FX2N-485-BD
USER’S GUIDE
JY992D74401D
This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the FX2N-485-BD (hereafter abbreviated to "485BD") and should be
read and understood before attempting to install or use the unit. Further information can be found in the
associated manuals mentioned below.
Specifications are subject to change without notice
Safety guidelines for the user and protection of the FX
2N
-485-BD.
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c) All operators of the completed equipment should be trained to use this product in a safe and
coordinated manner in compliance to established safety practices.
Note: The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.
Notes on the Symbols Used in this Manual
At various times throughout this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property
damage.
• Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for the actual use of
the product based on these illustrative examples.
• Please contact a Mitsubishi distributor for more information concerning applications in life critical
situations or high reliability.
Associated Manuals
PROGRAMMING MANUAL, PROGRAMMING MANUAL ΙΙ, or FX Series User’s Manual - Data
Communication Edition mentioned below are not provided in sets with a product.
Contact our agent where the product was purchased to request the manuals accordingly.
★Indispensable manual
Manual Name Manual
Number Description
★FX Series User's Manual - Data
Communication Edition JY997D16901
Describes contents related to communication
available in FX Series PLC such as wiring,
communication setting, and program examples.
★FX2N HARDWARE MANUAL JY992D66301
Describes contents related to hardware of FX2N
Series PLC such as specifications, wiring, and
installation.
★PROGRAMMING MANUAL ΙΙ JY992D88101 Describes contents related to instruction in FX1S/
FX1N/FX2N/FX2NC Series PLC.
This manual describes the installation the and specifications of the 485BD.
For details on wiring (including use of terminal resistor and preparation of cable) with communication equipment,
system configuration and communication setting, and program examples, refer to the "FX Series User's Manual - Data
Communication Edition".
1. Outline of Product
The 485BD is an insulated RS-485 communication board with an European type terminal block.
Connected to the main unit of the FX2N Series PLC, it enables signal exchange between the PLC and
equipment via an RS-485 port.
1.1 Communication Functions and Applicable PLC
(Available in indicated version or later)
1.2 Outside dimensions and name of each part
Unit: mm (inches)
Accessories: Terminal resistor 330Ω2
Terminal resistor 110Ω1
M3 screw to mount board 2
Station No. label for link
➀Mounting hole (2-φ3.5)
➁Terminal block for RS-485 equipment
The top face of this terminal box is higher than the top face
of the PLC panel cover by approximately 7 mm (0.27").
➂SD LED: Flickers at high speed during send.
➃RD LED: Flickers at high speed during receive.
➄Connector for PLC
1.3 System configuration
Only one function expansion board can be used for one main unit of FX2N.
FX2N-485-BD cannot be used by the plural. Other expansion boards cannot be used together with
FX2N-485-BD.For the system configuration, refer to the FX Series User's Manual - Data Communication
Edition offered separately.
2. Installation
Caution
• Use in the environments specified under the general specification in the manual.
Do not use the product in environments with excessive or conductive dust, corrosive or
flammable gas, oily smoke, moisture or rain, excessive heat, regular impact shocks or
excessive vibration, as it may result in electrical shock, fire, malfunction, damage or
deterioration on the product.
• Make sure to shut off the power outside the product before installing or wiring it.
Otherwise, electric shock or serious damage to on the product may occur.
• Never drop wire chips or shavings into the vent slits when drilling screw holes or performing
wiring, as they may cause fire, breakdown, or malfunction.
Securely install the 485BD to the designated port.
Poor connection may cause malfunction.
2.1 Installation procedure
Turn off the power of the programmable controller, and mount the
485BD using the following procedure.
➀Remove the panel cover from the top face of the base unit.
➁Connect the connector for programmable controller provided on
the 485BD to the board mounting connector provided on the
base unit.
➂Fix the 485BD to the base unit using the M3 self-tapping screws
supplied. Tightening torque: 0.3 to 0.6 Nym
➃Remove the cut out on the left of the panel cover using a tool
such as nippers or cutters so that the terminal block is
accessible. The top face of this terminal block is higher than the
top face of the panel cover of the programmable controller by
approximately 7 mm (0.27").
Communication
type FX2N Function
N:N network V2.00 Data transfer connecting up to eight FX Series PLCs.
Parallel link V1.04 Data transfer between two PLCs relationship specifying master/slave station.
Computer link V1.06 Data transfer via link protocol between PLC and computer (specified as the master
station).
No protocol
communication V1.06 Serial communication without protocol between PLC and equipment via RS-485
interface.
Inverter
communication V3.00 Controlling Mitsubishi's FREQROL inverter using EXTR instruction in function
expansion memory.
0.6mm
(0.02")
3.5mm
(0.13")
The end
should be
straight.
Recommended screwdriver to
tighten terminal screws
35(1.38")
39(1.54")
52(2.05")
46(1.81")
23
1
45

