaceheater,stove,etc.,harmfulsubstanceswillbegenerated.
nUse appropriate tools and piping materials for installation.
ThepressureofR32is1.6timesmorethanR22.Notusingappropriatetoolsor
materialsandincompleteinstallationcouldcausethepipestoburstorinjury.
nWhen pumping down the refrigerant, stop the compressor before discon-
necting the refrigerant pipes.
Iftherefrigerantpipesaredisconnectedwhilethecompressorisrunningandthe
stopvalveisopen,aircouldbedrawninandthepressureintherefrigerationcycle
couldbecomeabnormallyhigh.Thiscouldcausethepipestoburstorinjury.
nWhen installing the unit, securely connect the refrigerant pipes before start-
ing the compressor.
Ifthecompressorisstartedbeforetherefrigerantpipesareconnectedandwhen
the stop valve is open, air could be drawn in and the pressure in the refrigeration
cyclecouldbecomeabnormallyhigh.Thiscouldcausethepipestoburstorinjury.
n Fastenaarenutwithatorquewrenchasspeciedinthismanual.
Iffastenedtootight,aarenutmaybreakafteralongperiodandcauserefrigerant
leakage.
nThe unit shall be installed in accordance with national wiring regulations.
nEarth the unit correctly.
Do not connect the earth to a gas pipe, water pipe, lightning rod or telephone
earth.Defectiveearthingcouldcauseelectricshock.
nBe sure to install an earth leakage breaker.
Failuretoinstallanearthleakagebreakermayresultinelectricshockorre.
n Whenusingagasburnerorotherame-producingequipment,completely
remove all of the refrigerant from the air conditioner and ensure that the
area is well-ventilated.
Iftherefrigerantleaksandcomesincontactinreorheatingpart,itwillcreate
harmfulgasandthereisriskofre.
nDo not use means to accelerate the defrosting process or to clean, other
than those recommended by the manufacturer.
nThe appliance shall be stored in a room without continuously operating
ignitionsources(forexample:openames,anoperatinggasapplianceor
an operating electric heater).
nDo not pierce or burn.
nBe aware that refrigerants may not contain an odour.
nPipe-work shall be protected from physical damage.
nThe installation of pipe-work shall be kept to a minimum.
nCompliance with national gas regulations shall be observed.
nKeep any required ventilation openings clear of obstruction.
nDo not use low temperature solder alloy in case of brazing the refrigerant
pipes.
nServicing shall be performed only as recommended by the manufacturer.
n Donotaltertheunit.Itmaycausere,electricshock,injuryorwaterleakage.
nWhen opening or closing the valve below freezing temperatures, refrigerant
may spurt out from the gap between the valve stem and the valve body,
resultingininjuries.
WARNING (Couldleadtodeath,seriousinjury,etc.)
MEANINGS OF SYMBOLS DISPLAYED ON INDOOR UNIT AND/OR OUTDOOR UNIT
WARNING
(Riskofre)
Thisunitusesaammablerefrigerant.
Ifrefrigerantleaksandcomesincontactwithreorheatingpart,itwillcreateharmfulgasandthereisriskofre.
ReadtheOPERATINGINSTRUCTIONScarefullybeforeoperation.
ServicepersonnelarerequiredtocarefullyreadtheOPERATINGINSTRUCTIONSandINSTALLATIONMANUALbeforeoperation.
FurtherinformationisavailableintheOPERATINGINSTRUCTIONS,INSTALLATIONMANUAL,andthelike.
Phillips screwdriver
Level
Scale
Utilityknifeorscissors
Torque wrench
Wrench(orspanner)
4mmhexagonalwrench
FlaretoolforR32,R410A
GaugemanifoldforR32,R410A
VacuumpumpforR32,R410A
ChargehoseforR32,R410A
Pipecutterwithreamer