
20
OCH784
Check code
Abnormal point and detection method Cause Countermeasure
P9
Pipe temperature thermistor/
Condenser-Evaporator (TH5)
1The unit is in 3-minute resume protec-
tion mode if short/open of thermistor is
detected. Abnormal if the unit does not
get back to normal within 3 minutes. (The
unit returns to normal operation, if it has
been reset normally.)
2Constantly detected during cooling,
drying, and heating operation (except
defrosting)
Short: 90:or more
Open: −40:or less
1Defective thermistor
characteristics
2Contact failure of connector
(CN44) on the indoor controller
board (Insert failure)
3Breaking of wire or contact
failure of thermistor wiring
4Temperature of thermistor is
90: or more, or −40:or less
caused by defective refrigerant
circuit.
5Defective indoor controller
board
1–3 Check resistance value of thermistor.
For characteristics, refer to (P1).
2Check contact failure of connector (CN44)
on the indoor controller board.
Refer to "9-7. TEST POINT DIAGRAM".
Turn the power on and check restart after
inserting connector again.
4Operate in test run mode and check pipe
<condenser/evaporator> temperature with
outdoor controller circuit board. If pipe <con-
denser/evaporator> temperature is extremely
low (in cooling mode) or high (in heating
mode), refrigerant circuit may have defect.
5Operate in test run mode and check pipe
<condenser/evaporator> temperature
with outdoor control circuit board. If there
is extreme difference with actual pipe
<condenser / evaporator> temperature,
replace indoor controller board.
There is no abnormality if none of above
comes within the unit.
Turn the power off, and on again to operate.
E0
or
E4
Remote controller transmission
error(E0)/signal receiving error(E4)
1Abnormal if main or sub remote con-
troller cannot receive any transmission
normally from indoor unit of refrigerant
address “0” for 3 minutes.
(Check code : E0)
2Abnormal if sub remote controller could
not receive any signal for 2 minutes.
(Check code: E0)
1Abnormal if indoor controller board can
not receive any data normally from
remote controller board or from other
indoor controller board for 3 minutes.
(Check code: E4)
2Indoor controller board cannot receive
any signal from remote controller for 2
minutes. (Check code: E4)
1Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2Set one of the remote controllers “main”
if there is no problem with the action above.
3Check wiring of remote controller.
• The number of connecting indoor units:
max. 16 units
• The number of connecting remote control-
ler: max. 2 units
• Total wiring length:
When one remote controller is connected:
max. 500 m
When two remote controllers are connect-
ed: 200m
(Do not use a multicore cable.)
If the cause of trouble is not any of 1–3above,
4Diagnose remote controllers.
a) When “OK” is displayed,
Remote controllers have no problem.
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
b) When “NG” is displayed,
Replace remote controller.
c) When “E3” or “ERC” is displayed, noise
may be causing abnormality.
Note: If the unit is not normal after replacing
indoor controller board in group control, indoor
controller board of address “0” may be abnor-
mal.
E3
or
E5
Remote controller transmission
error(E3)/signal receiving error(E5)
1Abnormal if remote controller could not
find blank of transmission path for 6 sec-
onds and could not transmit.
(Check code: E3)
2Remote controller receives transmitted
data at the same time and compares the
received and transmitted data. Abnormal
if these data are judged to be different 30
continuous times. (Check code: E3)
1Abnormal if indoor controller board could
not find blank of transmission path.
(Check code: E5)
2Indoor controller board receives trans-
mitted data at the same time and com-
pares the received and transmitted data.
Abnormal if these data are judged to be
different 30 continuous times. (Check
code: E5)
1Set a remote controller to main, and the
other to sub.
2Remote controller is connected with only
one indoor unit.
3The address changes to a separate setting.
4–6 Diagnose remote controller.
a) When “OK” is displayed, remote control-
lers have no problem.
Turn the power off,and on again to check.
When becoming abnormal again, replace
indoor controller board.
b) When “NG” is displayed, replace remote
controller.
c) When “E3” or “ERC” is displayed, noise
may be causing abnormality.
1Contact failure at transmission
wire of remote controller
2All remote controllers are set as
“sub” remote controller. In this
case, E0 is displayed on remote
controller, and E4 is displayed
at LED (LED1, LED2) on the
outdoor controller circuit board.
3Miswiring of remote controller
4Defective transmitting receiving
circuit of remote controller
5Defective transmitting receiving
circuit of indoor controller board
of refrigerant addresses “0”.
6Noise has entered into the
transmission wire of remote
controller.
12 remote controllers are set as
“main.”
(In case of 2 remote con-
trollers)
2Remote controller is connected
with 2 indoor units or more.
3Repetition of refrigerant
address
4Defective transmitting receiving
circuit of remote controller
5Defective transmitting receiving
circuit of indoor controller board
6Noise has entered into trans-
mission wire of remote control-
ler.
In case of checking pipe temperature
with outdoor controller circuit board,
be sure to connect A-control service
tool (PAC-SK52ST).
()