" & # * ,
!
"
3. Specifications
3.1 Environmental specifications
The environmental specifications are equivalent to those of the PLC main unit.
(Refer to the manual of the PLC main unit.)
3.2 Power supply specifications
5V DC, 60 mA is supplied as the power from the PLC.
3.3 Performance specifications
Item Description
Transmission standard In conformance to RS-485 and RS-422
Maximum transmission
distance 50m (164ft) maximum
Communication type No protocol communication, Computer link (dedicated protocol),
parallel link, N:N network
Communication method Full-duplex (When the version of PLC(FX2N) is Ver. 2.00 or later) /
Half-duplex (When the version of PLC(FX2N) is earlier than Ver. 2.00)
Communication
procedure
No protocol communication, Computer link (dedicated protocol 1,
dedicated protocol 4), parallel link, N:N network
Transmission speed
(baud rate)
No protocol communication, Computer link (dedicated protocol):
300/600/1200/2400/4800/9600/19200 (bps)
Parallel link: 19200(bps)
N:N network: 38400(bps)
Insulation None
Manual number : JY992D74401
Manual revision : D
Date : AUGUST 2006
Side
A
Side
BJAPANESE ENGLISH
Side
B
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any
patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving
industrial property rights which may occur as a result of using the contents noted in this manual.
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
FX2N-485-BD
USER’S GUIDE
JY992D74401D
This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the FX2N-485-BD (hereafter abbreviated to "485BD") and should be
read and understood before attempting to install or use the unit. Further information can be found in the
associated manuals mentioned below.
Specifications are subject to change without notice
Safety guidelines for the user and protection of the FX
2N
-485-BD.
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c) All operators of the completed equipment should be trained to use this product in a safe and
coordinated manner in compliance to established safety practices.
Note: The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.
Notes on the Symbols Used in this Manual
At various times throughout this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property
damage.
• Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for the actual use of
the product based on these illustrative examples.
• Please contact a Mitsubishi distributor for more information concerning applications in life critical
situations or high reliability.
Associated Manuals
PROGRAMMING MANUAL, PROGRAMMING MANUAL ΙΙ, or FX Series User’s Manual - Data
Communication Edition mentioned below are not provided in sets with a product.
Contact our agent where the product was purchased to request the manuals accordingly.
★Indispensable manual
Manual Name Manual
Number Description
★FX Series User's Manual - Data
Communication Edition JY997D16901
Describes contents related to communication
available in FX Series PLC such as wiring,
communication setting, and program examples.
★FX2N HARDWARE MANUAL JY992D66301
Describes contents related to hardware of FX2N
Series PLC such as specifications, wiring, and
installation.
★PROGRAMMING MANUAL ΙΙ JY992D88101 Describes contents related to instruction in FX1S/
FX1N/FX2N/FX2NC Series PLC.
This manual describes the installation the and specifications of the 485BD.
For details on wiring (including use of terminal resistor and preparation of cable) with communication equipment,
system configuration and communication setting, and program examples, refer to the "FX Series User's Manual - Data
Communication Edition".
1. Outline of Product
The 485BD is an insulated RS-485 communication board with an European type terminal block.
Connected to the main unit of the FX2N Series PLC, it enables signal exchange between the PLC and
equipment via an RS-485 port.
1.1 Communication Functions and Applicable PLC
(Available in indicated version or later)
1.2 Outside dimensions and name of each part
Unit: mm (inches)
Accessories: Terminal resistor 330Ω2
Terminal resistor 110Ω1
M3 screw to mount board 2
Station No. label for link
➀Mounting hole (2-φ3.5)
➁Terminal block for RS-485 equipment
The top face of this terminal box is higher than the top face
of the PLC panel cover by approximately 7 mm (0.27").
➂SD LED: Flickers at high speed during send.
➃RD LED: Flickers at high speed during receive.
➄Connector for PLC
1.3 System configuration
Only one function expansion board can be used for one main unit of FX2N.
FX2N-485-BD cannot be used by the plural. Other expansion boards cannot be used together with
FX2N-485-BD.For the system configuration, refer to the FX Series User's Manual - Data Communication
Edition offered separately.
2. Installation
Caution
• Use in the environments specified under the general specification in the manual.
Do not use the product in environments with excessive or conductive dust, corrosive or
flammable gas, oily smoke, moisture or rain, excessive heat, regular impact shocks or
excessive vibration, as it may result in electrical shock, fire, malfunction, damage or
deterioration on the product.
• Make sure to shut off the power outside the product before installing or wiring it.
Otherwise, electric shock or serious damage to on the product may occur.
• Never drop wire chips or shavings into the vent slits when drilling screw holes or performing
wiring, as they may cause fire, breakdown, or malfunction.
Securely install the 485BD to the designated port.
Poor connection may cause malfunction.
2.1 Installation procedure
Turn off the power of the programmable controller, and mount the
485BD using the following procedure.
➀Remove the panel cover from the top face of the base unit.
➁Connect the connector for programmable controller provided on
the 485BD to the board mounting connector provided on the
base unit.
➂Fix the 485BD to the base unit using the M3 self-tapping screws
supplied. Tightening torque: 0.3 to 0.6 Nym
➃Remove the cut out on the left of the panel cover using a tool
such as nippers or cutters so that the terminal block is
accessible. The top face of this terminal block is higher than the
top face of the panel cover of the programmable controller by
approximately 7 mm (0.27").
Communication
type FX2N Function
N:N network V2.00 Data transfer connecting up to eight FX Series PLCs.
Parallel link V1.04 Data transfer between two PLCs relationship specifying master/slave station.
Computer link V1.06 Data transfer via link protocol between PLC and computer (specified as the master
station).
No protocol
communication V1.06 Serial communication without protocol between PLC and equipment via RS-485
interface.
Inverter
communication V3.00 Controlling Mitsubishi's FREQROL inverter using EXTR instruction in function
expansion memory.
0.6mm
(0.02")
3.5mm
(0.13")
The end
should be
straight.
Recommended screwdriver to
tighten terminal screws
35(1.38")
39(1.54")
52(2.05")
46(1.81")
23
1
45

