testing. Irreparable damage will occur if this instruction is not followed.
product.
•Connect the luminaire to the mains supply via a suitable junction box (not supplied) ensuring the
correct polarity is observed: L - Live (brown), N - Neutral (blue) (see Fig. 3)
Fig. 3
•Connect the battery via the plug and socket to the inverter
•Place the battery and inverter into the ceiling void ensuring that there is at least 50mm of clearance
above and around them
•Lift both of the spring clips on the sides of the luminaire and push into the ceiling
•Switch on and check for correct operation, ensuring the green indicator LED is illuminated
•We recommend, on commissioning the installation, a minimum charge period of 24-36 hours before
carrying out an emergency duration test
•If the batteries have been left in a discharged state for an extended period, we recommend that one or
more charge and discharge cycles are completed which should help to restore the battery capacity
WARNING
This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole
luminaire should be replaced.
Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the
product.
Installing in areas where the temperature consistently drops below 0°C may shorten the battery life.
This product is non-dimmable.
This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities
for where facilities exist.
The batteries in this luminaire are Nickel Cadmium and must be disposed of correctly. Please contact the local
authorities for the disposal of this toxic waste.
WARRANTY
This product has a warranty of 3 years (excluding battery) from date of purchase. Failure to install this product
in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the
batch code will invalidate the warranty. If this product should fail within its warranty period, it should be returned
to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for
any installation costs associated with the replacement product. Your statutory rights are not affected. ML
Accessories reserve the right to alter product specification without prior notice.
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
•Daily check – check LED charge indicator is illuminated
•Monthly functional test - simulate a mains supply failure for approx. 30 seconds by operation of key switch
or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is
illuminated
•Annual three hour duration test - simulate a mains supply failure for three hour continuous test by operation
of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge
indicator is illuminated
•If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test record
sheet
Fig. 3