" & # * ,
!
"
3. Specifications
3.1 Environmental specifications
The environmental specifications are equivalent to those of the PLC main unit.
(Refer to the manual of the PLC main unit.)
3.2 Power supply specifications
5V DC, 60 mA is supplied as the power from the PLC.
3.3 Performance specifications
Item Description
Transmission standard In conformance to RS-485 and RS-422
Maximum transmission
distance 50m (164ft) maximum
Communication type No protocol communication, Computer link (dedicated protocol),
parallel link, N:N network
Communication method Full-duplex (When the version of PLC(FX2N) is Ver. 2.00 or later) /
Half-duplex (When the version of PLC(FX2N) is earlier than Ver. 2.00)
Communication
procedure
No protocol communication, Computer link (dedicated protocol 1,
dedicated protocol 4), parallel link, N:N network
Transmission speed
(baud rate)
No protocol communication, Computer link (dedicated protocol):
300/600/1200/2400/4800/9600/19200 (bps)
Parallel link: 19200(bps)
N:N network: 38400(bps)
Insulation None
Manual number : JY992D74401
Manual revision : D
Date : AUGUST 2006
Side
A
Side
BJAPANESE ENGLISH
Side
B
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any
patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving
industrial property rights which may occur as a result of using the contents noted in this manual.
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
FX2N-485-BD
USER’S GUIDE
JY992D74401D
This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the FX2N-485-BD (hereafter abbreviated to "485BD") and should be
read and understood before attempting to install or use the unit. Further information can be found in the
associated manuals mentioned below.
Specifications are subject to change without notice
Safety guidelines for the user and protection of the FX
2N
-485-BD.
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c) All operators of the completed equipment should be trained to use this product in a safe and
coordinated manner in compliance to established safety practices.
Note: The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.
Notes on the Symbols Used in this Manual
At various times throughout this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property
damage.
• Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for the actual use of
the product based on these illustrative examples.
• Please contact a Mitsubishi distributor for more information concerning applications in life critical
situations or high reliability.
Associated Manuals
PROGRAMMING MANUAL, PROGRAMMING MANUAL ΙΙ, or FX Series User’s Manual - Data
Communication Edition mentioned below are not provided in sets with a product.
Contact our agent where the product was purchased to request the manuals accordingly.
★Indispensable manual
Manual Name Manual
Number Description
★FX Series User's Manual - Data
Communication Edition JY997D16901
Describes contents related to communication
available in FX Series PLC such as wiring,
communication setting, and program examples.
★FX2N HARDWARE MANUAL JY992D66301
Describes contents related to hardware of FX2N
Series PLC such as specifications, wiring, and
installation.
★PROGRAMMING MANUAL ΙΙ JY992D88101 Describes contents related to instruction in FX1S/
FX1N/FX2N/FX2NC Series PLC.
This manual describes the installation the and specifications of the 485BD.
For details on wiring (including use of terminal resistor and preparation of cable) with communication equipment,
system configuration and communication setting, and program examples, refer to the "FX Series User's Manual - Data
Communication Edition".
1. Outline of Product
The 485BD is an insulated RS-485 communication board with an European type terminal block.
Connected to the main unit of the FX2N Series PLC, it enables signal exchange between the PLC and
equipment via an RS-485 port.
1.1 Communication Functions and Applicable PLC
(Available in indicated version or later)
1.2 Outside dimensions and name of each part
Unit: mm (inches)
Accessories: Terminal resistor 330Ω2
Terminal resistor 110Ω1
M3 screw to mount board 2
Station No. label for link
➀Mounting hole (2-φ3.5)
➁Terminal block for RS-485 equipment
The top face of this terminal box is higher than the top face
of the PLC panel cover by approximately 7 mm (0.27").
➂SD LED: Flickers at high speed during send.
➃RD LED: Flickers at high speed during receive.
➄Connector for PLC
1.3 System configuration
Only one function expansion board can be used for one main unit of FX2N.
FX2N-485-BD cannot be used by the plural. Other expansion boards cannot be used together with
FX2N-485-BD.For the system configuration, refer to the FX Series User's Manual - Data Communication
Edition offered separately.
2. Installation
Caution
• Use in the environments specified under the general specification in the manual.
Do not use the product in environments with excessive or conductive dust, corrosive or
flammable gas, oily smoke, moisture or rain, excessive heat, regular impact shocks or
excessive vibration, as it may result in electrical shock, fire, malfunction, damage or
deterioration on the product.
• Make sure to shut off the power outside the product before installing or wiring it.
Otherwise, electric shock or serious damage to on the product may occur.
• Never drop wire chips or shavings into the vent slits when drilling screw holes or performing
wiring, as they may cause fire, breakdown, or malfunction.
Securely install the 485BD to the designated port.
Poor connection may cause malfunction.
2.1 Installation procedure
Turn off the power of the programmable controller, and mount the
485BD using the following procedure.
➀Remove the panel cover from the top face of the base unit.
➁Connect the connector for programmable controller provided on
the 485BD to the board mounting connector provided on the
base unit.
➂Fix the 485BD to the base unit using the M3 self-tapping screws
supplied. Tightening torque: 0.3 to 0.6 Nym
➃Remove the cut out on the left of the panel cover using a tool
such as nippers or cutters so that the terminal block is
accessible. The top face of this terminal block is higher than the
top face of the panel cover of the programmable controller by
approximately 7 mm (0.27").
Communication
type FX2N Function
N:N network V2.00 Data transfer connecting up to eight FX Series PLCs.
Parallel link V1.04 Data transfer between two PLCs relationship specifying master/slave station.
Computer link V1.06 Data transfer via link protocol between PLC and computer (specified as the master
station).
No protocol
communication V1.06 Serial communication without protocol between PLC and equipment via RS-485
interface.
Inverter
communication V3.00 Controlling Mitsubishi's FREQROL inverter using EXTR instruction in function
expansion memory.
0.6mm
(0.02")
3.5mm
(0.13")
The end
should be
straight.
Recommended screwdriver to
tighten terminal screws
35(1.38")
39(1.54")
52(2.05")
46(1.81")
23
1
45

" & # * ,
!
"
3. Specifications
3.1 Environmental specifications
The environmental specifications are equivalent to those of the PLC main unit.
(Refer to the manual of the PLC main unit.)
3.2 Power supply specifications
5V DC, 60 mA is supplied as the power from the PLC.
3.3 Performance specifications
Item Description
Transmission standard In conformance to RS-485 and RS-422
Maximum transmission
distance 50m (164ft) maximum
Communication type No protocol communication, Computer link (dedicated protocol),
parallel link, N:N network
Communication method Full-duplex (When the version of PLC(FX2N) is Ver. 2.00 or later) /
Half-duplex (When the version of PLC(FX2N) is earlier than Ver. 2.00)
Communication
procedure
No protocol communication, Computer link (dedicated protocol 1,
dedicated protocol 4), parallel link, N:N network
Transmission speed
(baud rate)
No protocol communication, Computer link (dedicated protocol):
300/600/1200/2400/4800/9600/19200 (bps)
Parallel link: 19200(bps)
N:N network: 38400(bps)
Insulation None
Manual number : JY992D74401
Manual revision : D
Date : AUGUST 2006
Side
A
Side
BJAPANESE ENGLISH
Side
B
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any
patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving
industrial property rights which may occur as a result of using the contents noted in this manual.
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
FX2N-485-BD
USER’S GUIDE
JY992D74401D
This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the FX2N-485-BD (hereafter abbreviated to "485BD") and should be
read and understood before attempting to install or use the unit. Further information can be found in the
associated manuals mentioned below.
Specifications are subject to change without notice
Safety guidelines for the user and protection of the FX
2N
-485-BD.
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c) All operators of the completed equipment should be trained to use this product in a safe and
coordinated manner in compliance to established safety practices.
Note: The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.
Notes on the Symbols Used in this Manual
At various times throughout this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property
damage.
• Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
• All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for the actual use of
the product based on these illustrative examples.
• Please contact a Mitsubishi distributor for more information concerning applications in life critical
situations or high reliability.
Associated Manuals
PROGRAMMING MANUAL, PROGRAMMING MANUAL ΙΙ, or FX Series User’s Manual - Data
Communication Edition mentioned below are not provided in sets with a product.
Contact our agent where the product was purchased to request the manuals accordingly.
★Indispensable manual
Manual Name Manual
Number Description
★FX Series User's Manual - Data
Communication Edition JY997D16901
Describes contents related to communication
available in FX Series PLC such as wiring,
communication setting, and program examples.
★FX2N HARDWARE MANUAL JY992D66301
Describes contents related to hardware of FX2N
Series PLC such as specifications, wiring, and
installation.
★PROGRAMMING MANUAL ΙΙ JY992D88101 Describes contents related to instruction in FX1S/
FX1N/FX2N/FX2NC Series PLC.
This manual describes the installation the and specifications of the 485BD.
For details on wiring (including use of terminal resistor and preparation of cable) with communication equipment,
system configuration and communication setting, and program examples, refer to the "FX Series User's Manual - Data
Communication Edition".
1. Outline of Product
The 485BD is an insulated RS-485 communication board with an European type terminal block.
Connected to the main unit of the FX2N Series PLC, it enables signal exchange between the PLC and
equipment via an RS-485 port.
1.1 Communication Functions and Applicable PLC
(Available in indicated version or later)
1.2 Outside dimensions and name of each part
Unit: mm (inches)
Accessories: Terminal resistor 330Ω2
Terminal resistor 110Ω1
M3 screw to mount board 2
Station No. label for link
➀Mounting hole (2-φ3.5)
➁Terminal block for RS-485 equipment
The top face of this terminal box is higher than the top face
of the PLC panel cover by approximately 7 mm (0.27").
➂SD LED: Flickers at high speed during send.
➃RD LED: Flickers at high speed during receive.
➄Connector for PLC
1.3 System configuration
Only one function expansion board can be used for one main unit of FX2N.
FX2N-485-BD cannot be used by the plural. Other expansion boards cannot be used together with
FX2N-485-BD.For the system configuration, refer to the FX Series User's Manual - Data Communication
Edition offered separately.
2. Installation
Caution
• Use in the environments specified under the general specification in the manual.
Do not use the product in environments with excessive or conductive dust, corrosive or
flammable gas, oily smoke, moisture or rain, excessive heat, regular impact shocks or
excessive vibration, as it may result in electrical shock, fire, malfunction, damage or
deterioration on the product.
• Make sure to shut off the power outside the product before installing or wiring it.
Otherwise, electric shock or serious damage to on the product may occur.
• Never drop wire chips or shavings into the vent slits when drilling screw holes or performing
wiring, as they may cause fire, breakdown, or malfunction.
Securely install the 485BD to the designated port.
Poor connection may cause malfunction.
2.1 Installation procedure
Turn off the power of the programmable controller, and mount the
485BD using the following procedure.
➀Remove the panel cover from the top face of the base unit.
➁Connect the connector for programmable controller provided on
the 485BD to the board mounting connector provided on the
base unit.
➂Fix the 485BD to the base unit using the M3 self-tapping screws
supplied. Tightening torque: 0.3 to 0.6 Nym
➃Remove the cut out on the left of the panel cover using a tool
such as nippers or cutters so that the terminal block is
accessible. The top face of this terminal block is higher than the
top face of the panel cover of the programmable controller by
approximately 7 mm (0.27").
Communication
type FX2N Function
N:N network V2.00 Data transfer connecting up to eight FX Series PLCs.
Parallel link V1.04 Data transfer between two PLCs relationship specifying master/slave station.
Computer link V1.06 Data transfer via link protocol between PLC and computer (specified as the master
station).
No protocol
communication V1.06 Serial communication without protocol between PLC and equipment via RS-485
interface.
Inverter
communication V3.00 Controlling Mitsubishi's FREQROL inverter using EXTR instruction in function
expansion memory.
0.6mm
(0.02")
3.5mm
(0.13")
The end
should be
straight.
Recommended screwdriver to
tighten terminal screws
35(1.38")
39(1.54")
52(2.05")
46(1.81")
23
1
45

" & # * ,
!
"
3. Specifications
3.1 Environmental specifications
The environmental specifications are equivalent to those of the PLC main unit.
(Refer to the manual of the PLC main unit.)
3.2 Power supply specifications
5V DC, 60 mA is supplied as the power from the PLC.
3.3 Performance specifications
Item Description
Transmission standard In conformance to RS-485 and RS-422
Maximum transmission
distance 50m (164ft) maximum
Communication type No protocol communication, Computer link (dedicated protocol),
parallel link, N:N network
Communication method Full-duplex (When the version of PLC(FX2N) is Ver. 2.00 or later) /
Half-duplex (When the version of PLC(FX2N) is earlier than Ver. 2.00)
Communication
procedure
No protocol communication, Computer link (dedicated protocol 1,
dedicated protocol 4), parallel link, N:N network
Transmission speed
(baud rate)
No protocol communication, Computer link (dedicated protocol):
300/600/1200/2400/4800/9600/19200 (bps)
Parallel link: 19200(bps)
N:N network: 38400(bps)
Insulation None
Manual number : JY992D74401
Manual revision : D
Date : AUGUST 2006

Other Mitsubishi Controllers manuals

Mitsubishi MELSEC A1SCPUC24-R2 Instructions for use

Mitsubishi

Mitsubishi MELSEC A1SCPUC24-R2 Instructions for use

Mitsubishi A2CCPU User manual

Mitsubishi

Mitsubishi A2CCPU User manual

Mitsubishi a2 Series Owner's manual

Mitsubishi

Mitsubishi a2 Series Owner's manual

Mitsubishi FX3G-14MR/ES User manual

Mitsubishi

Mitsubishi FX3G-14MR/ES User manual

Mitsubishi MELSEC-K User manual

Mitsubishi

Mitsubishi MELSEC-K User manual

Mitsubishi QCPU (Q Mode) User manual

Mitsubishi

Mitsubishi QCPU (Q Mode) User manual

Mitsubishi melservo-j2 series User manual

Mitsubishi

Mitsubishi melservo-j2 series User manual

Mitsubishi AJ65BT-64RD3 User manual

Mitsubishi

Mitsubishi AJ65BT-64RD3 User manual

Mitsubishi Melsec FX-4AD User manual

Mitsubishi

Mitsubishi Melsec FX-4AD User manual

Mitsubishi MELSEC Q Series Owner's manual

Mitsubishi

Mitsubishi MELSEC Q Series Owner's manual

Mitsubishi MELSEC L Series User manual

Mitsubishi

Mitsubishi MELSEC L Series User manual

Mitsubishi MELSEC-WS0-CPU0 User manual

Mitsubishi

Mitsubishi MELSEC-WS0-CPU0 User manual

Mitsubishi FX2N-64CL-M User manual

Mitsubishi

Mitsubishi FX2N-64CL-M User manual

Mitsubishi MELSEC-F FX1N-40MT-001 User manual

Mitsubishi

Mitsubishi MELSEC-F FX1N-40MT-001 User manual

Mitsubishi A1SD75P1-S3 User manual

Mitsubishi

Mitsubishi A1SD75P1-S3 User manual

Mitsubishi FX3G-4EX-BD User manual

Mitsubishi

Mitsubishi FX3G-4EX-BD User manual

Mitsubishi MELSEC Q Series User manual

Mitsubishi

Mitsubishi MELSEC Q Series User manual

Mitsubishi AJ65SBT2B-64RD3 User manual

Mitsubishi

Mitsubishi AJ65SBT2B-64RD3 User manual

Mitsubishi MELSEC Q Series User manual

Mitsubishi

Mitsubishi MELSEC Q Series User manual

Mitsubishi FX3G Series User manual

Mitsubishi

Mitsubishi FX3G Series User manual

Mitsubishi A Series User manual

Mitsubishi

Mitsubishi A Series User manual

Mitsubishi AL-6MR-A User manual

Mitsubishi

Mitsubishi AL-6MR-A User manual

Mitsubishi AG-150A User manual

Mitsubishi

Mitsubishi AG-150A User manual

Mitsubishi FX3U-485ADP(-MB) User manual

Mitsubishi

Mitsubishi FX3U-485ADP(-MB) User manual

Popular Controllers manuals by other brands

IPCO STUDIO 3000 operating instructions

IPCO

IPCO STUDIO 3000 operating instructions

National Instruments NI PXIe-8840 installation guide

National Instruments

National Instruments NI PXIe-8840 installation guide

Sentera Controls RDCV Mounting and operating instructions

Sentera Controls

Sentera Controls RDCV Mounting and operating instructions

Wisi TOPLINE HEADEND OV 51S Mounting instructions

Wisi

Wisi TOPLINE HEADEND OV 51S Mounting instructions

Leviton 6616 installation guide

Leviton

Leviton 6616 installation guide

Huawei SUN2000-20KTL-M3 quick guide

Huawei

Huawei SUN2000-20KTL-M3 quick guide

Bosch E2800 installation manual

Bosch

Bosch E2800 installation manual

InTecMa SimpleStarter SST330i user manual

InTecMa

InTecMa SimpleStarter SST330i user manual

BLAUBERG Ventilatoren SGS E1 quick start guide

BLAUBERG Ventilatoren

BLAUBERG Ventilatoren SGS E1 quick start guide

Gewiss Chorus GWA1521 Technical manual

Gewiss

Gewiss Chorus GWA1521 Technical manual

BERMAD Omega Installation and operation guide

BERMAD

BERMAD Omega Installation and operation guide

Biamp ALC-404D Installation & operation guide

Biamp

Biamp ALC-404D Installation & operation guide

Lumel RE62 User Manual & Quick Start

Lumel

Lumel RE62 User Manual & Quick Start

Rosslare AC-225? AC-225IP? AC-225U quick guide

Rosslare

Rosslare AC-225? AC-225IP? AC-225U quick guide

Timotion TBB5 user manual

Timotion

Timotion TBB5 user manual

Mitsubishi Electric PAC-YG66DCA instruction manual

Mitsubishi Electric

Mitsubishi Electric PAC-YG66DCA instruction manual

Emerson Dixell WING XW264K Installing and operating instructions

Emerson

Emerson Dixell WING XW264K Installing and operating instructions

NAPCO NP-AMOD8 instructions

NAPCO

NAPCO NP-AMOD8 instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.